Plan Review Notes
Plan Review Notes For Permit 05091684
Permit Number 05091684
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-15 07:28:38DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
 (NOTE STATING "SUBSTANITAL MODIFICATIONS INCLUDING BUT
 NOT LIMITED TO BUILDING DEPARTMENT COMMENTS II" HAS
 CAUSED THE COMPLETE REVIEW OF EACH SHEET AND ADDED MANY
 HOURS OF REVIEW TIME AS SOME SHEETS ONLY HAD MINOR
 CHANGES BUT THE WHOLE SHEET WAS INDICATED IN THE
 REVISION CLOUD. NEW COMMENTS HAVE BEEN ORIGINATED
 BECAUSE OF CHANGES AND RE-REVIEW).
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2****RESPONSE
 NOTED, BUT SHEET A5.25 WAS
 NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED HAS BEEN
 LOCATED.
 ******RESPONSE NOTED, BUT THE INTENT OF THE CODE
 SECTION THAT REQUIRES SEPARATE PRIMARY AND SECONDARY
 ROOF DRAINS HAS NOT BEEN MET. IF THERE IS BLOCKAGE IN
 THE DOWNSPOUT, THEN AS INTENDED THE STORM WATER CAN
 DRAIN OVER THE TOP OF THE COLLECTOR HEAD, BUT IF THE
 SCUPPER OPENING IS COVERED/BLOCKED, THEN NEITHER THE
 PRIMARY, NOR THE SECONDARY DRAIN WILL WORK. SCUPPERS
 WILL BE REQUIRED IN THE PARAPET WALLS SIZED PER SECTION
 1107.3 AND A DETAIL WILL BE REQUIRED SHOWING THE
 LENGTH, HEIGHT & WIDTH AND INDICATING THE HEIGHT OFF
 THE ROOF AS REQUIRED IN SECTION 1503.4.2.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE
 NOTED, BUT SPECIFICATION "A" OR "B" IS NOT INDICATED ON
 THE PLANS.
  
 5. OK
 6. OK
 7. OK
  
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS STILL REQUIRED ON PLANS
 TO SHOW COMPLIANCE:
 A. 11-4.19.3 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED).
 ******RESPONSE NOTED, BUT PARALLEL APPROACH IS SHOWN.
 FORWARD APPROACH IS REQUIRED.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES. ******RESPONSE
 NOTED, BUT NOTE WAS NOT FOUND.
 C. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, BUT NOTE WAS NOT FOUND.
  
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOW WAS NOT
 FOUND ON THE CIVIL SHEET #10. PLEASE CLARIFY.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
 ******RESPONSE NOTED, BUT THE WATER DISTRIBUTION SYSTEM
 RISERS SHALL BE SHOWN IN ISOMETRIC FORM FROM THE
 ENTRANCE OF THE BUILDING THRU THE 5TH FLOOR. SHT
 AP/P14.26 AS INDICATED WAS THE STORM WATER RISER
 DIAGRAM, NOT THE POTABLE WATER RISER DIAGRAM.
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 ******RESPONSE NOTED, BUT SHT AP/P14.23 ONLY SHOWS
 RISERS, NOT THE BUILDING DRAIN ISOMETRIC, AND SHTS
 AP/P14.24 & AP/P14.25 DO NOT SHOW THE RISER LOCATIONS
 WITH THE RISER DESIGNATION NUMBERS.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED.
 SEE COMMENT RESPONSE TO COMMENT #10.
 RISER REQUIRED FOR ALL HORIZONTAL
 STORM DRAINAGE.
 ******RESPONSE NOTED, BUT SHT AP/P14.22 SHOWS NO STORM
 BUILDING DRAIN ISOMETRIC.--SHT AP/P14.26 SHOW ALL
 CLEANOUTS REQUIRED BY SECTION 1101.8.--P-TRAPS ARE
 NOT REQUIRED ON THE STORM SYSTEM.--5S, A MINIMUM 5"
 PIPE IS REQUIRED FOR THE 4" GD-1 1720SF OR INDICATE
 MINIMUM 1/4"/FT SLOPE. TABLE 1106.3.--1S, PIPE SIZE
 IS DECREASED IN SIZE IN THE DIRECTION OF FLOW
 DOWNSTREAM OF1858SF. UPSTREAM SHOWS 8" BUT DOWNSTREAM
 IS SHOWN AS 6". SECTION 704.2. 8" PIPE REQUIRED.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
 ******RESPONSE NOTED, BUT LENGHT, WIDTH & HEIGHT ARE
 NOT SHOWN FOR THE COLLECTOR HEAD. A CUT VIEW ONLY WAS
 SUBMITTED, PLEASE PROVIDE AN ELEVATION DETAIL TO SHOW
 ALL MEASUREMENTS.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE
 NOTED, BUT THE INTENT OF THE CODE SECTION THAT REQUIRES
 SEPARATE PRIMARY AND SECONDARY ROOF DRAINS HAS NOT BEEN
 MET. IF THE DOWNSPOUT BACKS UP THEN AS INTENDED THE
 STORM WATER CAN DRAIN OVER THE TOP OF THE COLLECTOR
 HEAD, BUT IF THE SCUPPER OPENING IS COVERED/BLOCKED,
 THEN NEITHER THE PRIMARY, NOR THE SECONDARY DRAIN WILL
 WORK. SCUPPERS WILL BE REQUIRED IN THE PARAPET WALLS
 SIZED PER SECTION 1107.3 AND A DETAIL WILL BE REQUIRED
 SHOWING THE HEIGHT & WIDTH AND INDICATING THE HEIGHT
 OFF THE ROOF AS REQUIRED IN SECTION 1503.4.2.
  
 6B. SHTS AP A5.05, AP A5.13, AND AP A5.24
 ROOF PLAN SHOWS UNITS AND FIXTURES.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 ********NEW COMMENTS 3RD REVIEW********
  
 1C. SHT AP/P14.01 UNIT A3 NOTE STATES "1/2IN CW/HW
 DOWN, BUT ONLY SHOWS C/W. PLEASE CLARIFY. SECTION
 105.2.1.
  
 2C. SHT AP/P14.03 UNITS C2 & C3 WERE DELETED FROM THE
 SHEET, BUT NO REVISION IS INDICATED. PLEASE CLOUD AND
 INDICATE REVISION WITH A NUMBERED DELTA TRIANGLE.
 SECTION 104.2.1.3.
  
 3C. SHT AP/P14.04 BOTH UNITS, IDENTIFY ALL STACK RISERS
 AND INDICATE WHICH MAIN STACK THEY CONNECT TO.--2ND
 FLOOR CLUBHOUSE PLUMBING PLAN. THE KITCHEN SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT FOR THE
 TOILET ROOM FIXTURES. SECTION 909.1.--INDICATE ON
 WHAT PAGE THE SANITARY LINE CONTINUES.
  
 4C. SHT AP/P14.05 IDENTIFY ALL STACKS. INDICATE WHICH
 SHEET THE PIPE CONTINUES AT THE COMMON AREAS.--4"
 GD-1, BY THE TRASH ROOM SQUARE FOOTAGE IS NOT LEGIBLE.
 SECTION 104.2.1.--THE BUILDING STORM DRAIN LINE HAS
 BEEN DELETED ON ONE SIDE OF THE SHEET. WAS IT RELOCATED
 TO ANOTHER SHEET? PLEASE CLARIFY. SECTION 104.2.1.--
 INDICATE THE RISER NUMBERS SO THEY CAN BE LOCATED ON
 THE NEXT LEVEL. (MANY RISERS HAVE THE SAME NUMBER. EACH
 RISER SHALL HAVE ITS OWN NUMBER SO IT CAN BE TRACED
 FROM THE GROUND FLOOR THRU THE ROOF. (SEE RISERS S-10,
 S-11 & S-12 FOR EXAMPLE). (IF THERE ARE TYPICAL RISERS,
 THEN INDICATE THAT IT IS A TYPICAL RISER, SUCH AS RISER
 S-11 AND THEN SHOW WHICH RISER NUMBERS ARE TYPICAL).
  
 5C. SHT AP/P14.06 INDICATE THE RISER NUMBERS SO THEY
 CAN BE LOCATED ON THE NEXT LEVEL. (MANY RISERS HAVE THE
 SAME NUMBER. EACH RISER SHALL HAVE ITS OWN NUMBER SO IT
 CAN BE TRACED FROM THE GROUND FLOOR THRU THE ROOF. (SEE
 RISER S-33 FOR EXAMPLE). (IF THERE ARE TYPICAL RISERS,
 THEN INDICATE THAT IT IS A TYPICAL RISER, SUCH AS RISER
 S-11 AND THEN SHOW WHICH RISER NUMBERS ARE TYPICAL).
  
 6C. SHT AP/P14.07 IDENTIFY ALL RISERS. SECTION 104.2.1.
 --MINIMUM 5" REQUIRED DOWNSTREAM OF 4" GD-1 1200SF &
 DOWNSTREAM OF 4" GD-1 836SF. (MANY RISERS HAVE THE SAME
 RISER NUMBER). TABLE 1106.3.
  
 7C. SHT AP/P14.08 IDENTIFY ALL RISERS. SECTION 104.2.1.
 (MANY RISERS HAVE THE SAME RISER NUMBER).
  
 8C. SHT AP/P14.09 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.
  
 9C. SHT AP/P14.10 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.
  
 10C. SHT AP/P14.11 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.--INDICATE WHERE THE NEW 4" CW
 FEEDS FROM AND CONTINUES ON TO. SECTION 104.2.1.
  
 11C. SHT AP/P14.12 FULL OPEN VALVES ARE REQUIRED PER
 SECTION 606.1(3). PLEASE INDICATE ON PLANS.
  
 12C. SHT AP/P14.13 PLAN KEY NOTES 3 & 4 WERE NOT
 LOCATED. PLEASE CLARIFY & CORRELATE. SECTION 104.2.1.
 --SHOW ALL RISER DESIGNATION NUMBERS .
  
 13C. SHT AP/P14.14 PLAN KEY NOTES 3 & 4 WERE NOT
 LOCATED. PLEASE CLARIFY & CORRELATE. SECTION 104.2.1.
 --ONE RISER DESIGNATION S/2 NOT INDICATING WHERE THE
 RISER IS LOCATED.--ONE RISER (2), THE 4" SANT.
 STACK FITTING APPEARS TO BE GUIDING THE THE WASTE
 AGAINST THE FLOW. SECTION 706.3.--SHOW ALL RISER
 DESIGNATION NUMBERS .
  
 14C. SHT AP/P14.15 NO REVISION NUMBER IS INDICATED IN
 THE DELTA TRIANGLE.--NO PLAN KEY NOTES NUMBERS ARE
 INDICATED AT THE UNITS NEXT TO THE MATCHLINE. SECTION
 104.2.1.--SHOW ALL RISER DESIGNATION NUMBERS .
  
 15C. SHT AP/P14.16 NO REVISION NUMBER OR DELTA
 INDICATED.--PLAN KEY NOTES 3 & 4 NOT LOCATED.--
 SHOW ALL RISER DESIGNATION NUMBERS .SECTION 104.2.1.
  
 16C. SHT AP/P14.17 NO PLAN KEY NOTES INDICATED FOR
 NUMBERS 1 & 2. PLEASE CLARIFY & CORRELATE. SECTION
 104.2.1.
  
 17C. SHT AP/P14.19 NO PLAN KEY NOTES INDICATED FOR
 NUMBERS 1 & 2. PLEASE CLARIFY & CORRELATE. SECTION
 104.2.1.
  
 18C. SHT AP/P14.21SANITARY RISERS 1, 4, 5, 6 & 7 EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK AT OR BELOW THE LOWEST HORIZONTAL BRANCH. SECTION
 903.4. PLEASE CORRECT ON RISERS.--SANT RISER 7
 TOTAL DFU'S IS 24, NOT 20. (BATHROOM GROUP IS 5, PLUS
 ONE FOR THE EXTRA LAV) TABLE 709.1 (SEE DEFINITION OF
 BATHROOM GROUP).--DETAIL #4, A FULL OPEN VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER.
 SECTION 606.1(7).
  
 19C. SHT AP/P14.22 ALL UNITS. A WATER HAMMER ARRESTOR
 IS REQUIRED AT THE DISHWASHER LINE PER SECTION 604.9.
 --UNITS B1, B2, B3 & B4 DO NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1.--UNITS C2 & C3. NO FLOOR
 PLANS ARE SUBMITTED FOR THESE UNITS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 20C. SHT AP/P14.23 SANITARY RISERS 1 THRU 9 & 19 ARE
 NOT SUBMITTED. PLEASE CLARIFY. SECTION 104.2.1.
  
 21C. SHTS AP/P14.24 & AP/P14.25 INDICATE THE RISER
 DESIGNATION NUMBERS AT THE BASE OF EACH RISER TO BE
 ABLE TO TRACK THE RISERS FROM FLOOR TO FLOOR. SECTION
 104.2.1.
  
 22C. SHT AP/P14.26 SHOW THE CLEANOUTS REQUIRED IN
 SECTION 1101.8.--P-TRAPS ARE NOT REQUIRED IN THE
 STORM SYSTEM.--MINIMUM 5" REQUIRED AT 4" GD-1
 17720SF OR SHOW SLOPE MINIMUM 1/4"/FT.--8" REQUIRED
 AT 7176SF. 6" WAS SHOWN. PIPE WAS REDUCED IN THE
 DIRECTION OF FLOW AND IS NOT ALLOWED PER SECTION 704.2.
 8" PIPE IS REQUIRED. TABLE 1106.3.
  
 23C. SHT AP/P14.27 SHOW THE CLEANOUTS REQUIRED IN
 SECTION 1101.8.--P-TRAPS ARE NOT REQUIRED IN THE
 STORM SYSTEM.
  
 24C. NOTE: REVISION #1 HAS BEEN DELETED FROM THE TITLE
 BLOCK REVISION INDEX FROM MOST ALL PLUMBING SHEETS. ALL
 REVISIONS SHALL BE INDICATED IN THE REVISION INDEX FOR
 RECORD KEEPING. PLEASE SHOW ALL REVISIONS THROUGHOUT
 THE LENGTH OF THE PROJECT. SECTION 104.2.1.3.
  
 25C. THERE IS NO KEY PLAN OR COLUMN LINES TO INDICATE
 WHAT SECTION OF THE BUILDING IS LOCATED ON WHICH SHEET.
 MATCH LINES DO NOT INDICATE INFORMATION TO DIRECT
 INFORMATION FROM ONE SHEET TO ANOTHER. IT IS TIME
 CONSUMING WHEN ONE SECTION OF THE PLANS HAS NO RELATION
 TO ANOTHER WITH INFORMATION SUBMITTED. PLEASE SUBMIT A
 KEY PLAN ON EACH SHEET OF THE FLOOR PLANS AS HAS BEEN
 SUBMITTED ON THE ARCHITECTURAL SHEET IN ORDER TO
 EXPEDITE THE PLAN REVIEWS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  