| Date |
Text |
| 2006-10-20 16:45:48 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | A. OK |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT P-1 PLUMBING RISER FOR BUILDING 1 |
| | DOES NOT REFLECT THE FLOOR PLAN. |
| | BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT |
| | RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS |
| | 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE |
| | OPPOSITE SIDE OF THE TOILET ROOM THAN |
| | THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW |
| | THE LAV STACKS VENTING THE W/C'S. - L/T |
| | SHALL NOT DRAIN THROUGH THE WET VENT OF |
| | THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF |
| | THE BATHROOM GROUP. |
| | SECTION 909.1. (SEE RED LINE EXAMPLE ONE |
| | SET OF PLANS). |
| | ****RESPONSE NOTED, BUT BAYS 9, 10, 13, |
| | 17, 20 DO NOT REFLECT THE FLOOR PLANS. |
| | THE FIXTURES ARE TURNED TO THE WRONG |
| | SIDE OF THE VENT PIPING. SEE FLOOR PLAN. |
| | - SHOW ALL PIPE SIZES. |
| | ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN |
| | CHANGED FOR ALL UNITS. THE 1-1/4" SANITARY TO THE |
| | LAUNDRY SINK DOES NOT MEET CODE. TABLE 709.1.-BAYS |
| | 3, 7, 11, 15, 19, & 21 THE BRANCH LINES DO NOT REFLECT |
| | THE FLOOR PLAN PIPING LAYOUT. BAYS 9 THRU 21 THE PIPING |
| | TO THE FIXTURES ARE FACING THE WRONG WAY. - NOT ALL |
| | PIPE SIZES ARE SHOWN. SECTION 104.2.1, TABLES 710.1(1) |
| | & 710.1(2).THE LAVS IN BAYS 1, 5, 9, 13, 17, & 20 ARE |
| | NOT VENTED AS SHOWN AND INDICATES THAT THE TRAP IS |
| | UNDERGROUND. SECTIONS 104.2.1 AND 901.2.1.THE FLOOR |
| | PLAN ON SHT S-1 SHOWS CLEANOUTS UPSTREAM OF THE W/C'S. |
| | THESE ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CLARIFY. |
| | |
| | 5. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| | BUILDING 2 DOES NOT REFLECT THE FLOOR |
| | PLAN. (SEE PREVIOUS COMMENT AND ADJUST |
| | RISER TO FLOOR PLAN AND PIPE PER CODE. |
| | SECTIONS 106.1.1 & 909.1. |
| | ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| | SIZES. |
| | ******RESPONSE NOTED, BUT THE RISER DIAGRAM HAS BEEN |
| | CHANGED FOR ALL UNITS. ALL BAYS, THE 1-1/4" SANT. TO |
| | THE LAUNDRY SINK DOES NOT MEET CODE. ALL BAYS, THE LAV |
| | IS NOT VENTED AS SHOWN, AND THE TRAP IS INDICATED AS |
| | BEING UNDERGROUND AS SHOWN.SECTIONS 104.2.1, 901.2.1 |
| | AND TABLE 709.1. SHT S-2 INDICATES CLEANOUTS UPSTREAM |
| | OF THE W/C'S. THE SANT. RISER DIAGRAM DOES NOT REFLECT |
| | THIS. PLEASE CLARIFY. |
| | |
| | 6. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| | BUILDING 3 DOES NOT REFLECT THE FLOOR |
| | PLAN. (SEE COMMENT #4 AND ADJUST RISER |
| | TO REFLECT THE FLOOR PLAN, AND PIPE PER |
| | CODE. SECTIONS 106.1.1 & 909.1. |
| | ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| | SIZES. |
| | ******RESPONSE NOTED, BUT THE 1-1/4" SANT. TO THE |
| | LAUNDRY SINKS DOES NOT MEET CODE. TABLE 709.1. THE LAVS |
| | ARE NOT VENTED AS SHOWN AND THE TRAPS ARE UNDERGROUND |
| | AS PIPED. SECTION 901.2.1. SHT S-3 SHOWS CLEANOUTS |
| | UPSTREAM OF THE W/C'S ON THE FLOOR PLAN BUT THE SANT. |
| | RISER DOES NOT REFLECT THIS. PLEASE CLARIFY. |
| | |
| | 7. SHT P-1 TYPICAL COLD RISER DOES NOT |
| | REFLECT THE FLOOR PLANS. SUBMIT A WATER |
| | RISER DIAGRAM FOR EACH BUILDING THAT |
| | REFLECT THE FLOOR PLAN OF THAT BUILDING. |
| | SHOW ALL PIPE SIZES, VALVES, INDICATE |
| | BAY NUMBER, INDICATE PIPING MATERIAL. |
| | INDICATE IF WATER IS UNDERGROUND OR |
| | ABOVE GROUND. - AN RPZV BACKFLOW IS |
| | REQUIRED FOR EACH BUILDING. SECTIONS |
| | 106.1.1, 606.1, 606.2, 608.13.2. |
| | ****RESPONSE NOTED, BUT THE WATER RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | THE FIXTURES ARE LOCATED EAST TO WEST IN |
| | THE TOILET ROOM AND THE FIXTURE LAYOUT |
| | ON THE RISER IS FROM SOUTH TO NORTH. |
| | WATER SERVICE IS NOT AS SHOWN ON THE C-1 |
| | SHEET. SEPARATE BACKFLOW REQUIRED FOR |
| | EACH BUILDING. SHOW ALL PIPE SIZES. |
| | INDICATE PIPING MATERIAL. |
| | ******RESPONSE NOTED, BUT NO MENTION OF THE MATERIAL |
| | FOR THE WATER PIPING WAS INDICATED. ALL BAYS ALL |
| | BUILDINGS SHOW A VALVE ABOVE THE FLOOR DOWNSTREAM OF |
| | ALL W/C'S. PLEASE INDICATE WHAT THAT VALVE IS FOR. |
| | SECTION 104.2.1. - BLDGS 2 & 3 WATER RISER DIAGRAMS DO |
| | NOT REFLECT THE FLOOR PLAN FIXTURE LAYOUT. INDICATE |
| | WHATE THE VALVE DOWNSTREAM OF ALL WATER CLOSETS IS FOR. |
| | SECTION 104.2.1. |
| | |
| | 8. OK |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | |
| | **************NEW COMMENT************** |
| | |
| | 1C. INFORMATIONAL - SEPARATE IRRIGATION PLANS AND |
| | PERMIT ARE REQUIRED. SECTION 104.3.1.1. |
| | |
| | REVIEW BY KEN STEVENS |