| 2007-01-01 13:54:45 | |
| | **** UNSAT2ND REVIEW ******** |
| | |
| | COURTNEY LAKES BUILDING #1 |
| | N. CONGRESS. |
| | |
| | ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE |
| | PREVIOUS REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND |
| | PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW |
| | COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH |
| | SET. |
| | PLEASE SEE THE COMMENTS ON BUILDING ONE ARE DIFFERENT |
| | IN MANY ASPECTS BASED ON THE DESIGN ALONE AND PROPOSED |
| | PHASES OF PROJECT. |
| | |
| | ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON |
| | PLANS SUBMITTED. |
| | |
| | ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE |
| | PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY |
| | A "NO, OK, NO/OK, N/A OR SEE NEW ". |
| | 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO |
| | BETTER EXPLAIN COMMENT MADE. |
| | 2) OK, WILL HAVE PREVIOUS NOTE REMOVED. |
| | 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED |
| | BY FURTHER EXPLANATION OF PREVIOUS NOTE. |
| | 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO |
| | THIS BUILDING AND PREVIOUS NOTE IS REMOVED. |
| | |
| | ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF |
| | PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH |
| | **** NEW NOTES**. |
| | |
| | |
| | 1) NOTE: NO, PLEASE SEE THE SETS ARE NOT BOUND TOGETHER |
| | IN A FASHION TO SECURE ALL SHEETS. |
| | PLEASE SEE THE PLANS SUBMITTED FOR BUILDING #1 ARE ALL |
| | FALLING APART AND WERE NOT SECURELY PUT TOGETHER. |
| | PLEASE SEE THE STAPLES BEING USED DO NOT GO THROUGH ALL |
| | SHEETS. |
| | PLEASE SEE SOME SETS WERE ALREADY COMING APART BEFORE |
| | THEY WERE OPENED FOR REVIEW. PLEASE SEE THIS IS |
| | REQUIRED FOR ALL SETS AND FOR ALL PLANS. |
| | PLEASE OBTAIN A METHOD TO SECURE AND BOUND PLANS |
| | TOGETHER. |
| | IF PLANS COME BACK IN THE SAME FASHION, THIS OFFICE |
| | WILL CONTACT THE CONTRACTOR TO COME IN AND PICK UP |
| | PLANS TO BE CORRECTED BEFORE PROCESSING AND BEFORE |
| | REVIEW WILL TAKE PLACE. |
| | THE STAPLES IN SOME HAVE ALREADY COME COMPLETELY OUT. |
| | THIS COMMENT IS FOR ALL WHETHER OR NOT COMMENT IS MADE |
| | FOR OTHER BUILDINGS OR BY OTHER TRADES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETED PLANS BOUND TOGETHER IN AN |
| | APPROPRIATE FASHION. PLEASE SEE ALL SHEETS WERE |
| | SUBMITTED LOOSELY AND NOT BOUND IN SETS. |
| | |
| | |
| | |
| | 2) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS |
| | DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES |
| | RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS |
| | PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE |
| | THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS |
| | ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH |
| | RESPECT TO THIS FROM OTHER TRADES. |
| | THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002 |
| | NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT |
| | NFPA-101 IS NOTED ) |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN |
| | EFFECT. |
| | PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA |
| | ADOPTED THE 2002 |
| | NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME |
| | ELECTRICAL COMMENTS WHICH WILL AFFECT THIS. |
| | PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED |
| | FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS |
| | ON OCT 1ST, 2005. |
| | |
| | 4) NOTE:NO, PLEASE SEE THE PREVIOUS NOTES AS THE |
| | PHASING OF THIS BUILDING #1 WILL STILL BE OF CONCERN. |
| | AS NOTED ON PLANS, IT IS THE INTENT TO OCCUPY PHASES OF |
| | THE BUILDING INSTEAD OF COMPLETING ALL AT ONCE. PLEASE |
| | SEE THERE ARE SEVERAL ISSUES WHICH CREATE AN CONCERN |
| | FOR LIFE SAFETY OF NOT ONLY THE OCCUPANTS HOWEVER ALSO |
| | FOR CONSTRUCTION WORKERS PER OSHA REGULATIONS FOR |
| | GUARDING O LIVE PARTS AND EXPOSEURE TO UNQUALIFIED |
| | PERSONNEL PER 110.27. |
| | PLEASE SEE NO INFORMATION FOR SPRINKLER PROTECTION AND |
| | HOW SYSTEMS WHICH FEED FROMONE TO ANOTHER SECTION |
| | WILL TAKE PLACE. |
| | PLEASE SEE THERE ARE CIRCUITS IN PHASES TWO AND THREE |
| | WHICH ARE BEING FED FROM PANELS ALREADY ENERGIZED UNDER |
| | PHASE ONE. |
| | THE HAZARD OF SYSTEMS BEING FED FROM OTHER PARTS OF THE |
| | BUILDING WHICH ARE FROM EQUIPMENT ALREADY ENERGIZED IS |
| | OF CONCERN. NO INFORMATION OF SCHEDULE SHUT DOWN BY THE |
| | DESIGNER AND CONTRACTOR WAS SUBMITTED. |
| | PLEASE KNOW DUE TO THE CIRCUITING AS SHOWN ON PLANS FOR |
| | BRANCH CIRCUITS, FEEDERS ETC APPROVAL OF THE WAY THE |
| | PROPOSED CONSTRUCTION WILL TAKE PLACE IS NOT FINALIZED |
| | AT THIS TIME. PLEASE ALSO SEE COMMENTS FROM OTHER |
| | TRADES LIKE THE FIRE MARSHAL AND BUILDING PLAN REVIEW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | 4) NOTE: PLEASESEE THAT THREE SEPARATE PERMIT |
| | APPLICATIONS WERE SUBMITTED AND NOTED FOR BLDG'S 1,2 |
| | AND 3, HOWEVER PLANS SHOWS BLDG TYPES 1.2&3 |
| | STRUCTURALLY ONLY ONE BUILDING. |
| | PLEASE SEE PERMIT APPLICATIONS ALL REFLECT THIS ONE 450 |
| | UNIT BLDG. |
| | PLEASE SEE THIS CONTRADICTS THE "PHASING PLAN" |
| | SUBMITTED ON A1.04 AS THIS PHASING PLAN INDICATES WORK |
| | ON BLDGS 4 AND 5 BEFORE COMPLETION OF BLDGS 1, 2 AND |
| | 3. |
| | PLEASE SEE COMMENTS FROM BLDG, FIRE AND OTHER |
| | REVIEWERS, AS CERTIFICATES OF OCCUPANCY(CO'S) FOR |
| | THESE CAN NOT BE GRANTED IN THIS ORDER AS THE FIRST |
| | "STRUCTURED BLDG"(1,2&3) WOULD NOT BE COMPLETE. |
| | PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY |
| | CO'S" WHICH MAY ALLOW OCCUPANCY OF SOME PARTS OF BLDGS, |
| | HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30 |
| | DAYS AND A MAX OF 3 TCO'S MAY ONLY BE GRANTED BY THE |
| | BLDG OFFICIAL. |
| | PLEASE KNOW, IN ANY CASE, ALL LIFE SAFETY, FIRE |
| | PROTECTION SYSTEMS, FIRE SPRINKLERS (FULLY CHARGED), |
| | ELECTRICAL SYSTEMS ETC SHALL BE COMPLETE IN THE BASE |
| | BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A TCO,/CO CAN BE |
| | GRANTED. |
| | ************************************* |
| | ALSO NOTED THAT BLDG'S TYPE 4 AND 5 WHICH ARE SEPARATE |
| | STRUCTURES AND INDEPENDENT OF EACH OTHER WERE NOT |
| | SUBMITTED FOR PERMIT. |
| | PLEASE SEE ALL PERMITS SUBMITTED AFTER OCT. 1ST, 2005 |
| | SHALL FALL UNDER THE 2004 FBC, WITH ALL OTHER CODES |
| | ADOPTED BY SAID CODE AND STATE OF FLORIDA. |
| | |
| | ************************************ |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) WITH RESPECT |
| | TO THIS. |
| | |
| | ************************************* |
| | PLEASE ALSO SEE NEXT COMMENT WITH RESPECT TO THE MAINS, |
| | SERVICES, AND METER RMS AS PROPOSED. |
| | ** SEE ALL NOTES FROM ALL REVIEWERS WHICH MAY ALSO |
| | AFFECT THIS SEQUENCE OF CONSTRUCTION. |
| | |
| | 5) NOTE: NO/OK. PLEASE SEE NOTE #4 ABOVE AND PLEASE |
| | SEE AS THE RISER HAS BEEN REVISED TO WHAT APPEARS TO BE |
| | NEW MAINS. PLEASE PROVIDE INFORMATION ON THE MAIN BEING |
| | SHOWN. RISER AND PLANS MAKE REFERENCE TO THESE BEING |
| | ?SHUNT-TRIP? WHICH ARE OK, HOWEVER PLEASE BE SURE EACH |
| | MAIN CONTAINS THE MANUAL MEANS OF DISCONNECT RATED FOR |
| | THE LOED SERVED AS REQUIRED PER 230.79 AND 230.76. |
| | PLEASE SEE RISER MENTIONS TO SEE METER CENTER RISER |
| | NOTES, HOWEVER RISER NOTES EACH METER CENTER WITH MAINS |
| | ALSO. PLEASE SEE NEW NOTES PERTAINING TO GROUNDING. |
| | PLEASE SEE PLANS DO NOT CORRELATE WITH THE RISER FOR |
| | ALL HOUSE PANELS AND EQUIPMENT. PLEASE SEE PLANS STILL |
| | INDICATE HOUSE METERS AT EACH ELECTRICAL ROOM WHEN THE |
| | RISER SHOWS ONE HOUSE METER/CT AND ALL HOUSE PANELS ARE |
| | FED FROM THE NEW DP. |
| | PLEASE SEE NEW NOTES FOR MANY OF THE REVISED ITEMS ON |
| | RISER. |
| | PLEASE SEE THE NOTES ABOVE WITH RESPECT TO PHASING OF |
| | THE PROJECT AND PANELS/FEEDERS AND BRANCH CIRCUITS |
| | CROSSING OVER PHASED AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | 5) NOTE: PLEASE SEE METER RMS AS SHOWN WOULD BE OK, |
| | HOWEVER STRUCTURE AS SHOWN FOR BLDG TYPE 1, 2 AND 3 |
| | (ONE BLDG) WOULD REQUIRE MAINS TO BE GROUPED. 90.4, |
| | 230.2, 230.70, 230.72, 230.76, 230.79 ETC. |
| | BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN ONE SERVICE AT |
| | SEPARATE LOCATIONS SHALL BE DIVIDED INTO SECTIONS AND |
| | SHALL HAVE THOSE SECTIONS DIVIDED BY "FIRE WALLS". |
| | PLEASE SEE FBC FOR DEFINITION OF "FIRE WALLS". |
| | PLEASE KNOW, STRUCTURE CONSTRUCTED AS SHOWN IN PLANS, |
| | WOULD REQUIRE MAIN DISCONNECTS GROUPED, WHICH WOULD |
| | THEN IN-TURN FEED METER ROOMS. |
| | OTHER DESIGN CHANGES IN THE "ONE BLDG" MAY ALSO PERMIT |
| | INDIVIDUAL SERVICES. |
| | PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN AS SEPARATE |
| | BLDGS WITH STAND ALONE SERVICES AND ALL MAINS ARE |
| | GROUPED. |
| | PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE REVIEWS DONE |
| | UNDER THOSE PERMIT APPLICATIONS. |
| | ** PLEASE SEE SOME OF THESE COMMENTS WOULD ALSO APPLY. |
| | |
| | 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH |
| | CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE |
| | DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC. |
| | PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED. |
| | PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. SEE NEW NOTES ALSO. |
| | PLEASE SEE HOUSE CIRCUITS AND NEW NOTES FOR THIS. |
| | FBC ADMIN SECTION 104.2.1.2, NEC 408.4, 310.16, 240.4 |
| | |
| | PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO |
| | REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON |
| | AREAS. |
| | |
| | 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY |
| | FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON |
| | PLANS SUBMITTED. |
| | ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH |
| | DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING |
| | TO THOSE AREAS CAN NOT BE VERIFIED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS, |
| | INCLUSIVE OF ALL UNITS AND COMMON AREAS. |
| | REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE |
| | AT THIS TIME. |
| | |
| | 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO |
| | SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED |
| | PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED |
| | PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN |
| | LEGAL RECORD. |
| | PLEASE SEE THE LAYOUT IN THIS BUILDING IS NOT THE SAME |
| | AS OTHER AND SEPARATE EGRESS PATHS ARE PRESENT. PLEASE |
| | ALSO SEE NEW NOTES PERTAINING TO ELEVATOR CORRIDOR. |
| | PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL |
| | PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH |
| | REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL |
| | EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN |
| | THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE |
| | TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH |
| | AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY |
| | DO. NOT ALL AREAS ARE THE LIKE. |
| | PLEASE ALSO SEE MISSING PHOTO-METRICS FOR CLUBHOUSE |
| | PLANS, STAIRS AND EGRESS PATHS. |
| | PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND |
| | PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND |
| | SITE LIGHTING. |
| | THIS COMMENT HAS BEEN PRIMARILY THE SAME NOTE FOR ALL |
| | THREE BUILDING PERMIT APPLICATIONS. |
| | PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS |
| | PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH |
| | COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER |
| | THIS PERMIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON |
| | AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS |
| | ETC. |
| | PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH |
| | REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER |
| | NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT |
| | CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS. |
| | PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC |
| | AND THE MIN OF 1FT CANDLE. |
| | **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE |
| | WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING |
| | LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN) |
| | NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS |
| | CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING. |
| | ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT |
| | SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW, |
| | THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND |
| | WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE |
| | PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED |
| | NIGHT-TIME SWIMMING. |
| | |
| | 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN |
| | A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND |
| | CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH |
| | BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE |
| | SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR |
| | BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES |
| | NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN |
| | ANY WAY. |
| | PLEASE SEE THERE ARE CIRCUITS SHOWN IN THIS BUILDING |
| | ALSO DO NOT CORRELATE WITH THE PANEL SCHEDULE AS |
| | SUBMITTED. |
| | PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE IN FACT |
| | BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE KNOW AT |
| | THIS TIME THERE ARE MANY ITEMS PERTAINING TO SITE |
| | LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE DROP, |
| | CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR SIZES |
| | ETC. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR |
| | WIND LOADS ON POLES. |
| | 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR |
| | ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC. |
| | PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND |
| | VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS |
| | AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING, |
| | LANDSCAPE LIGHTING WORK. |
| | ** ALSO NOTE: IN THAT COMPLETE WIND LOADING |
| | CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT |
| | OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH |
| | PLANS AND PERMIT APPLICATION FOR REVIEW. |
| | |
| | 8) NOTE: NO, PLEASE SEE NOT ALL ROOMS AND AREAS ARE |
| | CLEAR. IT APPEARS FOR THE MOST PART IN BUILDING #1 THIS |
| | HAS BEEN DONE. THE NOTE WILL REMAIN AS NEW NOTES |
| | PERTAINING TO FIXTURES AND CIRCUITING MAY AFFECT THESE |
| | AS SHOWN. PLEASE SEE NEW NOTES PERTAINING TO THE |
| | ELEVATOR EQUIPMENT ROOM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME |
| | SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND |
| | ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL. |
| | 7.8,7.9, 700.16 ETC |
| | |
| | 9) NOTE:NO, PLEASE SEE CIRCUITING FOR MANY OF THE |
| | CIRCUITS NOT SHOWN ON PLANS CAN NOT BE VERIFIED FOR THE |
| | REQUIRED DEDICATED CIRCUITS. PLEASE SEE PLANS AND |
| | CORRELATE WITH THE HOUSE PANEL FOR THIS BUILDING. |
| | PLEASE ALSO SEE NEW NOTES PERTAINING TO THE EQUIPMENT |
| | ROOM. |
| | PLEASE SEE 620.22,23,24 AND 620.51 ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED |
| | BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE |
| | RMS/EQUIPMENT AREAS. |
| | PLEASE ADJUST HOUSE PANELS AS NEEDED. |
| | |
| | 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON |
| | RISER SHEETS. PLEASE SEE NOT ENOUGH INFORMATION WAS |
| | SHOWN ON FP FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION, |
| | TIME OF OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE |
| | SEE THE SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE |
| | UNITS AND NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR |
| | EACH BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED. |
| | PLEASE ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS. |
| | PLEASE ALSO SEE MISSING THE RELEVANT CODES ON FP |
| | SHEETS. |
| | PLEASE SEE THAT THIS BUILDING DOES NOT SEEM TO BE |
| | FULLY SPRINKLED. |
| | PLEASE SEE A LAYOUT FROM UNITS COULD NOT BE SEEN FOR |
| | PROTECTION, SEE FIRE REVIEW NOTES. PLEASE ALSO SEE |
| | NOTES PERTAINING TO SMOKE DETECTOR/ALARM DEVICES |
| | REQUIREMENTS. |
| | PLEASE KNOW AS EACH BUILDING IS UNDER A SEPARATE |
| | PERMIT, THREE SETS OF PLANS SHALL BE ACCOMPANIED BY |
| | THREE SETS OF ALL SUBMITTALS AS REQUESTED. |
| | PLEASE SEE NFPA-20 FOR ALL REQUIREMENTS FOR ROOM. |
| | PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT |
| | SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE |
| | AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP |
| | AS DIESEL AS NOTED ON FP SHEETS. |
| | PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE |
| | PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER |
| | 2003 NFPA-20 IS REQUIRED. |
| | PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS |
| | FOR FUEL TANK. |
| | PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS |
| | REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A |
| | MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE |
| | MARSHAL'S OFFICE DEPENDING ON OCCUPANCY. |
| | FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE |
| | AND MECH). |
| | |
| | 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER |
| | PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL |
| | SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE |
| | KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA |
| | DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF |
| | THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2 |
| | ADMINSECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL |
| | PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS |
| | OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | 310.16, 240.4,215.5 |
| | |
| | 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT |
| | COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE |
| | DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT |
| | WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN |
| | ON BUILDING #1'S PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A |
| | AND 50A CIRCUITS. |
| | PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES |
| | FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE |
| | ADJUST CIRCUITING AS NEEDED. |
| | PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES, |
| | VOLTAGES ETC WAS NOT SUBMITTED. |
| | PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE |
| | OCP AT ABOVE MENTIONED. |
| | 240.4, 310.16 ETC |
| | |
| | 13) NOTE: OK, HOWEVER SEE NOTES. |
| | |
| | 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS |
| | TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON |
| | RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE. |
| | PLEASE SEE TYPICAL NOTE #4 AND #7 DO NOT CORRELATE ON |
| | RISER. |
| | PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT |
| | ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY.PLEASE SEE |
| | NEW NOTES FOR NEW MAINS. |
| | PLEASE ADJUST ALL NOTE SON RISER AND NOTES NOTED AS |
| | RISER NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR |
| | PANELS/EQUIPMENT BEING FED BY SAID OCP. |
| | PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH |
| | 125A OCP AS LISTED ON RISER ETC. |
| | PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A |
| | 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4 |
| | COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR |
| | "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC. |
| | |
| | 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS |
| | BUILDING. SEE NEW NOTES. |
| | |
| | 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL |
| | FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW |
| | THESE FOR CODE COMPLIANCE. |
| | PLEASE KNOW THAT IF BUILDING DOES NOT FALL UNDER |
| | EXEMPTION OF NFPA FOR SMOKE DEVICES REQUIRED INSIDE |
| | SLEEPING ROOMS, THEN THESE WILL BE REQUIRED TO BE SHOWN |
| | AND CIRCUITED. PLEASE BE AWARE THAT ONCE THESE DEVICES |
| | (IF SMOKE ALARMS AT 120V) ARE INSTALLED, THESE WOULD BE |
| | REQUIRED TO BE ON A ARC FAULT PROTECTED CIRCUIT. PANEL |
| | SCHEDULE AND/OR CIRCUITING MAY NEED TO BE ADJUSTED. |
| | PLEASE LABEL ALL CIRCUITS ON PANEL SCHEDULE WHICH |
| | CONTAIN AFCI PROTECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT" |
| | PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED |
| | PROTECTION OF RECEPTS. |
| | PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR |
| | ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS, |
| | LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT |
| | PLANS AND ADJUST. |
| | |
| | 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT |
| | APPLICATION FOR BUILDING #1 INDICATES 450 UNITS AND |
| | THAT IS WHAT WAS ORIGINALLY APPLIED FOR ON ORIGINAL |
| | APPLICATION AND ENTERED INTO OUR SYSTEM. |
| | PLEASE SEE THE NEW PERMIT APPLICATION FOR THE NEW |
| | CONTRACTOR DOES NOT DESCRIBE WORK IN DETAIL PROPOSED |
| | FOR THIS PARTICULAR BUILDING. ONLY MENTIONS NEW |
| | CONSTRUCTION FOR APARTMENT COMPLEX. PLEASE BE SURE TO |
| | CORRELATE EACH APPLICATION FOR EACH BUILDING AND BE |
| | SURE ALL INFORMATION IS COORDINATED WITH THE BUILDING. |
| | PLEASE CORRELATE PLANS, PERMIT APPLICATIONS AND ADJUST |
| | PLANS AS NEEDED. |
| | FBC 104.2.1.2 ADMIN SECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE LOADS, UNITS, PANELS, AND |
| | BUILDING/METER LOAD CALCULATIONS: |
| | A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT |
| | "B-3" SHOWN ON |
| | 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE |
| | LOCATED ON BLDG LOAD CALCULATIONS ON 16.25? |
| | B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT |
| | "C-2" WHICH IS ALSO SHOWN ON |
| | 16.26 BUT NOT IN CALCS ON 16.25?? |
| | ** PLEASE ADJUST ALL AS NEEDED. |
| | |
| | 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY |
| | SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF |
| | TWO GROUNDING ELECTRODE SYSTEMS SHOWN? |
| | PLEASE SEE METER CENTER "SCHEDULE" WHICH INCLUDES A |
| | 3/0, HOWEVER SEE NEW NOTES FOR GROUNDING ELECTRODE, |
| | EQUIPMENT GROUNDING CONDUCTORS ETC. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE |
| | GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON |
| | RISER. |
| | 250.50. |
| | |
| | 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL |
| | WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION |
| | FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS |
| | REQUIRED PER |
| | 230.8 |
| | |
| | 22) NOTE: N/A, HOWEVER SEE NEW NOTES. |
| | |
| | 23) NOTE: N/A, HOWEVER SEE NEW NOTES. |
| | |
| | 24) NOTE: N/A. |
| | |
| | 25) NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 26) NOTE: OK. |
| | |
| | 27) NOTE: OK. |
| | |
| | 28) NOTE:NO, PLEASE SEE THIS BUILDING DOES NOT SEEM |
| | TO BE FULLY SPRINKLED. PLEASE SEE LAYOUTS PROVIDED ON |
| | FP SHEETS DO NOT INDICATE HEADS IN ANY OF THE UNITS ON |
| | PLANS. THERE ARE NOTES FOR SOME CLOSETS AND BATHROOMS; |
| | HOWEVER THOSE DO NOT CORRELATE WITH PLANS AS NO HEADS |
| | ARE SHOWN FOR COVERAGE. PLEASE SEE FIRE MARSHAL'S |
| | REVIEW AS THE BASE SYSTEM IS REQUIRED UNDER THE |
| | BUILDING PERMITTED SET OF PLANS EVEN THOUGH THE FS |
| | PERMIT WILL BE SEPARATE WITH SEPARATE PLANS ETC. |
| | PLEASE ALSO SEE NOTES PERTAINING TO CIRCUITING AND |
| | PLEASE SEE NEW NOTES FOR THESE DEVICES AND TYPES |
| | SHOWN. |
| | PLEASE SEE 2001 FBC 905.2 WHICH IS MORE RESTRICTIVE AND |
| | DOES NOT CONTAIN THE EXCEPTION. |
| | PLEASE REVIEW LOCATIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL |
| | SLEEPING ROOMS. |
| | PLEASE SEE 2002 NFPA-72 11.5.3.1 |
| | PLEASE ADJUST NOTE FOR SD'S ON PLANS AS |
| | SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM |
| | SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM |
| | KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES |
| | FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING |
| | TYPE) |
| | ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT |
| | PROTECTION OF SD'S AND CIRCUITING. |
| | |
| | 29) NOTE: N/A PER THIS BUILDING REVIEW. |
| | |
| | 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL |
| | COMMON AREAS THIS CAN NOT BE VERIFIED. PLEASE ALSO SEE |
| | NOTES PERTAINING TO FIXTURES TYPES ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS, |
| | WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED |
| | AHEAD OF ANY LOCAL SWITCHES. |
| | THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR |
| | THESE IS NOT SHOWN. |
| | 215.5 |
| | |
| | 31) NOTE: OK. |
| | |
| | 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING |
| | GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS |
| | REQUIRED. |
| | UNIT(S) A 1, A-2, C1, C3 ETC. PLEASE GO THROUGH ALL. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG |
| | KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON |
| | WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE |
| | COUNTER SPACE. |
| | PLEASE SEE B-2, B-4ETC. |
| | PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF |
| | THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE |
| | SEE THESE AREAS REDLINED ON SHEETS. |
| | |
| | 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR |
| | SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF |
| | THIS IS NOT A PLUG-IN TYPE, PLEASE INDICATE ON PLANS |
| | WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR |
| | RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET |
| | SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED |
| | THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE |
| | STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE |
| | INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL |
| | NOT BE PERMITTED AS SHOWN IN SOME UNITS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE |
| | CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE |
| | TRANSFORMER? |
| | PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN |
| | A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED |
| | DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES. |
| | MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND |
| | HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION. |
| | PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN |
| | ACCELERANT. |
| | THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO |
| | DESIRED. |
| | 110.26, 240.24, 90.4 ETC |
| | |
| | 34) NOTE: OK. |
| | |
| | 35) NOTE: OK. |
| | |
| | ** NEW NOTES FOR THIS REVIEW ** |
| | |
| | 1) NOTE: PLEASE SUBMIT AND SHOW ALL FIXTURE |
| | DESIGNATIONS ON PLANS. PLEASE SEE SOME OF THE NOTES |
| | WHICH MENTION A PARTICULAR FIXTURE DO NOT CORRELATE |
| | WITH THE FIXTURE SCHEDULE PROVIDED. PLEASE SEE OTHERS |
| | ARE SHOWN WITH OUT ANY WATTAGE USE OR DESIGNATION(S). |
| | PLEASE COMPLETE AND COORDINATE ALL AS THESE CAN NOT BE |
| | REVIEWED FOR COMPLIANCE AT THIS TIME. |
| | |
| | 2) NOTE: PLEASE SEE PLANS SUBMITTED SEEM TO CONTAIN |
| | UNITS WHICH ARE NOT PART OF THIS PARTICULAR BUILDING? |
| | PLEASE SEE C-3. PLEASE SEE THESE DO NOT SEEM TO BE ON |
| | ARCHITECTURAL PLANS. |
| | 104.2.1.2, ADMIN SECTION |
| | NEC 408.4, 240.4, 310.16 TO BE VERIFIED. |
| | |
| | 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS |
| | SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| | 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE |
| | KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE |
| | REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE |
| | CONTACT THIS OFFICE OR THE BOARD. |
| | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE |
| | DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS |
| | THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN |
| | DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS |
| | 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD |
| | DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE |
| | ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE |
| | SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON |
| | THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN |
| | FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT |
| | DESIGNATIONS. |
| | |
| | 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN |
| | AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM |
| | LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4). |
| | THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW |
| | WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS |
| | NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW. |
| | PLEASE SHOW. |
| | |
| | 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS AS |
| | NOTED ABOVE IN NOTE #2 FOR NEW REVIEW NOTES. |
| | PLEASE SEE IF UNIT #C3 IS BEING DONE IN THIS BUILDING , |
| | INCLUDE REQUIRED FIRST FLOOR ELECTRICAL.210.52 |
| | PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND |
| | CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE |
| | NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE). |
| | |
| | 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED |
| | ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO |
| | BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON |
| | OTHER BUILDINGS? PLEASE SEE MISSING WHAT APPEARS TO BE |
| | A TRASH ROOM(S) AND ANY CIRCUITING FOR LIGHTS, |
| | COMPACTOR ETC. |
| | 240.4, 310.16, 408.4, ETC |
| | |
| | 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND |
| | SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA |
| | DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16 |
| | FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS, |
| | KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME |
| | RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO |
| | BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME |
| | OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS |
| | OF 15A'S ETC. PLEASE SEE THAT ANY OF THESE AREAS OF THE |
| | LIKE WILL BE REQUIRED TO CONTAIN THESE RECEPTACLES ON |
| | THE ONE OR MORE CIRCUITS AS NOTED. |
| | PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE. |
| | |
| | 9) NOTE:PLEASE SEE ELEVATOR CORRIDOR ON 16.06 AND ANY |
| | POSSIBLEBUILDING CODE COMMENTS BASED ON DEAD-END |
| | CORRIDORS AND DISTANCES PERMITTED ETC WITH AND/ OR WITH |
| | OUT BEING SPRINKLED. |
| | THIS IS ONLY BEING NOTED AS IF THE LAYOUT HAS TO CHANGE |
| | FOR ANY REASON, THIS WILL AFFECT THE ELECTRICAL PLANS. |
| | |
| | 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN |
| | ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO |
| | CONTAIN PANIC HARDWARE. |
| | 110.26/90.4 |
| | |
| | 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT |
| | THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS |
| | INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND |
| | THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ? |
| | PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC |
| | 104.2.1.2 FOR ADDITIONAL INFORMATION. |
| | NEC 310.16, 240.4 ETC. |
| | |
| | 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE |
| | RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON |
| | RISER. PLEASE SEE NOTE #1. PLEASE SEE THIS SAME NOTE IS |
| | PROVIDED FOR METER CENTERS, HOWEVER THE NEW MAINS WILL |
| | NOT BE METER CENTERS. |
| | 104.2.1.2 FBC ADMIN SECTION. |
| | |
| | 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP |
| | DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED? |
| | (NOT TO UNIT) |
| | 440.11. THIS CAN BE A TYPICAL DETAIL. |
| | |
| | 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES |
| | 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE |
| | COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | ** PLEASE KNOW ONE SET OF EACH OF THE PLANS FOR EACH |
| | BUILDING WILL BE RETAINED BY THIS OFFICEE. |
| | |
| | 15) NOTE: PLEASE SEE COMPLETE CLUBHOUSECIRCUITING AS |
| | NOTED IN OTHER REVIEW COMMENTS, HOWEVER THIS IS BEING |
| | NOTED FOR THE CLUBHOUSE TO EMPHASIZE THIS AND ALL ROOM |
| | AND AREA DESIGNATIONS. |
| | FBC 104.2.1.2 ADMIN SECTION AND NEC FOR REVIEW OF |
| | AREAS. 700.12E AS NOTED ABOVE ETC. |
| | |
| | 16) NOTE: PLEASE SEE 2ND FLOOR EXIT LIGHT OUTSIDE ON |
| | THE BUILDING IC SIDE WHICH PLACES THIS EXIT SIGN AT THE |
| | EGRESS DOORS FROM CLUBHOUSE. AN OCCUPANT IN THIS |
| | CORRIDOR WOULD READ THIS AS AN EXIT IN WHICH DOORS OPEN |
| | IN THE DIRECTION OF TRAVEL ETC. |
| | PLEASE REVIEW THE LOCATIONS AS SHOWN AND SEE POSSIBLE |
| | FIRE REVIEW NOTES. |
| | |
| | 17) NOTE: PLEASE SEE FIRE REVIEW COMMENTS WITH RESPECT |
| | TO ADDRESSING OF BUILDING AND THE LOCATION OF THE |
| | REQUIRED FIRE ALARM CONTROL PANEL. PLEASE SEE THE |
| | LOCATIONS WILL BE REQUIRED BY THE FIRE MARSHAL'S |
| | OFFICE. PLEASE SEE PLANS CURRENTLY SEEM TO SHOW |
| | MULTIPLE LOCATIONS WHICH ARE UNCLEAR AT THIS TIME. THIS |
| | COMMENT IS BEING MADE AS THIS WILL AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | 18) NOTE: PLEASE NOTE/INDICATE THE FEEDERS ON THE RISER |
| | FROM THE NEW MAINS OUT TO THE METER CENTERS. PLEASE |
| | KNOW AS THE METER CENTER SCHEDULE SEEMS TO INDICATE |
| | GROUNDING ELECTRODE AND NOT EQUIPMENT GROUNDING |
| | CONDUCTOR, IT IS UNCLEAR WHICH TO USE. A NOTE OF WHICH |
| | TO USE AND WHEN, OR ADJUSTING THE RISER AND RISER NOTES |
| | WOULD PROVIDE MORE DETAILS FOR THIS. |
| | PLEASE SEE NOTES WHICH WILL REQUIRE A "FLOATING |
| | NEUTRAL" AFTER THE FIRST MEANS OF DISCONNECT WILL BE |
| | REQUIRED ON RISER SHEETS. PLEASE SEE 250.6 AND 250.24B |
| | AS NEW MAINS ARE INSTALLED AND THE METERS WHICH CONTAIN |
| | NEUTRALS MAY NOT BE BONDED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | FBC 104.2.1.2 ADMIN SECTION. |
| | |
| | 19) NOTE: PLEASE SEE POWER FOR ELEVATOR IS BEING NOTED |
| | ON THE FORTH FLOOR PLANS? PLEASE ALSO SEE SEVERAL |
| | LOCATIONS WHICH PLACE THIS NOTE FOR POWER AND EQUIPMENT |
| | IN THE EGRESS CORRIDORS? |
| | PLEASE ALSO CORRELATE WITH THE FIFTH FLOOR PLANS AS |
| | THIS SEEMS TO BE THE LOCATION(S) IN WHICH EQUIPMENT |
| | WILL BE INSTALLED IN A ELEVATOR EQUIPMENT CLOSET. |
| | PLEASE SEE PREVIOUS NOTES WITH RESPECT TO CIRCUITING |
| | FOR BRANCH CIRCUITS WHICH COULD NOT BE LOCATED AS |
| | REQUIRED. |
| | NEC 620 |
| | FBC ADMIN SECTION 104.2.1.2 FOR CLARIFICATION. |
| | |
| | 20) NOTE: PLEASE INDICATE CLARIFY LOCATION OF THE PANEL |
| | "P". |
| | 110.26, 240.24, 408.7 ETC |
| | |
| | |
| | *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE |
| | NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR |
| | COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM |
| | DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE |
| | CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP |
| | IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE, |
| | AND SHOULD BE DONE FOR THIS REVIEW AS WELL. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |