| 2007-02-14 09:39:42 | BUILDING PLAN REVIEW |
| | PERMIT: 05091684 BLDG# 1 |
| | ADD: XXX N CONGRESS |
| | 74-43-43-20-00-000-3010 |
| | CONT: E. A. LANDERS |
| | TEL: (305)823-3938 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | COURTNEY LAKES APARTMENTS, LLC |
| | |
| | ARCH: FORUM ARCHITECTURE & INTERIOR |
| | |
| | |
| | DESIGN |
| | (407)830-1400 |
| | STRUC: ROBERT PLOWFIELD & ASSOC |
| | (407)657-6657 |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | ***IMPORTANT*** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK OF COURT BEFORE |
| | A PERMIT CAN BE ISSUED. |
| | NOTE NOC WILL BE NULL & VOID 90 DAYS AFTER RECORDING AT |
| | THE CLERK OF THE |
| | COURTS OFFICE IF WORK HAS NOT STARTED. FL S S |
| | 713.13(2). |
| | |
| | 2) THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE |
| | OF THE PROJECT (3 BUILDINGS) |
| | THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE |
| | CITY. THIS WILL SATISFY THE REQUIREMENT |
| | TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE |
| | NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED |
| | ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD |
| | INSPECTOR. |
| | AN ADDITIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED |
| | SHALL BE REQUIRED. |
| | FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE |
| | BEARING CAPACITY IS NOT DEFINETLY KNOWN OR IS IN |
| | QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT |
| | DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL |
| | MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF |
| | AS TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED |
| | TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A |
| | GEOTECHNICAL REPORT FROM A DESIGN PROFESSIONAL PROPERLY |
| | LICENSED IN THE STATE OF FLORIDA. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING |
| | ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANY |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | THE THRESHOLD REPORTS SUBMITTED HAVE COPIED |
| | SIGNATURES. |
| | |
| | 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES |
| | TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9A) CONTACT LILI URSA FOR ADDRESSING REQUIREMENTS @ |
| | (561)822-1239 |
| | |
| | 9B)PROVIDE A COPY OF THE NEW PLAT, LOT HAS BEEN |
| | SUBDIVIDED. |
| | |
| | 9C) ON ALL (3) PERMIT APPLICATIONS CORRECT THE PROPERTY |
| | CONTROL NUMBER TO |
| | THE NEW LOT. |
| | |
| | 9D) PROVIDE A SITE PLAN WITH LOCATION OF THE PROPOSED |
| | STRUCTURES WITH DIMENSIONS |
| | FOR TABLE 600 ISSUES.A2.01 HAS NO DIMENSIONS!RESPONSE |
| | COMMENTS ARE TO SEE CIVIL PLANS ,NO CIVIL PLANS |
| | PROVIDED IN THIS SET OF PLANS. |
| | |
| | |
| | 10A-K) COMPLIED. |
| | |
| | 11) SHEET A1.05 |
| | |
| | 11A-B) COMPLIED. |
| | |
| | 12)SITE PLAN A5.01 |
| | NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES |
| | AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS |
| | INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO |
| | BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED |
| | NUMBER OF ACCESSIBLE SPACES WOULD BE 21. |
| | CHAPTER 11 PART B- 4PARKING AND PASSENGER LOADING: |
| | ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO WHEELCHAIRS |
| | FOR AT LEAST 2% OF THE COVERED DWELLING UNITS: |
| | ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE ACCESS |
| | TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY |
| | DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G., |
| | SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS. |
| | |
| | 12A) COMPLIED. |
| | |
| | 12B)2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED |
| | INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY. |
| | ACCESSIBLE ROUTE: FAIR HOUSING AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL BE PROVIDED WITHIN THE BOUNDARY OF THE SITE |
| | FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE PARKING |
| | SPACES, PASSENGER LOADING ZONES IF PROVIDED, AND PUBLIC |
| | STREETS OR SIDEWALKS, TO AN ACCESSIBLE BUILDING |
| | ENTRANCE. |
| | 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE |
| | PARKING SPACES WILL BE THE VAN A VERTICAL CLEARANCE OF |
| | 98" MINIMUM AT THE SPACE AND ALONG THE VEHICULAR ROUTE |
| | THERETO. |
| | |
| | 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE |
| | PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6. |
| | |
| | 12C) THE SITE PLAN DOES NOT PROVIDE FOR HANDICAPPED |
| | PARKING UNDER THE BUILDING |
| | # 1, ANS1 A117.1, 4.6 PARKING AND PASSENGER LOADING |
| | ZONES, EQUIVALENT FACILITATION. |
| | |
| | 12D) SITE PLAN DOES NOT PROVIDE ANYINFORMATION AS TO |
| | CURB CUTS, PEDESTRIAN CROSS WALKS, ETC. |
| | |
| | 13) SHEET A5.01; |
| | |
| | 13A-E) COMPLIED. |
| | |
| | 13F) 2ND REQUEST, THEFIRE PUMP ROOM NO RATING OF |
| | WINDOW OR OPENING ?U? NOT IN WINDOW SCHEDULE. DOOR |
| | 1.01IS NOW RATED- OK. |
| | |
| | 13G-J) COMPLIED. |
| | |
| | 13K) NEW COMMENT : SHEET A5.05 INDICATES THE ROOF DECK, |
| | THE PLAN DOESN?T INDENTIFY THE DOORS FROM THE |
| | STAIRWELLS FOR ROOF ACCESS. |
| | 14)DETAILS ON A5.70: |
| | |
| | 14A-D) COMPLIED. |
| | |
| | 14E) 2ND REQUEST, THE LEASING OFFICETHE CUT SECTION |
| | PROVIDED AP A7.04 DETAIL# 4 DOES INDICATE A DROPPED |
| | CEILING IN THE CLOSET BUT NO INFORMATION IS PROVIDED AS |
| | TO THE CEILING AND WALL RATING OF THE CLOSET.1007.1.4. |
| | |
| | |
| | 15) SHEET A5.02: |
| | |
| | 15A-G) COMPLIED. |
| | 15B) UNDERSTOOD THAT THE STAIRS ARE TO BE CONSIDERED |
| | OPEN STAIRS, BUT THE CORRIDOR WILL STILL REQUIRE A WALL |
| | RATING, IT CAN NOT BE CONSIDERED AN OPEN BALCONY. |
| | PLEASE PROVIDE THE RATING FOR THE CORRIDOR. PLANS NOW |
| | INDICATE THE UNIT ENTRY DOORS BEING FIRE RATED. |
| | |
| | 15H) SHEET A5.04 TYPICAL 5TH FLOOR ELEVATOR DETAIL |
| | 2/A8.10 : |
| | NEW COMMENT:SHEET A5.04 INDICATES AN ELEVATOR |
| | DETAIL 2 /A8.10 , THIS ELEVATOR MACHINE ROOM DOES NOT |
| | INDICATE WALL OR DOOR RATINGS. |
| | |
| | 15I) NEW COMMENT: SHEET A5.05 STAIRWELL ACCESS TO ROOF. |
| | SEE 1008 SUCH STAIRWAY SHALL BE MARKED AT STREET AND |
| | FLOOR LEVELS WITH A SIGN INDICATING THAT IT CONTINUES |
| | TO THE ROOF. |
| | |
| | 15J) NEW COMMENT: SHEET A7.02 WALL SECTION# 3& A7.03 |
| | WALL SECTION# 1, DETAIL#21/ A7.10 INDICATES THE USE |
| | OF WHAT APPEARS TO BE EFIS WALL SYSTEMS, THERE IS A |
| | WALL IDENTITY TAG W1-14 , NO SUCH TAG ON SHEET A1.04? |
| | |
| | 15K) NEW COMMENT: SHEET A7.02 KEY NOTE # 10 NOTES SEE |
| | STRUCTURAL DRAWINGS FOR ROOF TRUSS ANCHORAGE, NO |
| | TRUSSES NEAR THE NOTE, WHY IS THE BAT INSULATION ON THE |
| | FLOOR? |
| | |
| | 16) SHEET A5.71: |
| | |
| | 16A-B) COMPLIED. |
| | |
| | 17) SHEET A5.20. COMPLIED. |
| | |
| | 18) SHEET A5.10: |
| | |
| | 18A) 2ND REQUEST, TRASH ROOM DETAIL4 OF A8.20 THE |
| | DETAIL IS INDICATING THE OPENING FROM THE CHUTE TO THE |
| | ACCESS ROOM. |
| | PLANS INDICATE A DETAIL 22 ON SHEET A7.10, SEE KEY NOT |
| | MARKER 13 & 23, BOTH APPEAR TO BE INCORRECT. |
| | |
| | 18B) COMPLIED. |
| | |
| | 18C) 2ND REQUEST THERE IS NO INFORMATION ON THE |
| | COMBUSTIBILITY OF THE TRASH CHUTE NOR |
| | ON AUTOMATICALLY CLOSING OPENINGS. 705.2.4.2. LOOKING |
| | FOR A SPEC INDICATING THE GAUGE OF METAL USED IN THE |
| | CHUTE, ETC. |
| | |
| | 18D-E) COMPLIED. |
| | |
| | 19) SHEET A5.11 IS FOR THE FIRST FLOOR ABOVE THE GARAGE |
| | FLOOR: |
| | |
| | 19A-C) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) SHEET A5.22 |
| | |
| | 21A) COMPLIED. |
| | |
| | 22) VARIOUS SHEETS ON BUILD 1,2 & 3 |
| | INDICATE A DETAIL SECTION# 23 SHEET |
| | A7.10. |
| | |
| | 22A) COMPLIED. |
| | |
| | 22B) COMPLIED. |
| | |
| | 22C) 2ND REQUEST, THIS SAME SECTION INDICATES USE OF |
| | FOAM TRIM ON THE EXTERIOR OF THE BUILDING ABOVE 40'. |
| | 1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, II |
| | AND IV CONSTRUCTION NOT MORE THANTHREE STORIES OR 40 |
| | FT (12.2 M) HIGH MAY BE OFTYPE VI CONSTRUCTION, AND |
| | MAY BE |
| | OF TYPE VI CONSTRUCTION ON ALL BUILDINGS OF TYPE III, V |
| | AND VI CONSTRUCTION. TRIM SHALL BE SECURED TO THE WALL |
| | WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS. |
| | WHEN ARCHITECTURAL TRIM IS LOCATED ALONG THE TOP OF |
| | EXTERIOR WALLS, IT SHALL BE COMPLETELY BACKED BY THE |
| | EXTERIOR WALL AND SHALL NOT EXTEND OVER THE TOP OF |
| | EXTERIOR WALLS. |
| | |
| | 23) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 24) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS, MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) OPERABLE WINDOWS |
| | FL 3485TRACO TR-6800 -OK |
| | FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | |
| | B) FIXED WINDOWS |
| | FL 3487TRACOTR-3800 - OK |
| | FL 632KAWNEER EXPIRED NOA NON-IMPACT |
| | REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE - |
| | DENIED |
| | |
| | C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT |
| | APPROVALS |
| | |
| | D) EXTERIOR HOLLOW METAL DOORS |
| | FL3078 AMWELD DENIED LOW PRESSURES SINGLE & |
| | PAIRS |
| | |
| | E) EXTERIOR GLAZED DOORS |
| | FL 3038TRACO 03-0829.06 SMALL MISSILE ONLY, NO |
| | PRESSURE TEST - DENIED |
| | FL 3038.3TRACO 03-0422.04 TR-8910 SMALL |
| | MISSILE TEST NO PRESSURE TEST - DENIED |
| | FL 3038.4TRACO 03-0422.04 TR-8910 LARGE |
| | MISSILE HIGHLIGHT ANCHOR FASTENING SCHEDULE MAY COMPLY |
| | FL3477TRACO TR-8300SLIDING GLASS DOOR |
| | NON-IMPACTREQUIRES 0-30' LARGE MISSILE, 30'-60' SMALL |
| | MISSILE - DENIED |
| | |
| | F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED |
| | |
| | G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A |
| | PRODUCT APPROVAL |
| | |
| | H) LOUVERS NO REPORT SUBMITTED. |
| | |
| | I) TRUSS ANCHORS NO REPORT SUBMITTED. |
| | |
| | J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION, |
| | UNDERLAYMENT, ROOF TILE AND ATTACHMENT METHODS. FL 1559 |
| | SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH SUB-SYSTEM TO |
| | BE USED. |
| | NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING |
| | PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL |
| | |
| | K) EFIS WALL SYSTEMS IF USED |
| | |
| | L)5/8" FIBER TOUGH AQUA ROCK SHEATHING |
| | |
| | M ) PRE-MANUFACTURED ROOF A/C STANDS- OK |
| | |
| | N) ROLL UP DOOR - NO REPORT SUBMITTED |
| | |
| | O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT |
| | APPROVAL |
| | |
| | P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT |
| | WHAT ANCHOR METHOD TO INSTALLROOF TILE |
| | |
| | 25- 27) COMPLIED, IMPACT GLASS IS SPECIFIED. |
| | |
| | 28) COMPLIED, IMPACT GLASS IS SPECIFIED. |
| | |
| | 29- 31) COMPLIED. |
| | |
| | 32- 35) COMPLIED. |
| | |
| | NOTE: CALCULATED VALUE OF THIS TYPE II BUILDING IS |
| | $39,353,983.00 |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | COURTNEY LAKES BLDG 1 ? 2NDREV.DOC |