Plan Review Notes
Plan Review Notes For Permit 05091684
Permit Number 05091684
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-21 12:51:222007-09-21 12:51:22
  
 ** DENIED 3RD REVIEW**
  
 BUILDING #1
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SEVERAL NEW COMMENTS BASED ON REVISED
 PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. PLEASE SEE
 THERE ARE SEVERAL COMMENTS FROM THE TWO PREVIOUS
 REVIEWS WHICH STILL REMAIN. PLEASE SEE FINAL COMMENT
 WITH RESPECT TO FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ***THE PREVIOUS REVIEW MENTIONED THERE MAY BE NEW
 COMMENTS AS THERE WAS A SUBSTANTIAL AMOUNT OF MISSING
 INFORMATION ON PLANS AND DOCUMENTS ETC.
 THE REVIEWS CAN ONLY BE DONE ON THE PLANS AND DOCUMENTS
 SUBMITTED. WHEN INFORMATION ON PLANS IS NOT COMPLETE OR
 MISSING A COMPLETE REVIEW FOR CODE COMPLIANCE IS NOT
 POSSIBLE. THEREFORE THERE ARE NEW COMMENTS.
  
 ** SOME ITEMS COULD HAVE BEEN RED-LINED, HOWEVER MOST
 OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME.
  
 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE
 DESIGNATIONS FOR ALL LIGHTING.
 PLEASE SEE THERE ARE SEVERAL AREAS INCLUDING FIRST
 FLOOR AND OTHER FLOORS WHERE FIXTURES ARE STILL MISSING
 DESIGNATIONS.
 PLEASE SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED
 WITH THESE AT THIS TIME.
 PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL
 PLANS COULD NOT BE FOUND.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS.
 THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT
 STATED ON THE IDR AS ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE
 INPUT DATA REPORT DOES NOT CORRELATE WITH ALL
 ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON
 PLANS.
  
 PLEASE SEE THE ENERGY CALCULATIONS/INPUT DATA REPORT IS
 MISSING A SUBSTANTIAL AMOUNT OF LIGHTING WHICH IS ON
 THE PLANS.
 PLEASE SEE FOR EXAMPLE ONE ROOM IN THE CLUBHOUSE:
 *FITNESS CENTER* WHICH LISTS ONE FIXTURE BEING
 FLUORESCENT AND 750WATTS ON THE INPUT DATA REPORT, YET
 HOW IS THIS POSSIBLE WHEN THE FIXTURE TYPES ON PLANS
 ARE INCANDESCENT, FLUORESCENT ETC, THERE A SEVERAL
 FIXTURES AND NOT JUST ONE AND THE TOTAL WATTAGE OF THE
 LIGHTING FIXTURES BASED ON THE FIXTURE LEGEND PROVIDED
 FOR THE CLUBHOUSE FAR EXCEEDS THE 750WATTS AS ENTERED?
  
 THIS IS THE SAME OF ALMOST ALL LOCATIONS NOT ONLY THE
 CLUBHOUSE. THERE ARE ACTUALLY HUNDREDS OF FIXTURES ON
 THE PLANS WHICH ARE NOT INCLUDED IN THE ENERGY
 CALCULATIONS.
 THE FIXTURE TYPES DO NOT CORRELATE.
 THE WATTAGE DOES NOT CORRELATE
 THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 THE TOTAL ENERGY CONSUMPTION OF LIGHTING ENTERED IN THE
 INPUT DATA REPORT IS FAR LESS THAN THE LIGHTING AND
 CONSUMPTION OF ENERGY ON PLANS.
 PLEASE KNOW THESE ARE MINIMUM REQUIREMENTS FOR ENERGY
 AND ARE FEDERAL AND STATE REQUIRED.
 13-415.0, 415.1.ABCD, 415.1.A, 415.2, THERE ARE TOO
 NUMEROUS CODE SECTIONS TO LIST, PLEASE SEE CHAPTER 13
 OF THE 2001 FBC.
  
 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY
 CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS
 AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO
 SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED
 SEALED OR ORIGINAL SIGNATURE.
 **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN
 PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS
 JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS
 1 AND 3.
 PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES
 SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD
 OF ENGINEERS NOT ONLY FOR THE FACT THIS OFFICE HAS
 REPEATEDLY MADE THIS SAME COMMENT ON NUMEROUS PROJECTS
 TO THE SAME DESIGNER, BUT ALSO FOR INFORMATION ON PLANS
 AND ENERGY CALCULATIONS NOT COORDINATING.
 THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE
 FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC
 61G15-23.002, FBC 103.1.
 ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED
 THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND
 NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA
 FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004
 FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY
 AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS
 SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS. **
 PLEASE BE SURE TO GO OVER ALL AND CORRECT.
  
 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES
 DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION.
 PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER
 BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMITS, PLANS AND FEES.
 PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED
 ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL
 NEED TO BE CORRECTED.
 PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH
 BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS
 DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT
 NOT THE OTHERS.
  
 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES
 *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN
 ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE
 ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME
 SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS
 COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS
 MADE.
 ** THIS IS ALSO SHOWN ON LEGENDS ON OTHER SHEETS.
  
 5) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS.
 PLEASE SEE THIS WAS NOTED ON PREVIOUS REVIEW AND
 SPECIFICALLY NOTED TO SEE 700.12E FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS.
 PLEASE SEE THERE IS EMERGENCY AND EXIT LIGHTING
 FIXTURES WHICH ARE STILL MISSING CIRCUITING. (
 CLUBHOUSE)
 FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
 ** THIS WAS IN PREVIOUS REVIEWS NOTES #6, #7, AND NOTE
 #30 AT A MINIMUM. SPECIFICALLY 700.12E WAS NOTED.
  
 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS
 BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE
 HARDWIRED?
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD
 PLUG IN?
  
 7) NOTE: PLEASE CLARIFY WHERE THE ROOM AND AREA
 DESIGNATIONS ARE ON PLANS. EXAMPLE: BEDROOM #1, DINING
 ROOM, LIVING ROOM ETC.
 PLEASE KNOW THE PREVIOUS REVIEW REQUESTED FOR ALL
 CIRCUITING TO BE COMPLETED ON PLANS AND TO CORRELATE
 WITH PANEL SCHEDULES HOWEVER AS NOTED IN NOTE #5 ABOVE
 THIS IS STILL NEEDED IN MANY LOCATIONS.
 PLEASE SEE SHEET E16.05, WHICH INDICATES CIRCUITS CB32
 FOR ELEVATOR PIT LIGHTS AND RECEPTACLES AND INDICATES
 CB-30 FOR *H*.
 THE *H* IS NOT KNOWN AND BOTH CIRCUITS ON PANEL
 SCHEDULE CB ARE SHOWN A BLANK/SPARES.
 AS THESE CIRCUITS ARE NOT INDICATED WE CAN NOT
 DETERMINE MINIMUM COMPLIANCE WITH 620.22-620.25 PLEASE
 SEE OTHER ELEVATOR EQUIPMENT ROOMS AND AREAS WHICH SEEM
 TO INDICATE LIGHTING HOWEVER THE LIGHTING IS SHOWN
 CIRCUITED ON THE SAME LIGHTING AS GARAGE AND/OR OTHER
 COMMON AREAS.
 PLEASE VERIFY ALL ON PLANS, AND CORRELATE WITH PANEL
 SCHEDULES. THIS IS NOT ALL LOCATIONS.
 ** THIS WAS NOTED ON PREVIOUS REVIEWS NOTE # 9.
  
 8) NOTE: PLEASE SEE THE MISSING LIGHTING OUTSIDE FIRE
 PUMP ROOM AND STAIR AREA. PLEASE SEE MISSING
 PHOTO-METRICS ETC.
 PLEASE SEE MISSING PHOTO-METRICS FOR CLUBHOUSE STAIR
 AREA UNDER NORMAL AND EMERGENCY.
 PLEASE SEE THE LEVEL OF LIGHTING OUTSIDE MAIN
 ELECTRICAL ROOM FOR BOTH CONDITIONS OF NORMAL AND
 EMERGENCY DOES NOT SEEM TO MEET THE MINIMUM LEVELS
 REQUIRED. PLEASE SEE THE NORMAL LEVEL IS SHOWN ONLY AS
 6.38 AND LESS THAN 1FT CANDLES UNDER EMERGENCY?
 NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE KNOW AS THERE ARE NO LIGHTING FIXTURES,
 CIRCUITING ETC SHOWN FOR SOME AREAS, PLEASE COMPLETE.
 PLEASE ALSO BE SURE TO GO OVER ALL EGRESS PATHS
 ESPECIALLY STAIR AREAS. THERE ARE OTHER AREAS ALSO.
  
 PLEASE ILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS
 SHOWN AS A *J* FIXTURE. S NO FIXTURE LEGEND WAS
 SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME. PLEASE
 ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA AND MAIN
 ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY BATTERY
 BACK UP LIGHTING FIXTURE OF SOME KIND.
 NEC 700.12E, 700.16, LS-101 7.8, 7.9
 ** THIS WAS NOTE ON PREVIOUS REVIEWS NOTE #6
  
 9) NOTE: PLEASE SEE THE PREVIOUS NOTES QUESTIONED THE
 EGRESS PATH FROM CLUBHOUSE INTO THE GARAGE WHICH IS
 MAIL CENTER HALL AS THE EXIT LIGHT AND DOOR ON
 CLUBHOUSE PLANS SHOWS THE EGRESS INTO THIS AREA AND THE
 MAIL CENTER HALL AREA INDICATES EXIT LIGHTS WITH
 DIRECTIONAL INTO THE CLUBHOUSE???
 THERE ARE SEVERAL OTHER LOCATIONS WHERE EXIT LIGHTS ARE
 IN QUESTION BASED ON THE LAYOUTS SHOWN ON THE
 ELECTRICAL PLANS.
 SEE MAIL CENTER AREA ADJACENT TO PARKING AREA WHICH
 DOES NOT INDICATE ANY EXIT LIGHT FIXTURES DIRECTING AN
 OCCUPANT TO THE EXIT.
 THIS HAS BEEN GONE OVER WITH THE BUILDING PLAN REVIEWER
 AND COMMENTS WILL BE NOTED ON THESE LOCATIONS. THE LIFE
 SAFETY PLAN ALSO INDICATES WHAT IS BEING SHOWN AS
 EGRESS PATHS THROUGH PARKING SPACES ETC.
 PLEASE SEE COMMENTS FROM BUILDING REVIEWER, AND FIRE
 MARSHAL.
 PLEASE SEE CHAPTER 10 OF THE FBC AND CHAPTER 7 OF THE
 LIFE SAFETY CODE.
 THE EGRESS PATHS ARE NOT IN REVIEW OF THE ELECTRICAL
 REVIEWER HOWEVER AS MANY OF THE EXIT AND EMERGENCY
 LIGHTING ARE IN QUESTION AND THIS DIRECTLY AFFECTS THE
 ELECTRICAL PLANS THIS IS BEING NOTED FOR INFORMATION AT
 THIS TIME.
  
 10) NOTE: PLEASE SEE PLANS ARE NOT COMPLETE WITH WIND
 LOAD INFORMATION FOR SITE LIGHTING.
 IF NOT INCLUDED IN THE PLANS, THEN THESE WILL ALL BE
 REQUIRED TO BE UNDER SEPARATE PERMITS.
 ** THIS WAS NOTED ON NOTE #7 ON PREVIOUS REVIEWS.
  
 11) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION
 AS REQUESTED ON THE PREVIOUS REVIEWS.
 PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO
 THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE
 SEE NO TIMES AT 100% RUNNING IS SHOWN.
 PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE
 MARSHAL.
 PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3,
 DOES NOT CONTAIN THE TEXT FOR CODE.
 PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED
 AT THIS TIME.
 PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME
 INFORMATION.
 PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP,
 YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS
 INDICATE AN ELECTRICAL FIRE PUMP.
 PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE
 WITH PLANS.
 110.3, 90.7, NFPA-70 695, NFPA-20 2003
 **THIS WAS NOTED ON TWO PREVIOUS REVIEWS ON NOTE #10.
  
 12) NOTE: PLEASE LABEL ALL MAINS, MAIN 1 OF ? , 2OF ?
 /SERVICE #1 MAIN #1, SERVICE #2 MAIN #1, SERVICE #3
 MAIN 1 ETC.
 PLEASE BE SURE TO CONTACT THIS OFFICE WITH RESPECT TO
 PLAGUE DIRECTLY LABELING AND INFORMATION. THIS CAN BE
 GONE OVER WITH THE CHIEF ELECTRICAL INSPECTOR ALSO
 BEFORE PLAGUES ARE INSTALLED.
 PLANS SHOW 7 MAINS AT THIS TIME.
 PLEASE SEE 230.2, (E)
  
 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO ELEVATOR PLATFORMS WHICH MAY AFFECT
 ELECTRICAL PLANS AND LAYOUTS.
  
 14) NOTE: PLEASE SEE DOOR SWING FOR METER/ELECTRICAL
 ROOM 1C2, NEEDS TO SWING OUT.
 110.26
  
 15) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW AT THIS TIME ONE SET OF PLANS MAY BE
 RETAINED BY THIS OFFICE FOR PEER REVIEW AS THERE ARE
 SOME CODE SECTIONS WHICH HAVE STILL NOT BEEN COMPLIED
 WITH.
 PLEASE KNOW ONE GONE OVER THIS FEE MAY BE ASSESSED
 WHICH IS REQUIRED UNDER THE FLORIDA STATUTES. THIS FEE
 IS NOT TO THE CONTRACTOR/OWNER OR DEVELOPER THIS IS TO
 THE DESIGN PROFESSIONAL(S).
 ** PLEASE BE SURE TO GO OVER COMMENTS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-20 16:32:342007-09-20 16:32:34
  
 REVIEW COMMENCED
2007-09-16 13:07:432007-09-16 13:07:43
  
 IN ELEC FOR REVIEW