| 2006-08-04 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED.THE NOC PROVIDED |
| | IS EXPIRED; OVER 90 DAYS WITHOUT |
| | COMMENCING WORK, FS713.13(2). |
| | |
| | 2.)SEPARATE PERMITS FOR EACH BUILDING |
| | AND THE DUMPSTER WILL BE REQUIRED FOR |
| | INSPECTION PURPOSES.SEPARATE PLANS ARE |
| | NOT REQUIRED. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)PER HAROLD PISKURA, THIS WILL NOT |
| | BE A RESIDENT INSPECTOR JOB AT THIS |
| | TIME. |
| | |
| | 5.)ADDRESSED. |
| | |
| | 6.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR PERMITTING, FBC*106.3.3. |
| | |
| | NEW COMMENT: FIRST REVIEW WAS IN |
| | JANUARY. IN FEBRUARY THE STATE OF |
| | FLORIDA INFORMED ME THAT THE 2001 |
| | FLORIDA STATE PRODUCT APPROVALS WERE NO |
| | LONGER GRANDFATHERED IN. PLEASE PRINT |
| | THE 2004 FLORIDA STATE PRODUCT |
| | APPROVALS. |
| | |
| | 7.-15.)ADDRESSED. |
| | |
| | 16.)FOR THE ROOF, INDICATE WHICH |
| | APPROVED ASSEMBLY YOU ARE USING IN THE |
| | PRODUCT APPROVAL. |
| | |
| | 2ND REVIEW - YOU HAVE HIGHLIGHTED ONE OF |
| | THE COMPONENTS.PLEASE CHOOSE AN |
| | APPROVED ASSEMBLY, BETWEEN PAGES 9-16. |
| | |
| | NEW COMMENT: |
| | |
| | 17.)YOU HAVE DECLARED A TYPE VA IN |
| | RESPONSE TO ANOTHER COMMENT.THIS |
| | REQUIRES 1 HOUR FOR STRUCTURAL ELEMENTS |
| | LISTED IN FBC TABLE 601.PROVIDE |
| | CALCULATED FIRE RESISTANCE OR APPROVED |
| | ASSEMBLY, DETAILS, AND NOTE ON THE PLAN. |
| | SHOW ALL REQUIRED OPENING PROTECTIVES |
| | AND DETAILS FOR PENETRATIONS. |
| | |
| | 18.) IF YOU CHANGE THE BUILDING TYPE, |
| | PLEASE SHOW COMPLIANCE WITH FBC TABLE |
| | 602 AS WELL AS FBC TABLE 503. |
| | |
| | 19.)SP1, NOTE DISTANCE FROM THE |
| | PROPERTY LINE FOR BUILDING 2 AND |
| | BUILDING 3.ALSO PLEASE MARK BUILDING |
| | 2. |