| 2006-12-29 08:58:28 | DENIED:BUILDING #2 / 2001 FBC |
| | |
| | RESPONSE TO COMMENTS FROM REVIEW DATED 1-31-06 |
| | |
| | COMMENT 1:OK |
| | |
| | COMMENT 2:RESPONSE INDICATES NOTE FOR RETURN AIR ON |
| | SHEETS M15.01 THROUGH M15.03.PLEASE NOTE THE R/A |
| | INDICATED ON THE PLAN IS CONSIDERED A TRANSFER UNDER |
| | 2001 FMC 601.4 EXCEPTION 2 NOT 1.PLEASE VERIFY GRILLE |
| | SIZES.ALL AIR INTO THE MASTER SUITE IS TO BE INCLUDED |
| | IN THE CALCULATION (I.E. BATHROOM, CLOSET, ETC). PLEASE |
| | ALSO NOTE WALL CAVITIES USED FOR TRANSPORTING R/A SHALL |
| | BE LINED WITH AN AIR BARRIER AND SEALED IN ACCORDANCE |
| | WITH 2001 FBC CHAPTER 13 SUB-CHAPTER 410.1.ABCD.3.7. |
| | |
| | COMMENT 3:RESPONSE INDICATES AHU CLOSET DOOR IS |
| | NON-COMBUSTIBLE BUT THE DOOR SCHEDULE ON SHEET A9.02 |
| | STILL INDICATES A WOOD DOOR.PLEASE CLARIFY. |
| | |
| | COMMENT 4:RESPONSE STATES THE CLEARANCE AROUND THE |
| | AHU EXCEEDS THE 4" REQUIREMENT UNDER 2001 FMC |
| | 603.1.3.4.THE DETAIL ON PLAN SHEET M15.06 DOES NOT |
| | REFLECT OR ANNOTATE 4" CLEARANCE.PLEASE ALSO NOTE, |
| | THE CONDENSATE LINE SHALL BE OF NON-COMBUSTIBLE |
| | MATERIAL (NO PVC IN AHU CLOSET). |
| | |
| | COMMENT 5:RESPONSE REFERS TO "CONDENSATE TRAP DETAIL" |
| | ON SHEET M15.09.THE DETAIL IS ACTUALLY ON SHEET |
| | M15.06.PER 2001 FMC 307.2.3 & 307.2.4 AN AUXILLARY |
| | DRAIN PAN IS REQUIRED.PLEASE CONTACT HAROLD MOSER, |
| | CHIEF MECHANICAL INSPECTOR WITH REGARDS TO THIS |
| | APPLICATION.HAROLD MOSER CAN BE REACHED AT |
| | (561)805-6732. |
| | |
| | COMMENT 6:OK |
| | |
| | COMMENT 7:OK |
| | |
| | COMMENT 8:OK |
| | |
| | COMMENT 9:OK |
| | |
| | COMMENT 10: OK |
| | |