| Date |
Text |
| 2007-10-19 08:30:06 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | TEL:561-805-6713FAX: |
| | 561-805-6731 |
| | |
| | JAMES JOHNSTON, PERMIT NO 05091684 |
| | BUILDING PLAN EXAMINERII PROJECT |
| | NAME COURTNEY LAKES, BLDG. 1 |
| | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS |
| | 344 COURTNEY LAKES CIRCLE |
| | DATE OCTOBER 17, 2007 |
| | |
| | BUILDINGPLANREVIEW |
| | FLORIDA BUILDING CODE 2001 |
| | |
| | |
| | FOR YOUR INFORMATION?. |
| | THE PLANS SUBMITTED ARE DRAWN FOR THIS PROJECT?S |
| | BUILDINGS TO BE CONSTRUCTED IN PHASES.PLEASE SEE THE |
| | 2001 CODE RELATED SECTION 104.5.1.104.5.1.1, |
| | 104.5.1.2 -NOTED HEREIN -REFERCENING,?WORK NOT |
| | COMMENCED WITHIN 6 MONTHS AFTER DATE OF PERMIT ISSUANCE |
| | THE PERMIT SHALL BE REVOKED AND A NEW PERMIT SHALL BE |
| | ISSUED.? THE NEW PERMIT SHALL BE ISSUED UNDER THE2004 |
| | BUIDING CODENOT THE 2001, REQUIRING EXISTING PLANS TO |
| | BE REDRAWN IN COMPLIANCE WITH THIS CODE. |
| | |
| | 104.5 CONDITIONS OF THE PERMIT |
| | 104.5.1 PERMIT INTENT. A PERMIT ISSUED SHALL BE |
| | CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND |
| | NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER, OR SET |
| | ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR |
| | SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING |
| | OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF |
| | ERRORS IN PLANS, CONSTRUCTION, OR VIOLATIONS OF THIS |
| | CODE. EVERY PERMIT ISSUED SHALL BECOME INVALID UNLESS |
| | THE WORK AUTHORIZED BY SUCH PERMIT IS COMMENCED WITHIN |
| | 6 MONTHS AFTER ITS ISSUANCE, OR IF THE WORK AUTHORIZED |
| | BY SUCH PERMIT IS SUSPENDED OR ABANDONED FOR A PERIOD |
| | OF 6 MONTHS AFTER THE TIME THE WORK IS COMMENCED. |
| | |
| | 104.5.1.1 IF WORK HAS COMMENCED AND THE PERMIT IS |
| | REVOKED, BECOMES NULL AND VOID, OR EXPIRES BECAUSE OF |
| | LACK OF PROGRESS OR ABANDONMENT, A NEW PERMIT COVERING |
| | THE PROPOSED CONSTRUCTION SHALL BE OBTAINED BEFORE |
| | PROCEEDING WITH THE WORK. |
| | |
| | 104.5.1.2 IF A NEW PERMIT IS NOT OBTAINED WITHIN 180 |
| | DAYS FROM THE DATE THE INITIAL PERMIT BECAME NULL AND |
| | VOID, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE |
| | THAT ANY WORK WHICH HAS BEEN COMMENCED OR COMPLETED BE |
| | REMOVED FROM THE BUILDING SITE. ALTERNATELY, A NEW |
| | PERMIT MAY BE ISSUED ON APPLICATION, PROVIDING THE WORK |
| | IN PLACE AND REQUIRED TO COMPLETE THE STRUCTURE MEETS |
| | ALL APPLICABLE REGULATIONS IN EFFECT AT THE TIME THE |
| | INITIAL PERMIT BECAME NULL AND VOID AND ANY REGULATIONS |
| | WHICH MAY HAVE BECOME EFFECTIVE BETWEEN THE DATE OF |
| | EXPIRATION AND THE DATE OF ISSUANCE OF THE NEW PERMIT. |
| | |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ). |
| | COMMENT-SHEETSGN A1.05GN A1.06THESE SHEETS ARE |
| | NOT LEGIBLE. |
| | |
| | |
| | |
| | A 1804.2.2 SOIL TEST REPORT |
| | THE REPORT SUBMITTED IN 2003 REFERENCES A CONCLUSION OF |
| | BEARING CAPACITY |
| | FOR A SINGLE STORY STRUCTURE. WHERE THE BEARING |
| | CAPACITY OF THE SOIL IS |
| | NOT DEFINITELY KNOWN OR IS IN QUESTION, THE BUILDING |
| | OFFICIAL MAY REQUIRE |
| | LOAD TESTS OR OTHER ADEQUATE PROOF AS TO THE |
| | PERMISSIBLE SAFE BEARING |
| | CAPACITY AT THAT PARTICULAR LOCATION.TO DETERMINE THE |
| | SAFE BEARING |
| | CAPACITY OF SOIL, IT SHALL BE TESTED AT SUCH LOCATIONS |
| | AND LEVELS AS |
| | CONDITIONS WARRANT, BY LOADING AN AREA NOT LESS THAN 4 |
| | SQ FT (0.37 M{2}) |
| | TO NOT LESS THAN TWICE THE MAXIMUM BEARING CAPACITY |
| | DESIRED FOR USE.SUCH |
| | DOUBLE LOAD SHALL BE SUSTAINED BY THE SOIL FOR A PERIOD |
| | OF NOT LESS THAN |
| | 48 HOURS WITH NO ADDITIONAL SETTLEMENT TAKING PLACE, IN |
| | ORDER THAT SUCH |
| | DESIRED BEARING CAPACITY MAY BE USED.SUBSOIL |
| | CONDITIONS SHALL BE |
| | EXAMINED AT THE EXPENSE OF THE OWNER, WHEN DEEMED |
| | NECESSARY BY THE |
| | BUILDING OFFICIAL. |
| | COMMENTPLEASE FURNISH A SOIL TEST REPORT APPLICABLE |
| | FOR THE THREE BUILDINGS ?FIVE STORIES EACH TO BE |
| | CONSTRUCTED WITH THE RECOMMENDATIONS FOR PROPER GROUND |
| | PREPARATION TO ACHIEVE THE DESIRED BEARING CAPACITY |
| | FOR EACH BUILDING. |
| | TWO COPIES OF THIS REPORT SHALL BE INCLUDED FOR EACH |
| | SEPARATE BUILDING PROJECT.THE REPORT IS TO ENCOMPASS |
| | THE THREE BUILDINGS, TWO COPIES FOR EACH BUILDING |
| | |
| | A-1 FBC1816.1SOIL TREATMENT |
| | COMMENTIDENTIFY THE CHEMICAL SOIL TREATMENT TO BE |
| | USED IN THE SLAB NOTES SHEET APS3.21 |
| | |
| | |
| | B PRODUCT APPROVALS |
| | COMMENTTHE FLORIDA PRODUCT APPROVAL COVER SHEET |
| | SHALL INCLUDE THE APPROVAL INFORMATION FOR THE PRODUCT |
| | SELECTED.SEE ATTACHED SAMPLE INCLUDED. |
| | THE DESIGNER OF RECORD SHALL REVIEW EACH APPROVAL?S |
| | SPECIFICATION PACKETAND ACKNOWLEDGE SAME ON THE |
| | APPROVAL COVER SHEETBY NAME DATE AND STATEMENT OF |
| | ACCEPTANCE |
| | |
| | |
| | B-1 WINDOWS / DOORS PRODUCT APPROVALS |
| | WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE |
| | 9B-72FLORIDA PRODUCT APPROVAL |
| | SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT |
| | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S |
| | SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR |
| | KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS |
| | AND SPECIFICATIONS.SEE:WEB SITE |
| | WWW.FLORIDABUILDING.COM |
| | NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE |
| | BY LEGACYFPA |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | |
| | B-2 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT |
| | APPROVAL COVER |
| | PAGE FOR THE FOLLOWING |
| | OPERABLE WINDOWS |
| | FIXED GLASS |
| | MULLION TUBES |
| | PANEL WALLS |
| | STORE FRONT GLAZING SYSTEM |
| | ALUMINUM OUT -SWING DOORS |
| | HOLLOW METAL DOORS |
| | TRUSS ANCHORS |
| | ROOFINGCOMPONENTS |
| | SHUTTERS |
| | SKYLIGHTS |
| | OVERHEAD GARAGE DOOR |
| | COMMENT-PLEASE COMPLY |
| | |
| | B-3 3RD REQUEST ? |
| | COMMENT-FURNISH THE FOLLOWING PRODUCT REPORTS |
| | TRACO OPERABLE WINDOWSNON IMPACT 0? TO 30?,LARGE |
| | MISSILE 30? TO 60? |
| | TRACO FIXED WINDOWS |
| | MULLIONS |
| | EXTERIOR HOLLOW METAL DOORS |
| | EXTERIOR GLAZED DOORS |
| | EXTERIOR LOUVER DOORS |
| | EXTERIOR RAILINGS, ENGINEERING REQUIRED |
| | LOUVERS,NO REPORT SUBMITTED |
| | ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION, |
| | UNDERLAYMENT,ROOF TILE,ROOF SYSTEM |
| | IDENTIFY EACH COMPONENT TO BE USED |
| | RATIONAL ANALYSIS FOR ZONE 2 AND THREE |
| | EFIS WALL SYSTEM (IF USED) |
| | 5/8? AQUA ROCK SHEATHING |
| | ROLL UP DOOR |
| | WOOD BASE STRUCTURAL PANELSFBC 2315.1.11 |
| | |
| | |
| | B-4 FBC2405PROVIDE DESIGN LOADS ON ALL WINDOW , |
| | DOOR, COMPONENTS ON SCHEDULE |
| | 1. NEGATIVE WIND LOAD - DEAD LOAD |
| | 2. POSITIVE WIND LOAD + DEAD LOAD |
| | 3. DEAD LOAD + 1/2 POSITIVE WIND LOAD |
| | WIND LOADS SHALL BE DETERMINED FROM 1606. THE DEAD LOAD |
| | FOR THE GLASS IN LB/SQ FT SHALL BE TAKEN AS THE TOTAL |
| | THICKNESS OF THE GLASS PANES AND PLIES IN INCHES X 13. |
| | THIS APPLIES FOR GLASS 30 DEGREES OR LESS FROM |
| | HORIZONTAL. FOR OTHER SLOPES THE GLASS DEAD LOAD IS |
| | EQUAL TO THIS VALUE TIMES THE COSINE OF ITS SLOPE FROM |
| | HORIZONTAL. |
| | |
| | |
| | B-5 FBC2411.3.1.4 THE ARCHITECT OR PROFESSIONAL |
| | ENGINEER OF RECORD SHALL BE |
| | REQUIRED TO SPECIFY THE DESIGN WIND PRESSURE, |
| | DETERMINED IN ACCORDANCE |
| | WITH CHAPTER 16 (HIGH VELOCITY HURRICANE ZONES), FOR |
| | ALL GARAGE DOORS, |
| | SKYLIGHTS OPERATIVE WINDOWS AND FIXED GLAZING.THE |
| | DESIGN WIND PRESSURE |
| | FOR EACH COMPONENT OF THE EXTERIOR BUILDING SURFACE, |
| | SHALL BE |
| | INCORPORATED INTO THE BUILDING DESIGN DRAWING SO AS TO |
| | ALLOW THE |
| | RESPECTIVE MANUFACTURER TO SIZE THE PREFABRICATED |
| | ASSEMBLY FOR THE |
| | PROPER WIND PRESSURES. |
| | COMMENTPLEASE PROVIDE THIS INFORMATION ON THE |
| | ELEVATIONS |
| | |
| | |
| | C FBC105.13 THRESHOLD BUILDING |
| | 105.13.2 THE SPECIAL INSPECTOR SHALL INSPECT THE |
| | SHORING AND RE-SHORING |
| | FOR CONFORMANCE TO THE SHORING AND RE-SHORING PLANS |
| | SUBMITTED TO THEENFORCING AGENCY.A FEE SIMPLE TITLE |
| | OWNER OF A BUILDING WHICH DOES NOT MEET THE MINIMUM |
| | SIZE, HEIGHT, OCCUPANCY, OCCUPANCY CLASSIFICATION OR |
| | NUMBER-OF-STORIES CRITERIA WHICH WOULD RESULT IN |
| | CLASSIFICATION AS A THRESHOLD BUILDING UNDER |
| | ?553.71(7) FLORIDA STATUTES, MAY DESIGNATE SUCH |
| | BUILDING AS A THRESHOLD BUILDING, SUBJECT TO MORE THAN |
| | THE MINIMUM |
| | NUMBER OF INSPECTIONS REQUIRED BY THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | COMMENTPLEASE FURNISH A SHORING AND RE-SHORING PLAN |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | D SITE PLAN AND ASSOCIATED COMPONENTS REQUIRED3RD |
| | REQUEST(NOT INCLUDED) |
| | (A) PARKING SPACES LOCATED OUTSIDE AND UNDERNEATH THE |
| | BUILDING. CURBING, RAMPS, ACCESSIBLE ISLES FOR THE |
| | HANDICAP, SIGNAGE, SIDEWALKS, CURB CUTS, PEDESTRIAN |
| | CROSS WALKS |
| | (B) HANDICAP SPACES LOCATED OUTSIDE AND UNDERNEATH THE |
| | BUILDING PERIMETER. IDENTIFY ALL HANDICAP PARKING |
| | SPACES AS DEFINED BY THEAMERICANS WITH DISABILITIES |
| | FLORIDA BUILDING CODE CHAPTER 11 PART BANSIA117-1 |
| | ANDFAIR HOUSING ACT GUIDELINES |
| | (C) IDENTIFY THE ACCESSIBLE ROUTE AS DEFINED BY |
| | THE AMERICANS WITH DISABILITIES- FLORIDA BUILDING |
| | CODE CHAPTER 11 AND FAIR HOUSING ACT GUIDELINES |
| | (D) IDENTIFY VAN ACCESSIBLE PARKING SPACES UNDER |
| | BUILDING AND EXTERIOR IN COMPLIANCE WITH THE AMERICANS |
| | WITH DISABILITIES FLORIDA BUILDING CODE CHAPTER 11AND |
| | FAIR HOUSING ACT GUIDELINES, NOTE PARKING SPACES FOR |
| | VANS SHALL HAVE VERTICAL CLEARANCE OF 98? |
| | (E) ONE ACCESSIBLE ROUTE FAIR HOUSING, FROM THE |
| | BOUNDARY SITES PUBLIC TRANSPORTATION STOP TO AN |
| | ACCESSIBLE BUILDING ENTRANCE. CHAPTER 11, PART B ? |
| | ANSI A117.1,502.6 |
| | COMMENTPLEASE FURNISH A SEPARATE SITE PLAN FOR |
| | BUILDING NO 1. INCLUDE ALL INFORMATION REQUESTED FOR |
| | COMPLIANCE. |
| | |
| | E FBC411.2 AUTOMOBILE PARKING GARAGES |
| | 411.2.1 AUTOMOBILE PARKING GARAGES SHALL BE CLASSIFIED |
| | AS EITHER OPEN, AS DEFINED IN 411.3, OR ENCLOSED AND |
| | SHALL MEET THE APPROPRIATE CRITERIA OF 411.3 OR 411.4. |
| | |
| | E-1 FBC411.3ENCLOSED PARKING GARAGES |
| | |
| | FBC 411.4.1 ENCLOSED AUTOMOBILE PARKING GARAGES AND |
| | PORTIONS THEREOF WHICH DO NOT MEET THE DEFINITION OF |
| | OPEN PARKING GARAGES SHALL BE LIMITED TO THE ALLOWABLE |
| | HEIGHTS AND AREAS SPECIFIED IN TABLE 500 FOR GROUP S |
| | BUILDINGS. |
| | 411.4.2 A MECHANICAL VENTILATION SYSTEM FOR THE |
| | REMOVAL OF THE PRODUCTS OF COMBUSTION SHALL BE |
| | PROVIDED IN ENCLOSED AUTOMOBILE PARKING GARAGES. THE |
| | MECHANICAL SYSTEM SHALL BE CAPABLE OF PROVIDING AT |
| | LEAST 6 AIR CHANGES PER HOUR FOR EACH LEVEL. UNDER |
| | NORMAL USE THE VENTILATION OF THE |
| | ENCLOSED AUTOMOBILE PARKING GARAGE SHALL COMPLY WITH |
| | THE VENTILATION REQUIREMENTS OF 411.5. |
| | 411.2.2 THE CLEAR HEIGHT OF EACH FLOOR LEVEL IN |
| | VEHICLE AND PEDESTRIAN TRAFFIC AREAS SHALL NOT BE LESS |
| | THAN 7? |
| | |
| | E-2 FBC 411.3 OPEN PARKING GARAGES411.3.1 |
| | OPEN AUTOMOBILE PARKING GARAGES WITH ROOF PARKING MAY |
| | BE CONSTRUCTED TO THE ALLOWABLE HEIGHTS AND AREAS |
| | SPECIFIED IN TABLE 411.3.1. TO BE CONSIDERED OPEN, THE |
| | GARAGE SHALL MEET THE REQUIREMENTS OF411.3.2, |
| | 411.3.3 AND411.3.4. |
| | |
| | 411.3.2 THE EXTERIOR AND INTERIOR WALLS OF THE GARAGE |
| | SHALL BE DESIGNED IN ACCORDANCE WITH ONE OF THE |
| | FOLLOWING: |
| | 1. AT LEAST 50 PERCENT OF THE CLEAR HEIGHT BETWEEN |
| | FLOORS SHALL BE OPEN TO THE ATMOSPHERE FOR THE FULL |
| | LENGTH OF AT LEAST TWO EXTERIOR WALLS, EXCLUDING |
| | REQUIRED STAIR AND ELEVATOR WALLS AND STRUCTURAL |
| | COLUMNS. INTERIOR WALL LINES AND COLUMN LINES SHALL BE |
| | AT LEAST 20 PERCENT OPEN AND UNIFORMLY DISTRIBUTED, OR |
| | 2. THE EXTERIOR WALLS OF THE STRUCTURE SHALL HAVE |
| | UNIFORMLY DISTRIBUTED OPENINGS ON TWO OR MORE SIDES |
| | TOTALING NO LESS THAN 40 PERCENT OF THE BUILDING |
| | PERIMETER. THE AREA OF SUCH OPENINGS IN THE EXTERIOR |
| | WALLS ON EACH LEVEL SHALL BE AT LEAST 20 PERCENT OF THE |
| | TOTAL PERIMETER WALL AREA OF EACH LEVEL. INTERIOR WALL |
| | LINES AND COLUMN LINES SHALL BE AT LEAST 20 PERCENT |
| | OPEN AND UNIFORMLY DISTRIBUTED. |
| | COMMENTPLEASE VERIFY OPEN OR ENCLOSED WITH THE CODE |
| | SECTIONS PROVIDED HEREIN |
| | |
| | F FBC104.3 EXAMINATION OF DOCUMENTS |
| | 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL |
| | EXAMINE OR CAUSE TO BE EXAMINED EACH APPLICATION FOR A |
| | PERMIT AND THE ACCOMPANYING DOCUMENTS, CONSISTING OF |
| | DRAWINGS, SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL |
| | DATA, AND SHALL ASCERTAIN BY SUCH EXAMINATIONS WHETHER |
| | THE CONSTRUCTION INDICATED AND DESCRIBED IS IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF THE TECHNICAL CODES |
| | AND ALL OTHER PERTINENT LAWS OR ORDINANCES. |
| | COMMENTSHEETAP S3.12PARTIAL 2ND FLOOR PLAN DETAIL |
| | 11-S4.21AT ?SLAB OPEN AREA NO SLAB? |
| | THIS DETAIL IS FOR THE ELEVATOR AND STAIRWAY, PLEASE |
| | CLARIFY. |
| | G FBC106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ). |
| | COMMENT-IDENTIFY EXPANSION JOINT MATERIAL.PROVIDE |
| | MANUFACTURER SPECIFICATIONS |
| | |
| | G-1 COMMENT- DEFINE BUILT UP ROOFING ELEVATIONS FOR |
| | POSITIVE DRAINAGE ON THE FOLLOWING PLAN SHEETS |
| | AP-A5.05,AP-A5.10,AP-A5.20 |
| | |
| | G-2 COMMENT- WALL SECTIONS REFER TO SHEET A1.04. |
| | PLEASE FURNISH THE I.D. SHEET GN-A1.04 |
| | |
| | G-3 COMMENT- SOME OF THE WALL SECTIONS ON THE |
| | ARCHITECTURAL FLOOR PLANS DO NOT MATCH THE INTENDED |
| | UNIT DETAILS BECAUSE, VARIOUS WALLS ARE END WALLS AND |
| | OTHERS ARE LOCATED NEAR A STAIRWAY. PLEASE IDENTIFY THE |
| | WALL SECTIONS ON THE ARCHITECTURAL FLOOR PLANS THAT ARE |
| | APPLICABLE FOR ITS CONDITION. |
| | |
| | G-4 COMMENT- CLUBHOUSE OCCUPANCY IS RATED A. PLEASE |
| | ADD TO SHEET GN-A1.02 |
| | |
| | H FLORIDA ACCESSIBILITY CODE CHAPTER 11 |
| | COMMENT-MEN?S BATHROOM WALL PARTITIONS ARE |
| | ENCROACHING INTO TOILET ROOM SEE ADA FIG 28 |
| | WOMEN?S BATHROOMWALL PARTITIONS ARE ENCROACHING INTO |
| | TOILET ROOM SEE ADA FIG 28 |
| | DETAIL ALL BATHROOM ACCESSORIES, GRAB BARS, TOILET |
| | PAPER HOLDER, PAPER TOWEL DISPENSER, MIRROR |
| | PLEASE NOTE THE BATHROOMS ARE NOT CONSIDERED A STALL |
| | |
| | H-1 FLORIDA ACCESSIBLE CODE11-4.10 ELEVATORS |
| | 11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. THE FLOOR AREA |
| | OF ELEVATOR CARS SHALL PROVIDE SPACE FOR WHEELCHAIR |
| | USERS TO ENTER THE CAR, MANEUVER WITHIN REACH OF |
| | CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE DOOR |
| | OPENING AND INSIDE DIMENSIONS SHALL BE AS SHOWN IN |
| | FIGURE 11-22. THE CLEARANCE BETWEEN THE CAR PLATFORM |
| | SILL AND THE EDGE OF ANY HOIST WAY LANDING SHALL BE NO |
| | GREATER THAN 1-1/4 INCHES (32 MM). |
| | COMMENTAP-A8.10 PROVIDE A FLOOR PLAN OF THE |
| | ELEVATOR CAB UTILIZING THIS SECTION OF THE ADA |
| | |
| | H-2 FBC1814.1ELEVATOR PIT |
| | COMMENTAP-A8.10 WHERE REQUIRED. WHERE A |
| | GROUNDWATER TABLE INVESTIGATION INDICATES THAT |
| | HYDROSTATIC PRESSURE CONDITIONS EXIST, WALLS AND FLOORS |
| | RETAINING EARTH AND ENCLOSING SPACES BELOW FINISHED |
| | GROUND LEVEL SHALL BE WATERPROOFED IN ACCORDANCE WITH |
| | ?1814.2. WHERE HYDROSTATIC PRESSURE CONDITIONS DO NOT |
| | EXIST, DAMP PROOFING AND PERIMETER DRAINAGE SHALL BE |
| | PROVIDED IN ACCORDANCE WITH 1814.3. |
| | |
| | I FBC1003.2 |
| | COMMENT-AP-A8.01SECTION 15? PLEASE DETAIL THE |
| | STAIRWAYS FOR TREAD DEPTH, CHANGES AT LANDINGS AND |
| | HEADROOM CLEARANCE FROM TREAD TO BEAM ABOVE. |
| | |
| | J FBC1606STRUCTURAL LOADS |
| | COMMENT-SUBMIT ENGINEERING DESIGN FOR THE BALCONY |
| | RAILINGS IN COMPLIANCE WITH THIS SECTION. |
| | |
| | K FBC1404.1.1ARCHITECTURAL TRIMABOVE 3 STORIES OR |
| | 40 FT |
| | COMMENT-IDENTIFY THE FASTENING HARDWARE TO BE USED |
| | IN SECURING THE FOAM TRIM TO THE BUILDING EXTERIOR |
| | SURFACE |
| | |
| | L FBC705PROTECTION OF OPENINGS AP-A8.20 |
| | IDENTIFY THE FIRE RATING FOR THE TRASH CHUTE DOORS |
| | |
| | |
| | |
| | PREVIOUS PLAN REVIEWER?S COMMENTSDATED5/22/07 |
| | |
| | 12B) 3RD REQUEST: |
| | PLEASE INCORPORATE THE CIVIL DRAWINGS INTO THIS PLAN |
| | FOR REVIEW, NOT A NOTE REFERENCING CHAPTER 11. |
| | THE ACCESSIBLE ROUTE MUST BE DESIGN, REVIEWED AND |
| | CONSTRUCTED BY THE PLAN. |
| | SEE THIS PLAN REVIEWER?S COMMENT ITEM ?D? |
| | |
| | 12B1) PLEASE PROVIDE INFORMATION FOR VAN |
| | ACCESSIBILITY. SEE THIS PLAN REVIEWER?S COMMENT ITEM |
| | ?D? |
| | |
| | 12B2) PLEASE PROVIDE A DETAIL OF THE SIGN WITH THE |
| | HANDICAP SYMBOLS AND COLORS. PROVIDE A DETAIL OF THE |
| | POLE HEIGHT FROM THE EXTERIOR GRADE TO THE SIGN AS PER |
| | FA CHAPTER 11 |
| | |
| | 12C) PLEASE PROVIDE A SITE PLAN WITH PARKING UNDERNEATH |
| | THE BUILDING, CURB CUTS,PEDESTRIAN CROSS WALKS, |
| | RAMPS, HANDICAP TEXTURE SURFACES ON THE RAMPS, RAMP |
| | WIDTH, RAMP PITCH, RAMP CONNECTION TO SIDEWALK. |
| | |
| | 14E) THIS COMMENT IS REQUESTING A REFERENCE TO A DROP |
| | CEILING IN THE LEASING OFFICE CLOSET. |
| | CUT SECTION AP-A7.04 DETAIL IS A STAIR LANDING DETAIL |
| | ??? |
| | |
| | 22C) ARCHITECTURAL TRIM LOCATED ABOVE 40?. |
| | SEE THIS PLAN REVIEWER?S COMMENT K. PROVIDE THE TYPE OF |
| | FASTENERS, SIZE, LENGTH, SPACING OF FASTENERS AND ALL |
| | RELATED HARDWARE, AS TO GAUGE OF METAL, DESCRIPTION, |
| | |
| | 23) PRODUCT APPROVALS PLEASE SUBMIT THIS IS THE 3RD |
| | REQUEST |
| | SEE THIS PLAN REVIEWER?S COMMENT B |
| | |