| 2008-02-19 09:49:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | NOTE: THE PLUMBING SUBMITTAL FROM 2/1/08 SHOULD HAVE |
| | BEEN SUBMITTED AS A PLUMBING REVISION TO THE MASTER |
| | PERMIT #05091674. ANY FUTURE REVISIONS SHALL BE |
| | SUBMITTED WITH FEES PAID BEFORE PLAN REVIEW. THE |
| | FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. ORIGINAL PLUMBING SHEETS P-1 AND P-2 WERE SIGNED |
| | AND SEALED BY ARCHITECT STEPHAN A. YECKES (AR#7444). |
| | ANY REVISIONS TO THESE PLUMBING SHEETS SHALL BE BY THE |
| | DESIGN PROFESSIONAL OF RECORD WITH THE REQUIRED TITLE |
| | BLOCK INFORMATION. PER CHAPTER 481, FLORIDA |
| | STATUTES,PART 1. |
| | |
| | 2. SHEET BUILDING (1) 12 UNITS TOTAL, SANITARY RISER |
| | DIAGRAM: |
| | |
| | A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR |
| | ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES. |
| | PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS. |
| | |
| | B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE |
| | CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER |
| | FBC PLUMBING SECTION *701.1 SCOPE. |
| | |
| | 3. SHEET BUILDING (2) 17 UNITS TOTAL, SANITARY RISER |
| | DIAGRAM: |
| | |
| | A} CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS FOR |
| | ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND LAVATORIES. |
| | PER FBC PLUMBING SECTION *1002.1 FIXTURE TRAPS. |
| | |
| | B} CLEARLY SIZE ALL PIPING (REFERENCE RED LINE |
| | CORRECTIONS INDICATING PIPES THAT WERE NOT SIZED). PER |
| | FBC PLUMBING SECTION *701.1 SCOPE. |
| | |
| | C} THE 3" HORIZONTAL DRY VENT IN LAST UNIT IS NOT |
| | ALLOWED. PER FBC PLUMBING SECTION *905.3 VENT |
| | CONNECTION TO DRAINAGE SYSTEM. |
| | |
| | 4. SHEET BUILDING (3) 3 UNITS, SANITARY RISER |
| | DIAGRAM:CLEARLY INDICATE THE REQUIRED WATER SEAL TRAPS |
| | FOR ALL DRINKING FOUNTAINS, LAUNDRY TRAYS, AND |
| | LAVATORIES. PER FBC PLUMBING SECTION *1002.1 FIXTURE |
| | TRAPS. |
| | |
| | 5. SHEET WATER SERVICE 32 UNITS: |
| | |
| | A} PLEASE CLEARLY INDICATE THE SIZING TO ALL MAINS AND |
| | BRANCHES, THE WAY ITS BEING INDICATED IS CONFUSING. PER |
| | FBC PLUMBING SECTION *601.1 SCOPE. |
| | |
| | B} PLEASE CLARIFY IF IT IS THE INTENT TO DELETE ALL |
| | FULL-OPEN VALVES AND INTERIOR WATER PIPING TO THE |
| | FIXTURES AS IS APPROVED ON SHEET P-2. PER CITY OF WPB |
| | AMENDMENTS TO CHAPTER 1, SECTION *106.1.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |