Plan Review Notes
Plan Review Notes For Permit 05091684
Permit Number 05091684
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-01 13:54:45 
 **** UNSAT2ND REVIEW ********
  
 COURTNEY LAKES BUILDING #1
 N. CONGRESS.
  
 ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE
 PREVIOUS REVIEW STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND
 PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW
 COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH
 SET.
 PLEASE SEE THE COMMENTS ON BUILDING ONE ARE DIFFERENT
 IN MANY ASPECTS BASED ON THE DESIGN ALONE AND PROPOSED
 PHASES OF PROJECT.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON
 PLANS SUBMITTED.
  
 ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE
 PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY
 A "NO, OK, NO/OK, N/A OR SEE NEW ".
 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO
 BETTER EXPLAIN COMMENT MADE.
 2) OK, WILL HAVE PREVIOUS NOTE REMOVED.
 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED
 BY FURTHER EXPLANATION OF PREVIOUS NOTE.
 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO
 THIS BUILDING AND PREVIOUS NOTE IS REMOVED.
  
 ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF
 PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH
 **** NEW NOTES**.
  
  
 1) NOTE: NO, PLEASE SEE THE SETS ARE NOT BOUND TOGETHER
 IN A FASHION TO SECURE ALL SHEETS.
 PLEASE SEE THE PLANS SUBMITTED FOR BUILDING #1 ARE ALL
 FALLING APART AND WERE NOT SECURELY PUT TOGETHER.
 PLEASE SEE THE STAPLES BEING USED DO NOT GO THROUGH ALL
 SHEETS.
 PLEASE SEE SOME SETS WERE ALREADY COMING APART BEFORE
 THEY WERE OPENED FOR REVIEW. PLEASE SEE THIS IS
 REQUIRED FOR ALL SETS AND FOR ALL PLANS.
 PLEASE OBTAIN A METHOD TO SECURE AND BOUND PLANS
 TOGETHER.
 IF PLANS COME BACK IN THE SAME FASHION, THIS OFFICE
 WILL CONTACT THE CONTRACTOR TO COME IN AND PICK UP
 PLANS TO BE CORRECTED BEFORE PROCESSING AND BEFORE
 REVIEW WILL TAKE PLACE.
 THE STAPLES IN SOME HAVE ALREADY COME COMPLETELY OUT.
 THIS COMMENT IS FOR ALL WHETHER OR NOT COMMENT IS MADE
 FOR OTHER BUILDINGS OR BY OTHER TRADES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETED PLANS BOUND TOGETHER IN AN
 APPROPRIATE FASHION. PLEASE SEE ALL SHEETS WERE
 SUBMITTED LOOSELY AND NOT BOUND IN SETS.
  
  
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS
 DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES
 RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS
 PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE
 THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS
 ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH
 RESPECT TO THIS FROM OTHER TRADES.
 THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002
 NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT
 NFPA-101 IS NOTED )
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN
 EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA
 ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME
 ELECTRICAL COMMENTS WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED
 FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS
 ON OCT 1ST, 2005.
  
 4) NOTE:NO, PLEASE SEE THE PREVIOUS NOTES AS THE
 PHASING OF THIS BUILDING #1 WILL STILL BE OF CONCERN.
 AS NOTED ON PLANS, IT IS THE INTENT TO OCCUPY PHASES OF
 THE BUILDING INSTEAD OF COMPLETING ALL AT ONCE. PLEASE
 SEE THERE ARE SEVERAL ISSUES WHICH CREATE AN CONCERN
 FOR LIFE SAFETY OF NOT ONLY THE OCCUPANTS HOWEVER ALSO
 FOR CONSTRUCTION WORKERS PER OSHA REGULATIONS FOR
 GUARDING O LIVE PARTS AND EXPOSEURE TO UNQUALIFIED
 PERSONNEL PER 110.27.
 PLEASE SEE NO INFORMATION FOR SPRINKLER PROTECTION AND
 HOW SYSTEMS WHICH FEED FROMONE TO ANOTHER SECTION
 WILL TAKE PLACE.
 PLEASE SEE THERE ARE CIRCUITS IN PHASES TWO AND THREE
 WHICH ARE BEING FED FROM PANELS ALREADY ENERGIZED UNDER
 PHASE ONE.
 THE HAZARD OF SYSTEMS BEING FED FROM OTHER PARTS OF THE
 BUILDING WHICH ARE FROM EQUIPMENT ALREADY ENERGIZED IS
 OF CONCERN. NO INFORMATION OF SCHEDULE SHUT DOWN BY THE
 DESIGNER AND CONTRACTOR WAS SUBMITTED.
 PLEASE KNOW DUE TO THE CIRCUITING AS SHOWN ON PLANS FOR
 BRANCH CIRCUITS, FEEDERS ETC APPROVAL OF THE WAY THE
 PROPOSED CONSTRUCTION WILL TAKE PLACE IS NOT FINALIZED
 AT THIS TIME. PLEASE ALSO SEE COMMENTS FROM OTHER
 TRADES LIKE THE FIRE MARSHAL AND BUILDING PLAN REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 4) NOTE: PLEASESEE THAT THREE SEPARATE PERMIT
 APPLICATIONS WERE SUBMITTED AND NOTED FOR BLDG'S 1,2
 AND 3, HOWEVER PLANS SHOWS BLDG TYPES 1.2&3
 STRUCTURALLY ONLY ONE BUILDING.
 PLEASE SEE PERMIT APPLICATIONS ALL REFLECT THIS ONE 450
 UNIT BLDG.
 PLEASE SEE THIS CONTRADICTS THE "PHASING PLAN"
 SUBMITTED ON A1.04 AS THIS PHASING PLAN INDICATES WORK
 ON BLDGS 4 AND 5 BEFORE COMPLETION OF BLDGS 1, 2 AND
 3.
 PLEASE SEE COMMENTS FROM BLDG, FIRE AND OTHER
 REVIEWERS, AS CERTIFICATES OF OCCUPANCY(CO'S) FOR
 THESE CAN NOT BE GRANTED IN THIS ORDER AS THE FIRST
 "STRUCTURED BLDG"(1,2&3) WOULD NOT BE COMPLETE.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY
 CO'S" WHICH MAY ALLOW OCCUPANCY OF SOME PARTS OF BLDGS,
 HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30
 DAYS AND A MAX OF 3 TCO'S MAY ONLY BE GRANTED BY THE
 BLDG OFFICIAL.
 PLEASE KNOW, IN ANY CASE, ALL LIFE SAFETY, FIRE
 PROTECTION SYSTEMS, FIRE SPRINKLERS (FULLY CHARGED),
 ELECTRICAL SYSTEMS ETC SHALL BE COMPLETE IN THE BASE
 BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A TCO,/CO CAN BE
 GRANTED.
 *************************************
 ALSO NOTED THAT BLDG'S TYPE 4 AND 5 WHICH ARE SEPARATE
 STRUCTURES AND INDEPENDENT OF EACH OTHER WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE ALL PERMITS SUBMITTED AFTER OCT. 1ST, 2005
 SHALL FALL UNDER THE 2004 FBC, WITH ALL OTHER CODES
 ADOPTED BY SAID CODE AND STATE OF FLORIDA.
  
 ************************************
 PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) WITH RESPECT
 TO THIS.
  
 *************************************
 PLEASE ALSO SEE NEXT COMMENT WITH RESPECT TO THE MAINS,
 SERVICES, AND METER RMS AS PROPOSED.
 ** SEE ALL NOTES FROM ALL REVIEWERS WHICH MAY ALSO
 AFFECT THIS SEQUENCE OF CONSTRUCTION.
  
 5) NOTE: NO/OK. PLEASE SEE NOTE #4 ABOVE AND PLEASE
 SEE AS THE RISER HAS BEEN REVISED TO WHAT APPEARS TO BE
 NEW MAINS. PLEASE PROVIDE INFORMATION ON THE MAIN BEING
 SHOWN. RISER AND PLANS MAKE REFERENCE TO THESE BEING
 ?SHUNT-TRIP? WHICH ARE OK, HOWEVER PLEASE BE SURE EACH
 MAIN CONTAINS THE MANUAL MEANS OF DISCONNECT RATED FOR
 THE LOED SERVED AS REQUIRED PER 230.79 AND 230.76.
 PLEASE SEE RISER MENTIONS TO SEE METER CENTER RISER
 NOTES, HOWEVER RISER NOTES EACH METER CENTER WITH MAINS
 ALSO. PLEASE SEE NEW NOTES PERTAINING TO GROUNDING.
 PLEASE SEE PLANS DO NOT CORRELATE WITH THE RISER FOR
 ALL HOUSE PANELS AND EQUIPMENT. PLEASE SEE PLANS STILL
 INDICATE HOUSE METERS AT EACH ELECTRICAL ROOM WHEN THE
 RISER SHOWS ONE HOUSE METER/CT AND ALL HOUSE PANELS ARE
 FED FROM THE NEW DP.
 PLEASE SEE NEW NOTES FOR MANY OF THE REVISED ITEMS ON
 RISER.
 PLEASE SEE THE NOTES ABOVE WITH RESPECT TO PHASING OF
 THE PROJECT AND PANELS/FEEDERS AND BRANCH CIRCUITS
 CROSSING OVER PHASED AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 5) NOTE: PLEASE SEE METER RMS AS SHOWN WOULD BE OK,
 HOWEVER STRUCTURE AS SHOWN FOR BLDG TYPE 1, 2 AND 3
 (ONE BLDG) WOULD REQUIRE MAINS TO BE GROUPED. 90.4,
 230.2, 230.70, 230.72, 230.76, 230.79 ETC.
 BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN ONE SERVICE AT
 SEPARATE LOCATIONS SHALL BE DIVIDED INTO SECTIONS AND
 SHALL HAVE THOSE SECTIONS DIVIDED BY "FIRE WALLS".
 PLEASE SEE FBC FOR DEFINITION OF "FIRE WALLS".
 PLEASE KNOW, STRUCTURE CONSTRUCTED AS SHOWN IN PLANS,
 WOULD REQUIRE MAIN DISCONNECTS GROUPED, WHICH WOULD
 THEN IN-TURN FEED METER ROOMS.
 OTHER DESIGN CHANGES IN THE "ONE BLDG" MAY ALSO PERMIT
 INDIVIDUAL SERVICES.
 PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN AS SEPARATE
 BLDGS WITH STAND ALONE SERVICES AND ALL MAINS ARE
 GROUPED.
 PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE REVIEWS DONE
 UNDER THOSE PERMIT APPLICATIONS.
 ** PLEASE SEE SOME OF THESE COMMENTS WOULD ALSO APPLY.
  
 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH
 CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE
 DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC.
 PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED.
 PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. SEE NEW NOTES ALSO.
 PLEASE SEE HOUSE CIRCUITS AND NEW NOTES FOR THIS.
 FBC ADMIN SECTION 104.2.1.2, NEC 408.4, 310.16, 240.4
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO
 REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON
 AREAS.
  
 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY
 FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH
 DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING
 TO THOSE AREAS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS,
 INCLUSIVE OF ALL UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE
 AT THIS TIME.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO
 SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED
 PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED
 PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN
 LEGAL RECORD.
 PLEASE SEE THE LAYOUT IN THIS BUILDING IS NOT THE SAME
 AS OTHER AND SEPARATE EGRESS PATHS ARE PRESENT. PLEASE
 ALSO SEE NEW NOTES PERTAINING TO ELEVATOR CORRIDOR.
 PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL
 PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH
 REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL
 EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN
 THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE
 TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH
 AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY
 DO. NOT ALL AREAS ARE THE LIKE.
 PLEASE ALSO SEE MISSING PHOTO-METRICS FOR CLUBHOUSE
 PLANS, STAIRS AND EGRESS PATHS.
 PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND
 PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND
 SITE LIGHTING.
 THIS COMMENT HAS BEEN PRIMARILY THE SAME NOTE FOR ALL
 THREE BUILDING PERMIT APPLICATIONS.
 PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS
 PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH
 COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER
 THIS PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON
 AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS
 ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH
 REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER
 NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT
 CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE
 WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING
 LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN)
 NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS
 CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT
 SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS
 REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND
 WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE
 PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN
 A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND
 CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH
 BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE
 SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR
 BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES
 NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN
 ANY WAY.
 PLEASE SEE THERE ARE CIRCUITS SHOWN IN THIS BUILDING
 ALSO DO NOT CORRELATE WITH THE PANEL SCHEDULE AS
 SUBMITTED.
 PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE IN FACT
 BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE KNOW AT
 THIS TIME THERE ARE MANY ITEMS PERTAINING TO SITE
 LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE DROP,
 CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR SIZES
 ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR
 WIND LOADS ON POLES.
 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR
 ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND
 VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS
 AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND LOADING
 CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT
 OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH
 PLANS AND PERMIT APPLICATION FOR REVIEW.
  
 8) NOTE: NO, PLEASE SEE NOT ALL ROOMS AND AREAS ARE
 CLEAR. IT APPEARS FOR THE MOST PART IN BUILDING #1 THIS
 HAS BEEN DONE. THE NOTE WILL REMAIN AS NEW NOTES
 PERTAINING TO FIXTURES AND CIRCUITING MAY AFFECT THESE
 AS SHOWN. PLEASE SEE NEW NOTES PERTAINING TO THE
 ELEVATOR EQUIPMENT ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME
 SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND
 ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL.
 7.8,7.9, 700.16 ETC
  
 9) NOTE:NO, PLEASE SEE CIRCUITING FOR MANY OF THE
 CIRCUITS NOT SHOWN ON PLANS CAN NOT BE VERIFIED FOR THE
 REQUIRED DEDICATED CIRCUITS. PLEASE SEE PLANS AND
 CORRELATE WITH THE HOUSE PANEL FOR THIS BUILDING.
 PLEASE ALSO SEE NEW NOTES PERTAINING TO THE EQUIPMENT
 ROOM.
 PLEASE SEE 620.22,23,24 AND 620.51 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED
 BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE
 RMS/EQUIPMENT AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON
 RISER SHEETS. PLEASE SEE NOT ENOUGH INFORMATION WAS
 SHOWN ON FP FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION,
 TIME OF OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE
 SEE THE SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE
 UNITS AND NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR
 EACH BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED.
 PLEASE ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS.
 PLEASE ALSO SEE MISSING THE RELEVANT CODES ON FP
 SHEETS.
 PLEASE SEE THAT THIS BUILDING DOES NOT SEEM TO BE
 FULLY SPRINKLED.
 PLEASE SEE A LAYOUT FROM UNITS COULD NOT BE SEEN FOR
 PROTECTION, SEE FIRE REVIEW NOTES. PLEASE ALSO SEE
 NOTES PERTAINING TO SMOKE DETECTOR/ALARM DEVICES
 REQUIREMENTS.
 PLEASE KNOW AS EACH BUILDING IS UNDER A SEPARATE
 PERMIT, THREE SETS OF PLANS SHALL BE ACCOMPANIED BY
 THREE SETS OF ALL SUBMITTALS AS REQUESTED.
 PLEASE SEE NFPA-20 FOR ALL REQUIREMENTS FOR ROOM.
 PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT
 SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP
 AS DIESEL AS NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE
 PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER
 2003 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS
 FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS
 REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A
 MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE
 AND MECH).
  
 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER
 PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL
 SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE
 KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA
 DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF
 THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2
 ADMINSECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL
 PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS
 OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 310.16, 240.4,215.5
  
 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT
 COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE
 DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT
 WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN
 ON BUILDING #1'S PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A
 AND 50A CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES
 FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE
 ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES,
 VOLTAGES ETC WAS NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE
 OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13) NOTE: OK, HOWEVER SEE NOTES.
  
 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS
 TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON
 RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE.
 PLEASE SEE TYPICAL NOTE #4 AND #7 DO NOT CORRELATE ON
 RISER.
 PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT
 ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY.PLEASE SEE
 NEW NOTES FOR NEW MAINS.
 PLEASE ADJUST ALL NOTE SON RISER AND NOTES NOTED AS
 RISER NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR
 PANELS/EQUIPMENT BEING FED BY SAID OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH
 125A OCP AS LISTED ON RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A
 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4
 COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR
 "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC.
  
 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL
 FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW
 THESE FOR CODE COMPLIANCE.
 PLEASE KNOW THAT IF BUILDING DOES NOT FALL UNDER
 EXEMPTION OF NFPA FOR SMOKE DEVICES REQUIRED INSIDE
 SLEEPING ROOMS, THEN THESE WILL BE REQUIRED TO BE SHOWN
 AND CIRCUITED. PLEASE BE AWARE THAT ONCE THESE DEVICES
 (IF SMOKE ALARMS AT 120V) ARE INSTALLED, THESE WOULD BE
 REQUIRED TO BE ON A ARC FAULT PROTECTED CIRCUIT. PANEL
 SCHEDULE AND/OR CIRCUITING MAY NEED TO BE ADJUSTED.
 PLEASE LABEL ALL CIRCUITS ON PANEL SCHEDULE WHICH
 CONTAIN AFCI PROTECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT"
 PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS,
 LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT
 PLANS AND ADJUST.
  
 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT
 APPLICATION FOR BUILDING #1 INDICATES 450 UNITS AND
 THAT IS WHAT WAS ORIGINALLY APPLIED FOR ON ORIGINAL
 APPLICATION AND ENTERED INTO OUR SYSTEM.
 PLEASE SEE THE NEW PERMIT APPLICATION FOR THE NEW
 CONTRACTOR DOES NOT DESCRIBE WORK IN DETAIL PROPOSED
 FOR THIS PARTICULAR BUILDING. ONLY MENTIONS NEW
 CONSTRUCTION FOR APARTMENT COMPLEX. PLEASE BE SURE TO
 CORRELATE EACH APPLICATION FOR EACH BUILDING AND BE
 SURE ALL INFORMATION IS COORDINATED WITH THE BUILDING.
 PLEASE CORRELATE PLANS, PERMIT APPLICATIONS AND ADJUST
 PLANS AS NEEDED.
 FBC 104.2.1.2 ADMIN SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS, UNITS, PANELS, AND
 BUILDING/METER LOAD CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT
 "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE
 LOCATED ON BLDG LOAD CALCULATIONS ON 16.25?
 B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT
 "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY
 SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF
 TWO GROUNDING ELECTRODE SYSTEMS SHOWN?
 PLEASE SEE METER CENTER "SCHEDULE" WHICH INCLUDES A
 3/0, HOWEVER SEE NEW NOTES FOR GROUNDING ELECTRODE,
 EQUIPMENT GROUNDING CONDUCTORS ETC.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE
 GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON
 RISER.
 250.50.
  
 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL
 WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION
 FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS
 REQUIRED PER
 230.8
  
 22) NOTE: N/A, HOWEVER SEE NEW NOTES.
  
 23) NOTE: N/A, HOWEVER SEE NEW NOTES.
  
 24) NOTE: N/A.
  
 25) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 26) NOTE: OK.
  
 27) NOTE: OK.
  
 28) NOTE:NO, PLEASE SEE THIS BUILDING DOES NOT SEEM
 TO BE FULLY SPRINKLED. PLEASE SEE LAYOUTS PROVIDED ON
 FP SHEETS DO NOT INDICATE HEADS IN ANY OF THE UNITS ON
 PLANS. THERE ARE NOTES FOR SOME CLOSETS AND BATHROOMS;
 HOWEVER THOSE DO NOT CORRELATE WITH PLANS AS NO HEADS
 ARE SHOWN FOR COVERAGE. PLEASE SEE FIRE MARSHAL'S
 REVIEW AS THE BASE SYSTEM IS REQUIRED UNDER THE
 BUILDING PERMITTED SET OF PLANS EVEN THOUGH THE FS
 PERMIT WILL BE SEPARATE WITH SEPARATE PLANS ETC.
 PLEASE ALSO SEE NOTES PERTAINING TO CIRCUITING AND
 PLEASE SEE NEW NOTES FOR THESE DEVICES AND TYPES
 SHOWN.
 PLEASE SEE 2001 FBC 905.2 WHICH IS MORE RESTRICTIVE AND
 DOES NOT CONTAIN THE EXCEPTION.
 PLEASE REVIEW LOCATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM
 SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM
 KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES
 FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING
 TYPE)
 ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT
 PROTECTION OF SD'S AND CIRCUITING.
  
 29) NOTE: N/A PER THIS BUILDING REVIEW.
  
 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL
 COMMON AREAS THIS CAN NOT BE VERIFIED. PLEASE ALSO SEE
 NOTES PERTAINING TO FIXTURES TYPES ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS,
 WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR
 THESE IS NOT SHOWN.
 215.5
  
 31) NOTE: OK.
  
 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING
 GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS
 REQUIRED.
 UNIT(S) A 1, A-2, C1, C3 ETC. PLEASE GO THROUGH ALL.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG
 KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON
 WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE
 COUNTER SPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF
 THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE
 SEE THESE AREAS REDLINED ON SHEETS.
  
 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR
 SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF
 THIS IS NOT A PLUG-IN TYPE, PLEASE INDICATE ON PLANS
 WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR
 RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET
 SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED
 THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE
 STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE
 INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL
 NOT BE PERMITTED AS SHOWN IN SOME UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE
 CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE
 TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN
 A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED
 DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND
 HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION.
 PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO
 DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 ** NEW NOTES FOR THIS REVIEW **
  
 1) NOTE: PLEASE SUBMIT AND SHOW ALL FIXTURE
 DESIGNATIONS ON PLANS. PLEASE SEE SOME OF THE NOTES
 WHICH MENTION A PARTICULAR FIXTURE DO NOT CORRELATE
 WITH THE FIXTURE SCHEDULE PROVIDED. PLEASE SEE OTHERS
 ARE SHOWN WITH OUT ANY WATTAGE USE OR DESIGNATION(S).
 PLEASE COMPLETE AND COORDINATE ALL AS THESE CAN NOT BE
 REVIEWED FOR COMPLIANCE AT THIS TIME.
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED SEEM TO CONTAIN
 UNITS WHICH ARE NOT PART OF THIS PARTICULAR BUILDING?
 PLEASE SEE C-3. PLEASE SEE THESE DO NOT SEEM TO BE ON
 ARCHITECTURAL PLANS.
 104.2.1.2, ADMIN SECTION
 NEC 408.4, 240.4, 310.16 TO BE VERIFIED.
  
 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS
 SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE
 KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE
 CONTACT THIS OFFICE OR THE BOARD.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS
 THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN
 DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS
 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD
 DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE
 ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE
 SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON
 THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN
 FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT
 DESIGNATIONS.
  
 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN
 AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM
 LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4).
 THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW
 WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS
 NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW.
 PLEASE SHOW.
  
 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS AS
 NOTED ABOVE IN NOTE #2 FOR NEW REVIEW NOTES.
 PLEASE SEE IF UNIT #C3 IS BEING DONE IN THIS BUILDING ,
 INCLUDE REQUIRED FIRST FLOOR ELECTRICAL.210.52
 PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND
 CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE
 NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE).
  
 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED
 ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO
 BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON
 OTHER BUILDINGS? PLEASE SEE MISSING WHAT APPEARS TO BE
 A TRASH ROOM(S) AND ANY CIRCUITING FOR LIGHTS,
 COMPACTOR ETC.
 240.4, 310.16, 408.4, ETC
  
 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND
 SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA
 DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16
 FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS,
 KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME
 RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO
 BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME
 OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS
 OF 15A'S ETC. PLEASE SEE THAT ANY OF THESE AREAS OF THE
 LIKE WILL BE REQUIRED TO CONTAIN THESE RECEPTACLES ON
 THE ONE OR MORE CIRCUITS AS NOTED.
 PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE.
  
 9) NOTE:PLEASE SEE ELEVATOR CORRIDOR ON 16.06 AND ANY
 POSSIBLEBUILDING CODE COMMENTS BASED ON DEAD-END
 CORRIDORS AND DISTANCES PERMITTED ETC WITH AND/ OR WITH
 OUT BEING SPRINKLED.
 THIS IS ONLY BEING NOTED AS IF THE LAYOUT HAS TO CHANGE
 FOR ANY REASON, THIS WILL AFFECT THE ELECTRICAL PLANS.
  
 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN
 ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO
 CONTAIN PANIC HARDWARE.
 110.26/90.4
  
 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT
 THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS
 INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND
 THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ?
 PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC
 104.2.1.2 FOR ADDITIONAL INFORMATION.
 NEC 310.16, 240.4 ETC.
  
 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE
 RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON
 RISER. PLEASE SEE NOTE #1. PLEASE SEE THIS SAME NOTE IS
 PROVIDED FOR METER CENTERS, HOWEVER THE NEW MAINS WILL
 NOT BE METER CENTERS.
 104.2.1.2 FBC ADMIN SECTION.
  
 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP
 DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED?
 (NOT TO UNIT)
 440.11. THIS CAN BE A TYPICAL DETAIL.
  
 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW ONE SET OF EACH OF THE PLANS FOR EACH
 BUILDING WILL BE RETAINED BY THIS OFFICEE.
  
 15) NOTE: PLEASE SEE COMPLETE CLUBHOUSECIRCUITING AS
 NOTED IN OTHER REVIEW COMMENTS, HOWEVER THIS IS BEING
 NOTED FOR THE CLUBHOUSE TO EMPHASIZE THIS AND ALL ROOM
 AND AREA DESIGNATIONS.
 FBC 104.2.1.2 ADMIN SECTION AND NEC FOR REVIEW OF
 AREAS. 700.12E AS NOTED ABOVE ETC.
  
 16) NOTE: PLEASE SEE 2ND FLOOR EXIT LIGHT OUTSIDE ON
 THE BUILDING IC SIDE WHICH PLACES THIS EXIT SIGN AT THE
 EGRESS DOORS FROM CLUBHOUSE. AN OCCUPANT IN THIS
 CORRIDOR WOULD READ THIS AS AN EXIT IN WHICH DOORS OPEN
 IN THE DIRECTION OF TRAVEL ETC.
 PLEASE REVIEW THE LOCATIONS AS SHOWN AND SEE POSSIBLE
 FIRE REVIEW NOTES.
  
 17) NOTE: PLEASE SEE FIRE REVIEW COMMENTS WITH RESPECT
 TO ADDRESSING OF BUILDING AND THE LOCATION OF THE
 REQUIRED FIRE ALARM CONTROL PANEL. PLEASE SEE THE
 LOCATIONS WILL BE REQUIRED BY THE FIRE MARSHAL'S
 OFFICE. PLEASE SEE PLANS CURRENTLY SEEM TO SHOW
 MULTIPLE LOCATIONS WHICH ARE UNCLEAR AT THIS TIME. THIS
 COMMENT IS BEING MADE AS THIS WILL AFFECT THE
 ELECTRICAL PLANS.
  
 18) NOTE: PLEASE NOTE/INDICATE THE FEEDERS ON THE RISER
 FROM THE NEW MAINS OUT TO THE METER CENTERS. PLEASE
 KNOW AS THE METER CENTER SCHEDULE SEEMS TO INDICATE
 GROUNDING ELECTRODE AND NOT EQUIPMENT GROUNDING
 CONDUCTOR, IT IS UNCLEAR WHICH TO USE. A NOTE OF WHICH
 TO USE AND WHEN, OR ADJUSTING THE RISER AND RISER NOTES
 WOULD PROVIDE MORE DETAILS FOR THIS.
 PLEASE SEE NOTES WHICH WILL REQUIRE A "FLOATING
 NEUTRAL" AFTER THE FIRST MEANS OF DISCONNECT WILL BE
 REQUIRED ON RISER SHEETS. PLEASE SEE 250.6 AND 250.24B
 AS NEW MAINS ARE INSTALLED AND THE METERS WHICH CONTAIN
 NEUTRALS MAY NOT BE BONDED AFTER THE FIRST MEANS OF
 DISCONNECT.
 FBC 104.2.1.2 ADMIN SECTION.
  
 19) NOTE: PLEASE SEE POWER FOR ELEVATOR IS BEING NOTED
 ON THE FORTH FLOOR PLANS? PLEASE ALSO SEE SEVERAL
 LOCATIONS WHICH PLACE THIS NOTE FOR POWER AND EQUIPMENT
 IN THE EGRESS CORRIDORS?
 PLEASE ALSO CORRELATE WITH THE FIFTH FLOOR PLANS AS
 THIS SEEMS TO BE THE LOCATION(S) IN WHICH EQUIPMENT
 WILL BE INSTALLED IN A ELEVATOR EQUIPMENT CLOSET.
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO CIRCUITING
 FOR BRANCH CIRCUITS WHICH COULD NOT BE LOCATED AS
 REQUIRED.
 NEC 620
 FBC ADMIN SECTION 104.2.1.2 FOR CLARIFICATION.
  
 20) NOTE: PLEASE INDICATE CLARIFY LOCATION OF THE PANEL
 "P".
 110.26, 240.24, 408.7 ETC
  
  
 *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR
 COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM
 DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE
 CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP
 IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE,
 AND SHOULD BE DONE FOR THIS REVIEW AS WELL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2007-01-01 09:16:542007-01-01 09:16:54
 IN ELEC FOR REVIEW, IN PROGRESS.