| 2007-09-19 13:06:28 | *** NOTES ADDED** |
| | |
| | **) PLEASE SEE NOTES ADDED UNDER BUILDING #3 FOR FIRE |
| | PUMP. |
| | **) PLEASE SEE NOTES ADDED UNDER BUILDIGN#3 FOR |
| | POSSIBLE CONCERNS WITH EGRESS LIGHITNG FROM UNITS, B4, |
| | C-3 SPIRAL STAIRS.MAY NOT USE SWITCHED RECEPTACLE. |
| | THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW AS THESE |
| | AREAS AND USE IS NOW MORE CLEAR. |
| | **) PLEASE SEE NOTES ON ELECTRICAL RISER NEEDS TO MEET |
| | AND CORRELATE WITH RISER. EXAMPLE, SEE NOTE #10 WHICH |
| | MENTIONS POWER COMPANY TO INSTALL CONDUCTORS, HOWEVER |
| | PLEASE KNOW THE POWER COMPANY DOES NOT TYPICALLY |
| | INSTALL CONDUCTORS AFTER METERING DEVICES. |
| 2007-09-18 08:12:07 | 2007-09-18 08:12:07 |
| | |
| | ** DENIED 3RD REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE |
| | THERE ARE SOME NEW COMMENTS BASED ON REVISED |
| | PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. |
| | ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER |
| | SOME CAN NOT BE AT THIS TIME. |
| | |
| | 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE |
| | DESIGNATIONS FOR ALL LIGHTING. |
| | PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL |
| | PLANS COULD NOT BE FOUND. |
| | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR |
| | EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS. |
| | THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT |
| | STATED ON THE IDR AS ON PLANS. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE |
| | INPUT DATA REPORT DOES NOT CORRELATE WITH ALL |
| | ELECTRICAL LIGHTING WHICH IS ON PLANS. PLEASE SEE |
| | MISSING A SUBSTANTIAL AMOUNT OF LIGHTING ON THE INPUT |
| | DATE REPORT. |
| | 13-415.0, 415.1.ABCD, 415.1.A, 415.2 |
| | |
| | 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY |
| | CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS |
| | AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO |
| | SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED |
| | SEALED OR ORIGINAL SIGNATURE. |
| | **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN |
| | PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS |
| | JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS |
| | 1 AND 3. |
| | PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES |
| | SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD |
| | OF ENGINEERS. |
| | THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE |
| | FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC |
| | 61G15-23.002., FBC 103.1. |
| | ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED |
| | THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND |
| | NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA |
| | FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004 |
| | FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY |
| | AND AS REQUIRED. |
| | |
| | |
| | 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES |
| | DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION. |
| | PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER |
| | BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE |
| | PERMITS, PLANS AND FEES. |
| | PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED |
| | ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL |
| | NEED TO BE CORRECTED. |
| | |
| | 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES |
| | *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN |
| | ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE |
| | ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME |
| | SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 |
| | |
| | 5) NOTE: PLEASE SEE SHEET E16.04 AS THE MAIL ROOM DOES |
| | NOT CONTAIN ANY DOORS, OPENINGS, OR LIGHTING. PLEASE |
| | SEE THE SHEET A1.30 DOES NOT INDICATE THE SAME LAYOUT |
| | FOR THIS AREA. PLEASE CORRELATE THE TWO AS THESE |
| | LAYOUTS DO NOT MATCH AT THIS TIME. |
| | PLEASE SEE ANY CHANGES IN LIGHTING ETC. |
| | FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION AND COORDINATION OF PLANS. |
| | |
| | 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS |
| | BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE |
| | HARDWIRED? |
| | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING |
| | MEANS. |
| | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD |
| | PLUG IN? |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-16 13:36:05 | 2007-09-16 13:36:05 |
| | |
| | REVIEW TO CONTINUE ON 9/17> REVIEWNOTES TO FOLLOW |
| | ONCE REVIEW IS COMPLETED. |
| | THERE WILL BE ITEMS THAT NEED TO BE ADDRESSED. |
| 2007-09-16 13:01:25 | 2007-09-16 13:01:25 |
| | |
| | IN ELEC FOR REVIEW |