| Date |
Text |
| 2006-12-21 15:18:48 | DENIED:2001 FLORIDA BUILDING CODE |
| | |
| | BUILDING #1:PLEASE NOTE, PAGES HAVE CHANGED SINCE |
| | PREVIOUS REVIEW DATED 1-31-06 |
| | |
| | RESPONSE TO COMMENT 1:RESPONSE INDICATES VENTILATION |
| | CALCULATIONS ON SHEET M15.23. PLAN SHEET M15.23 IS |
| | WAS NOT SUBMITTED FOR REVIEW, BUT THE CALCULATION DOES |
| | APPEAR ON PLAN SHEET M15.07,CALCULATIONS WERE NOT |
| | GIVEN THE THE UNITS. |
| | |
| | RESPONSE TO COMMENT 2:OKAY |
| | |
| | RESPONSE TO COMMENT 3:RESPONSE INDICATES THE AHU |
| | CLOSET DOOR WAS CHANGED ON THE DOOR SCHEDULE A9.02 TO A |
| | NON-COMUSTIBLE DOOR.THIS IS NOT THE CASE, THE DOOR |
| | SCHEDULE INDICATES A WOOD DOOR.PLEASE ALSO NOTE ON |
| | PLAN SHEET M15.01, M15.02, & M15.03KEY NOTE #11 |
| | INDICATES A "FULL HEIGHT LOUVERED DOOR" WHICH IS NOT |
| | REFLECTED ON THE DOOR SCHEDULE.PLEASE CORRELATE. |
| | PLEASE ALSO NOTE, THE CONDENSATE LINE SHALL ALSO BE OF |
| | NON-COMBUSTIBLE MATERIAL. |
| | |
| | RESPONSE TO COMMENT 4:RESPONSE INDICATES CLEARANCE |
| | AROUND THE AHU EXCEEDS THE MINIMUM OF 4" AS REQUIRED IN |
| | 2001 FMC 603.1.3.THIS NOT WHAT IS DEPICTED IN THE |
| | DETAIL OF THE AHU MOUNTING DETAIL ON PLAN SHEET M15.09. |
| | PLEASE REVISE PLAN TO REFLECT PROPER CLEARANCE.PLEASE |
| | ALSO NOTE THE AFOREMENTIONED DETAIL SHOWS OUTSIDE AIR |
| | DUCT.THIS IS NOT INDICATED ON ANY OF THE PLANS, |
| | PLEASE PROVIDE DUCT SIZE, LAYOUT, MATERIAL AND INTAKE. |
| | |
| | RESPONSE TO COMMENT 5:RESPONSE INDICATES "CONDENSATE |
| | TRAP DETAIL" ON SHEET M15.22.SHEET M15.22 WAS NOT |
| | SUBMITTED.PLEASE NOTE, THE ORIGINAL COMMENT REQUESTED |
| | INFORMATION ON THE AUXILIARY DRAIN PAN & OVERFLOW |
| | PROTECTION AS REQUIRED IN 2001 FMC 307.2.3.COMMENT |
| | WAS NOT ADDRESSED. |
| | |
| | RESPONSE TO COMMENT 6:RESPONSE STATES "TYPICAL |
| | CONDENSING UNIT INSTALLATION DETAIL" ON SHEET M15.22. |
| | THIS SHEET WAS NOT SUBMITTED. |
| | |
| | RESPONSE TO COMMENT 7 ALSO REFERS TO SHEET M15.22 WHICH |
| | WAS NOT SUBMITTED FOR REVIEW. |
| | |
| | RESPONSE TO COMMENT 8:OKAY |
| | |
| | RESPONSE TO COMMENT 9:RESPONSE REFERS TO PLAN SHEETS |
| | M15.05 THROUGH M15.08.KEY NOTE ON SHEETS INDICATES |
| | M15.05 THROUGH M15.08 3/4 PVC CONDENSATE TO TERMINATE |
| | BEUOND EXTERIOR WALL.PLEASE ANNOTATE THE FOLLOWING: |
| | |
| | |
| | A) EXTERIOR TERMINATION SHALL BE A MINIMUM OF 12" |
| | FROM BUILDING STRUCTURE PER 2001 FBC 1503.4.4. |
| | |
| | B) PVC IS COMBUSTIBLE AND SHALL NOT BE INSTALLED |
| | IN THE PLENUM OF THE AHU CLOSET. |
| | |
| | RESPONSE TO COMMENT 10: OKAY |
| | |
| | *******************NEW COMMENT******************** |
| | |
| | 11. PLAN SHEET A8.20 INDICATES THE TRASH CHUTE.PER |
| | 2001 FBC 705.2.4.6, AN APPROVED AUTOMATIC SPRINKLER |
| | SYSTEM SHALL BE INSTALLED AT THE TOP AND AT ALTERNATE |
| | FLOOR LEVELS IN REFUSE AND LAUNDRY CHUTES AND IN THE |
| | TERMINATION & INCINERATOR ROOMS. |
| | |
| | *****REVIEW IN PROGRESS********* |