Plan Review Notes
Plan Review Notes For Permit 05091684
Permit Number 05091684
Review Stop M
Sequence Number 3
Notes
Date Text
2007-10-04 17:42:29REVIEW #: 3
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THERE HAVE BEEN SIGNIFICANT CHANGES AS WELL AS
 PAGES ADDED TO PLANS. THE LEVEL OF CHANNGES REQUIRES A
 THOROUGH REVIEW OF MECHANICAL PLANS IN THEIR ENTIRETY.
 ANY COMMENT FROM PREVIOUS REVIEWS NOT REPEATED IN THIS
 REVIEW SHALL BE CONSIDERED TO HAVE BEEN ADEQUATELY
 ADDRESSED.
  
 1. M15.01 THRU M15.03: R/A JUMPERS FROM BEDROOMS ARE
 NOT SIZED TO MEET THE BALANCED R/A EXCEPTIONS OF FBC,M
 601.4. ALL DROPS INTO A MASTER SUITE SHALL BE INCLUDED
 PER EXCEPTION #3. THE MINIMUM SIZE JUMPER NEEDED FOR 7
 INCH AND 4 INCH ROUND DROPS IS 77 SQUARE INCHES. THE 9
 INCH ROUND SHOWN ON PLANS PROVIDES 63.6 SQUARE INCHES.
 A MINIMUM 10 INCH ROUND DUCT IS REQUIRED TO MEET
 EXCEPTION #1. UNLESS JUMPERS AND TRANSFERS ARE DESIGNED
 TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED
 AT FINAL INSPECTION TO VERIFY A DIFFERENTIAL PRESSURE
 OF 0.01 IN. W.C. OR LESS ACROSS THE CLOSED DOOR IN
 ACCORDANCE WITH THIS SECTION.
  
 2. M15.01 THRU M15.03: NOTE 10 TABLE FOR TRANSFER
 GRLLS, SIZES SHOWN ARE NOT IN COMPLIANCE WITH FBC,M
 601.4 EXCEPTION #2. SEE COMMENT 1 ABOVE FOR
 REQUIREMENTS IF TRANSFERS ARE NOT DESIGNED TO MEET THE
 EXCEPTIONS UNDER THIS SECTION.
  
 3. M15.01 THRU M15.03: KEY NOTE #9, NO INFORMATION WAS
 PROVIDED REGARDING DRYERS OR INSTALLATION INSTRUCTIONS
 AS STATED IN THE NOTE. PROVIDE INFORMATION NEEDED TO
 SHOW COMPLIANCE WITH FBC,M 501.4 AND KEY NOTE #9.
  
 4. M15.01: THE CONFIGURATION OF THE AC CLOSET IN
 APARTMENT A3 IS DIFFERENT FROM THE TYPICAL MOUNTING
 DETAIL SHOWN ON M15.22. PROVIDE DETAIL FOR THIS
 INSTALLATION SHOWING HOW DUCTED RETURN TO GRILL (SEE
 NOTE 6 ON M15.01) WILL WORK WITH A WATER HEATER UNDER
 THE AHU. ALSO, SHOW HOW O.A. DUCT IS TO TERMINATE IN
 CLOSET.
  
 5. M15.01 THRU M15.03: ALL APARTMENTS EXCEPT A3 CALL
 FOR FULLY LOUVERED DOORS ON A/C CLOSETS FOR RETURN AIR.
 ARCHITECTURAL FLOOR PLANS A5.50 THRU A5.53 SHOW DOORS
 AS U02 AND U-18. DOOR SCHEDULE ON A-9.02 SHOWS THESE TO
 BE "J" TYPE DOORS, WHICH ARE SOLID 6-PANEL DOORS.
 COORDINATE PLANS AND SHOW HOW AIR IS TO BE RETURNED TO
 A/C CLOSETS. FBC,M 601.4
  
 6. M15.04: FIRST AND SECOND FLOOR AREAS, BASED ON LIFE
 SAFETY PLANS A1.20 AND A1.21 ALONG WITH FLOOR PLANS
 A5.07 AND A5.71 THERE ARE NUMEROUS LOATIONS WHERE DUCTS
 ARE PENETRATING RATED WALL ASSEMBLIES. SHOW OPENING
 PROTECTIVES AT ALL LOCATIONS WHERE DUCTS PENETRATE
 RATED ASSEMBLIES. BE SURE TO COOORDINATE WITH
 ARCHITECTURAL PLAND. FBC,M 607.1.2 AND 607.6
  
 7. M15.05 THRU M15.08 AND M15.11: KEY NOTE #1 CALLS FOR
 3/4 INCH PVC FROM EACH AHU TO CONDENSATE RISER. PVC
 SHALL NOT BE LOCATED IN A/C CLOSETS USED AS PLENUMS PER
 FBC,M 602.2.1. ALSO, CONDENSATE LINES AS SHOWN ON PLANS
 WILL REQUIRE A SIGNIFICANT CHANGE IN ELEVATION TO
 MAINTAIN A UNIFORM ALIGNMENT AND SLOPE IN ACCORDANCE
 WITH FBC,M 307.2.2 DUE TO THE LONG HORIZONTAL RUNS
 SHOWN IN GARAGE AREA. PROVIDE AN ELEVATION VIEW DETAIL
 SHOWING THE FEASIBILITY OF THIS CONFIGURATION WHILE
 TAKING INTO ACCOUNT STRUCTURAL ELEMENTS AND REQUIRED
 CLEARANCES IN THE GARAGE. THE AREA CHOSEN FOR THIS
 DETAIL SHOULD INCORPORATE A "WORST CASE" CONDITION. FBC
 104.2.1.2
  
 8. M15.22: CONDENSATE TRAP DETAIL FOR NON-DUCTED RETURN
 UNITS, THE SECONDARY DRAIN LINE FROM THE AUXILIARY
 DRAIN PAN SHALL NOT BE CONNECTED TO THE PRIMARY
 CONDENSATE RISER. A SEPARATE DRAIN LINE SHALL EXTEND
 FROM THE PAN TO A CONSPICUOUS POINT AND SERVE AS AN
 ALARM WHICH INDICATES THAT THE PRIMARY DRAIN IS
 RESTRICTED.AS AN ALTERNATIVE TO A SEPARATE DRAIN
 LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH
 DEVICE SHALL BE USED TO CONTROL OVERFLOW BY
 AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE
 THAT PRODUCES THE CONDENSATE. THE FLOAT SWITCH ON THE
 SECONDARY DRAIN OUTLET AT THE AHU MAY BE INSTALLED
 (ALTHOUGH IT'S NOT NECESSARY) BUT IT CAN NOT REPLACE
 THE SEPARATE SECONDARY DRAIN LINE OR THE FLOAT SWITCH
 REQUIRED ON THE AUXILIARY DRAIN PAN. THE FLOAT SWITCH
 ON THE SECONDARY DRAIN OUTLET AT THE AHU IS ACCEPTABLE
 AS OVERFLOW PROTECTION ONLY ON THE DUCTED RETURN UNITS
 WHERE AN AUXILIARY DRAIN PAN CAN NOT BE INSTALLED UNDER
 THE AHU. FBC,M 307.2.3 AND 307.2.4
  
 9. M15.22: DUCT SUPPORT DETAIL INDICATES 1/2 INCH WIDE
 22GA SUPPORTS ON FLEX DUCT. THE MATERIAL SUPPORTING
 FLEX DUCT SHALL NOT BE LESS THAN 1 1/2 INCHES WIDE.
 FBC,M 603.5.6.6(6).
  
 10. M15.22: CONDENSING UNIT DETAIL CALLS FOR 1/4 INCH
 CABLES TIED TO THE CONDENSER AND THE BEAM WITH 3/8 INCH
 LAG BOLTS. LAG BOLTS ARE FOR USE IN WOOD. PLEASE
 SPECIFY A FASTENER WHICH IS APPROPRIATE FOR THIS
 APPLICATION. ALSO, INDICATE ON PLANS THE WIND SPEED TO
 WHICH THIS CONNECTION DETAIL IS DESIGNED. FBC,M 301.13
 AND FBC CH.16
  
 11. M15.22: TYPICAL AHU DETAIL, PROVIDE MANUAL VOLUME
 DAMPER AT OUTDOOR AIR DUCT IN CLOSET PER FBC
 13-409.1.ABCD.2.
  
 12. M15.23: PROVIDE OUTDOOR AIR CALCULATIONS FOR
 DWELLING UNITS IN ACCORDANCE WITH FBC,M TABLE 403.3.
  
 13. M15.21: FIRE PUMP ROOM, PROVIDE SUBMITTAL AND
 INSTALLATION DETAIL FOR THE DIESEL STORAGE TANK. ALSO,
 PROVIDE DETAIL FOR THE DIESEL ENGINE EXHAUST WITH
 DISCHARGE LOCATION. STATIONARY LIQUID FUELED INTERNAL
 COMBUSTION ENGINES, INCLUDING FUEL STORAGE AND PIPING
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 37-94. SEE
 FBC,M 915.1 AND 915.2.
  
 14: ENERGY: THERE WERE TWO DIFFERENT SETS OF
 CALCULATIONS SUBMITTED. FORM 400A-2004 V2.5 IS NOT
 VALID AS THIS PROJECT IS UNDER THE 2001 FBC. THE 2004
 FORM IS DISREGARDED AND THE 2001 FORM IS BEING REVIEWED
 FOR CODE COMPLIANCE. FBC 13-400.3.A.
  
 15. ENERGY: SEVERAL ITEMS LISTED ON THE INPUT DATA
 REPORT DO NOT CORRELATE WITH WHAT IS SHOWN ON PLANS.
 EXAMPLE: THE REPORT INDICATES EXTERIOR WALL ASSEMBLES
 WITH R-VALUE OF 11.94. THE WALL AS DESCRIBED IN THE
 REPORT IS NOT SHOWN ON ARCHITECTURAL PLANS. THE
 INFORMATION USED IN THE INPUT DATA REPORT SHALLL
 CORRELATE WITH PLANS. PLEASE VERIFY ALL ASSEMBLIES,
 R-VALUES, U-FACTORS AND INFILTRATION RATES ARE IN
 COMPLIANCE AND CORRESPOND WITH WHAT IS ON ARCHITECTURAL
 PLANS. FBC 13-400.3.A
  
 16. ENERGY: COOLING LOAD CALCS, DATA USED TO PERFORM
 COOLING LOAD CALCULATIONS AS SHOWN ON THE SYSTEM SIZING
 SUMMARY DO NOT MATCH THE VALUES SHOWN ON PLAN. EXAMPLE:
 AHU CH-3 ON SUMMARY SHOWS 120 CFM OF OUTDOOR AIR.
 EQUIPMENT SCHEDULEON M15.23 SHOWS 200 CFM, PLEASE
 CORRELATE PLANS AND CALCULATIONS. FBC 13-407.1.ABCD.1
  
 17. ENERGY: PROVIDE AUTOMATIC SETBACK OR SHUTDOWN
 CONTROLS IN ACCORDANCE WITH FBC 13-407.1.ABCD.2.4.1.
  