Plan Review Notes
Plan Review Notes For Permit 05091686
Permit Number 05091686
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-19 13:06:28*** NOTES ADDED**
  
 **) PLEASE SEE NOTES ADDED UNDER BUILDING #3 FOR FIRE
 PUMP.
 **) PLEASE SEE NOTES ADDED UNDER BUILDIGN#3 FOR
 POSSIBLE CONCERNS WITH EGRESS LIGHITNG FROM UNITS, B4,
 C-3 SPIRAL STAIRS.MAY NOT USE SWITCHED RECEPTACLE.
 THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW AS THESE
 AREAS AND USE IS NOW MORE CLEAR.
 **) PLEASE SEE NOTES ON ELECTRICAL RISER NEEDS TO MEET
 AND CORRELATE WITH RISER. EXAMPLE, SEE NOTE #10 WHICH
 MENTIONS POWER COMPANY TO INSTALL CONDUCTORS, HOWEVER
 PLEASE KNOW THE POWER COMPANY DOES NOT TYPICALLY
 INSTALL CONDUCTORS AFTER METERING DEVICES.
2007-09-18 08:12:072007-09-18 08:12:07
  
 ** DENIED 3RD REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SOME NEW COMMENTS BASED ON REVISED
 PLANS/PLANS AND DOCUMENTS NOW SUBMITTED.
 ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER
 SOME CAN NOT BE AT THIS TIME.
  
 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE
 DESIGNATIONS FOR ALL LIGHTING.
 PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL
 PLANS COULD NOT BE FOUND.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS.
 THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT
 STATED ON THE IDR AS ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE
 INPUT DATA REPORT DOES NOT CORRELATE WITH ALL
 ELECTRICAL LIGHTING WHICH IS ON PLANS. PLEASE SEE
 MISSING A SUBSTANTIAL AMOUNT OF LIGHTING ON THE INPUT
 DATE REPORT.
 13-415.0, 415.1.ABCD, 415.1.A, 415.2
  
 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY
 CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS
 AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO
 SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED
 SEALED OR ORIGINAL SIGNATURE.
 **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN
 PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS
 JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS
 1 AND 3.
 PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES
 SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD
 OF ENGINEERS.
 THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE
 FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC
 61G15-23.002., FBC 103.1.
 ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED
 THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND
 NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA
 FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004
 FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY
 AND AS REQUIRED.
  
  
 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES
 DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION.
 PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER
 BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMITS, PLANS AND FEES.
 PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED
 ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL
 NEED TO BE CORRECTED.
  
 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES
 *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN
 ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE
 ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME
 SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01
  
 5) NOTE: PLEASE SEE SHEET E16.04 AS THE MAIL ROOM DOES
 NOT CONTAIN ANY DOORS, OPENINGS, OR LIGHTING. PLEASE
 SEE THE SHEET A1.30 DOES NOT INDICATE THE SAME LAYOUT
 FOR THIS AREA. PLEASE CORRELATE THE TWO AS THESE
 LAYOUTS DO NOT MATCH AT THIS TIME.
 PLEASE SEE ANY CHANGES IN LIGHTING ETC.
 FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
  
 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS
 BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE
 HARDWIRED?
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD
 PLUG IN?
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-16 13:36:052007-09-16 13:36:05
  
 REVIEW TO CONTINUE ON 9/17> REVIEWNOTES TO FOLLOW
 ONCE REVIEW IS COMPLETED.
 THERE WILL BE ITEMS THAT NEED TO BE ADDRESSED.
2007-09-16 13:01:252007-09-16 13:01:25
  
 IN ELEC FOR REVIEW