| Date |
Text |
| 2007-09-21 12:51:22 | 2007-09-21 12:51:22 |
| | |
| | ** DENIED 3RD REVIEW** |
| | |
| | BUILDING #1 |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE |
| | THERE ARE SEVERAL NEW COMMENTS BASED ON REVISED |
| | PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. PLEASE SEE |
| | THERE ARE SEVERAL COMMENTS FROM THE TWO PREVIOUS |
| | REVIEWS WHICH STILL REMAIN. PLEASE SEE FINAL COMMENT |
| | WITH RESPECT TO FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | ***THE PREVIOUS REVIEW MENTIONED THERE MAY BE NEW |
| | COMMENTS AS THERE WAS A SUBSTANTIAL AMOUNT OF MISSING |
| | INFORMATION ON PLANS AND DOCUMENTS ETC. |
| | THE REVIEWS CAN ONLY BE DONE ON THE PLANS AND DOCUMENTS |
| | SUBMITTED. WHEN INFORMATION ON PLANS IS NOT COMPLETE OR |
| | MISSING A COMPLETE REVIEW FOR CODE COMPLIANCE IS NOT |
| | POSSIBLE. THEREFORE THERE ARE NEW COMMENTS. |
| | |
| | ** SOME ITEMS COULD HAVE BEEN RED-LINED, HOWEVER MOST |
| | OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME. |
| | |
| | 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE |
| | DESIGNATIONS FOR ALL LIGHTING. |
| | PLEASE SEE THERE ARE SEVERAL AREAS INCLUDING FIRST |
| | FLOOR AND OTHER FLOORS WHERE FIXTURES ARE STILL MISSING |
| | DESIGNATIONS. |
| | PLEASE SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED |
| | WITH THESE AT THIS TIME. |
| | PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL |
| | PLANS COULD NOT BE FOUND. |
| | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR |
| | EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS. |
| | THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT |
| | STATED ON THE IDR AS ON PLANS. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE |
| | INPUT DATA REPORT DOES NOT CORRELATE WITH ALL |
| | ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON |
| | PLANS. |
| | |
| | PLEASE SEE THE ENERGY CALCULATIONS/INPUT DATA REPORT IS |
| | MISSING A SUBSTANTIAL AMOUNT OF LIGHTING WHICH IS ON |
| | THE PLANS. |
| | PLEASE SEE FOR EXAMPLE ONE ROOM IN THE CLUBHOUSE: |
| | *FITNESS CENTER* WHICH LISTS ONE FIXTURE BEING |
| | FLUORESCENT AND 750WATTS ON THE INPUT DATA REPORT, YET |
| | HOW IS THIS POSSIBLE WHEN THE FIXTURE TYPES ON PLANS |
| | ARE INCANDESCENT, FLUORESCENT ETC, THERE A SEVERAL |
| | FIXTURES AND NOT JUST ONE AND THE TOTAL WATTAGE OF THE |
| | LIGHTING FIXTURES BASED ON THE FIXTURE LEGEND PROVIDED |
| | FOR THE CLUBHOUSE FAR EXCEEDS THE 750WATTS AS ENTERED? |
| | |
| | THIS IS THE SAME OF ALMOST ALL LOCATIONS NOT ONLY THE |
| | CLUBHOUSE. THERE ARE ACTUALLY HUNDREDS OF FIXTURES ON |
| | THE PLANS WHICH ARE NOT INCLUDED IN THE ENERGY |
| | CALCULATIONS. |
| | THE FIXTURE TYPES DO NOT CORRELATE. |
| | THE WATTAGE DOES NOT CORRELATE |
| | THE NUMBER OF FIXTURES DOES NOT CORRELATE. |
| | THE TOTAL ENERGY CONSUMPTION OF LIGHTING ENTERED IN THE |
| | INPUT DATA REPORT IS FAR LESS THAN THE LIGHTING AND |
| | CONSUMPTION OF ENERGY ON PLANS. |
| | PLEASE KNOW THESE ARE MINIMUM REQUIREMENTS FOR ENERGY |
| | AND ARE FEDERAL AND STATE REQUIRED. |
| | 13-415.0, 415.1.ABCD, 415.1.A, 415.2, THERE ARE TOO |
| | NUMEROUS CODE SECTIONS TO LIST, PLEASE SEE CHAPTER 13 |
| | OF THE 2001 FBC. |
| | |
| | 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY |
| | CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS |
| | AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO |
| | SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED |
| | SEALED OR ORIGINAL SIGNATURE. |
| | **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN |
| | PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS |
| | JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS |
| | 1 AND 3. |
| | PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES |
| | SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD |
| | OF ENGINEERS NOT ONLY FOR THE FACT THIS OFFICE HAS |
| | REPEATEDLY MADE THIS SAME COMMENT ON NUMEROUS PROJECTS |
| | TO THE SAME DESIGNER, BUT ALSO FOR INFORMATION ON PLANS |
| | AND ENERGY CALCULATIONS NOT COORDINATING. |
| | THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE |
| | FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC |
| | 61G15-23.002, FBC 103.1. |
| | ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED |
| | THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND |
| | NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA |
| | FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004 |
| | FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY |
| | AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS |
| | SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS. ** |
| | PLEASE BE SURE TO GO OVER ALL AND CORRECT. |
| | |
| | 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES |
| | DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION. |
| | PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER |
| | BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE |
| | PERMITS, PLANS AND FEES. |
| | PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED |
| | ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL |
| | NEED TO BE CORRECTED. |
| | PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH |
| | BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS |
| | DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT |
| | NOT THE OTHERS. |
| | |
| | 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES |
| | *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN |
| | ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE |
| | ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME |
| | SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS |
| | COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS |
| | MADE. |
| | ** THIS IS ALSO SHOWN ON LEGENDS ON OTHER SHEETS. |
| | |
| | 5) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS. |
| | PLEASE SEE THIS WAS NOTED ON PREVIOUS REVIEW AND |
| | SPECIFICALLY NOTED TO SEE 700.12E FOR CIRCUITING OF |
| | EMERGENCY AND EXIT LIGHTS. |
| | PLEASE SEE THERE IS EMERGENCY AND EXIT LIGHTING |
| | FIXTURES WHICH ARE STILL MISSING CIRCUITING. ( |
| | CLUBHOUSE) |
| | FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION AND COORDINATION OF PLANS. |
| | ** THIS WAS IN PREVIOUS REVIEWS NOTES #6, #7, AND NOTE |
| | #30 AT A MINIMUM. SPECIFICALLY 700.12E WAS NOTED. |
| | |
| | 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS |
| | BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE |
| | HARDWIRED? |
| | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING |
| | MEANS. |
| | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD |
| | PLUG IN? |
| | |
| | 7) NOTE: PLEASE CLARIFY WHERE THE ROOM AND AREA |
| | DESIGNATIONS ARE ON PLANS. EXAMPLE: BEDROOM #1, DINING |
| | ROOM, LIVING ROOM ETC. |
| | PLEASE KNOW THE PREVIOUS REVIEW REQUESTED FOR ALL |
| | CIRCUITING TO BE COMPLETED ON PLANS AND TO CORRELATE |
| | WITH PANEL SCHEDULES HOWEVER AS NOTED IN NOTE #5 ABOVE |
| | THIS IS STILL NEEDED IN MANY LOCATIONS. |
| | PLEASE SEE SHEET E16.05, WHICH INDICATES CIRCUITS CB32 |
| | FOR ELEVATOR PIT LIGHTS AND RECEPTACLES AND INDICATES |
| | CB-30 FOR *H*. |
| | THE *H* IS NOT KNOWN AND BOTH CIRCUITS ON PANEL |
| | SCHEDULE CB ARE SHOWN A BLANK/SPARES. |
| | AS THESE CIRCUITS ARE NOT INDICATED WE CAN NOT |
| | DETERMINE MINIMUM COMPLIANCE WITH 620.22-620.25 PLEASE |
| | SEE OTHER ELEVATOR EQUIPMENT ROOMS AND AREAS WHICH SEEM |
| | TO INDICATE LIGHTING HOWEVER THE LIGHTING IS SHOWN |
| | CIRCUITED ON THE SAME LIGHTING AS GARAGE AND/OR OTHER |
| | COMMON AREAS. |
| | PLEASE VERIFY ALL ON PLANS, AND CORRELATE WITH PANEL |
| | SCHEDULES. THIS IS NOT ALL LOCATIONS. |
| | ** THIS WAS NOTED ON PREVIOUS REVIEWS NOTE # 9. |
| | |
| | 8) NOTE: PLEASE SEE THE MISSING LIGHTING OUTSIDE FIRE |
| | PUMP ROOM AND STAIR AREA. PLEASE SEE MISSING |
| | PHOTO-METRICS ETC. |
| | PLEASE SEE MISSING PHOTO-METRICS FOR CLUBHOUSE STAIR |
| | AREA UNDER NORMAL AND EMERGENCY. |
| | PLEASE SEE THE LEVEL OF LIGHTING OUTSIDE MAIN |
| | ELECTRICAL ROOM FOR BOTH CONDITIONS OF NORMAL AND |
| | EMERGENCY DOES NOT SEEM TO MEET THE MINIMUM LEVELS |
| | REQUIRED. PLEASE SEE THE NORMAL LEVEL IS SHOWN ONLY AS |
| | 6.38 AND LESS THAN 1FT CANDLES UNDER EMERGENCY? |
| | NFPA-101 7.8.1.3, 7.9.2.2. |
| | PLEASE KNOW AS THERE ARE NO LIGHTING FIXTURES, |
| | CIRCUITING ETC SHOWN FOR SOME AREAS, PLEASE COMPLETE. |
| | PLEASE ALSO BE SURE TO GO OVER ALL EGRESS PATHS |
| | ESPECIALLY STAIR AREAS. THERE ARE OTHER AREAS ALSO. |
| | |
| | PLEASE ILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS |
| | SHOWN AS A *J* FIXTURE. S NO FIXTURE LEGEND WAS |
| | SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME. PLEASE |
| | ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA AND MAIN |
| | ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY BATTERY |
| | BACK UP LIGHTING FIXTURE OF SOME KIND. |
| | NEC 700.12E, 700.16, LS-101 7.8, 7.9 |
| | ** THIS WAS NOTE ON PREVIOUS REVIEWS NOTE #6 |
| | |
| | 9) NOTE: PLEASE SEE THE PREVIOUS NOTES QUESTIONED THE |
| | EGRESS PATH FROM CLUBHOUSE INTO THE GARAGE WHICH IS |
| | MAIL CENTER HALL AS THE EXIT LIGHT AND DOOR ON |
| | CLUBHOUSE PLANS SHOWS THE EGRESS INTO THIS AREA AND THE |
| | MAIL CENTER HALL AREA INDICATES EXIT LIGHTS WITH |
| | DIRECTIONAL INTO THE CLUBHOUSE??? |
| | THERE ARE SEVERAL OTHER LOCATIONS WHERE EXIT LIGHTS ARE |
| | IN QUESTION BASED ON THE LAYOUTS SHOWN ON THE |
| | ELECTRICAL PLANS. |
| | SEE MAIL CENTER AREA ADJACENT TO PARKING AREA WHICH |
| | DOES NOT INDICATE ANY EXIT LIGHT FIXTURES DIRECTING AN |
| | OCCUPANT TO THE EXIT. |
| | THIS HAS BEEN GONE OVER WITH THE BUILDING PLAN REVIEWER |
| | AND COMMENTS WILL BE NOTED ON THESE LOCATIONS. THE LIFE |
| | SAFETY PLAN ALSO INDICATES WHAT IS BEING SHOWN AS |
| | EGRESS PATHS THROUGH PARKING SPACES ETC. |
| | PLEASE SEE COMMENTS FROM BUILDING REVIEWER, AND FIRE |
| | MARSHAL. |
| | PLEASE SEE CHAPTER 10 OF THE FBC AND CHAPTER 7 OF THE |
| | LIFE SAFETY CODE. |
| | THE EGRESS PATHS ARE NOT IN REVIEW OF THE ELECTRICAL |
| | REVIEWER HOWEVER AS MANY OF THE EXIT AND EMERGENCY |
| | LIGHTING ARE IN QUESTION AND THIS DIRECTLY AFFECTS THE |
| | ELECTRICAL PLANS THIS IS BEING NOTED FOR INFORMATION AT |
| | THIS TIME. |
| | |
| | 10) NOTE: PLEASE SEE PLANS ARE NOT COMPLETE WITH WIND |
| | LOAD INFORMATION FOR SITE LIGHTING. |
| | IF NOT INCLUDED IN THE PLANS, THEN THESE WILL ALL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | ** THIS WAS NOTED ON NOTE #7 ON PREVIOUS REVIEWS. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION |
| | AS REQUESTED ON THE PREVIOUS REVIEWS. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO |
| | THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE |
| | SEE NO TIMES AT 100% RUNNING IS SHOWN. |
| | PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE |
| | MARSHAL. |
| | PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3, |
| | DOES NOT CONTAIN THE TEXT FOR CODE. |
| | PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED |
| | AT THIS TIME. |
| | PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME |
| | INFORMATION. |
| | PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP, |
| | YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS |
| | INDICATE AN ELECTRICAL FIRE PUMP. |
| | PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE |
| | WITH PLANS. |
| | 110.3, 90.7, NFPA-70 695, NFPA-20 2003 |
| | **THIS WAS NOTED ON TWO PREVIOUS REVIEWS ON NOTE #10. |
| | |
| | 12) NOTE: PLEASE LABEL ALL MAINS, MAIN 1 OF ? , 2OF ? |
| | /SERVICE #1 MAIN #1, SERVICE #2 MAIN #1, SERVICE #3 |
| | MAIN 1 ETC. |
| | PLEASE BE SURE TO CONTACT THIS OFFICE WITH RESPECT TO |
| | PLAGUE DIRECTLY LABELING AND INFORMATION. THIS CAN BE |
| | GONE OVER WITH THE CHIEF ELECTRICAL INSPECTOR ALSO |
| | BEFORE PLAGUES ARE INSTALLED. |
| | PLANS SHOW 7 MAINS AT THIS TIME. |
| | PLEASE SEE 230.2, (E) |
| | |
| | 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH |
| | RESPECT TO ELEVATOR PLATFORMS WHICH MAY AFFECT |
| | ELECTRICAL PLANS AND LAYOUTS. |
| | |
| | 14) NOTE: PLEASE SEE DOOR SWING FOR METER/ELECTRICAL |
| | ROOM 1C2, NEEDS TO SWING OUT. |
| | 110.26 |
| | |
| | 15) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE |
| | NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW AT THIS TIME ONE SET OF PLANS MAY BE |
| | RETAINED BY THIS OFFICE FOR PEER REVIEW AS THERE ARE |
| | SOME CODE SECTIONS WHICH HAVE STILL NOT BEEN COMPLIED |
| | WITH. |
| | PLEASE KNOW ONE GONE OVER THIS FEE MAY BE ASSESSED |
| | WHICH IS REQUIRED UNDER THE FLORIDA STATUTES. THIS FEE |
| | IS NOT TO THE CONTRACTOR/OWNER OR DEVELOPER THIS IS TO |
| | THE DESIGN PROFESSIONAL(S). |
| | ** PLEASE BE SURE TO GO OVER COMMENTS. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| | THIS REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-20 16:32:34 | 2007-09-20 16:32:34 |
| | |
| | REVIEW COMMENCED |
| 2007-09-16 13:07:43 | 2007-09-16 13:07:43 |
| | |
| | IN ELEC FOR REVIEW |