| 2006-08-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | A. OK |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT A-7 DETAIL "A" SHOW THE FLUSH |
| | CONTROLS. 11-4.16.5 FOR THE W/C AND |
| | FAUCET TYPE 11-4.19.5 FOR THE LAV. |
| | ****RESPONSE NOTED, BUT PER 11-4.16.5 |
| | THE FLUSH CONTROLS SHALL BE ON THE WIDE |
| | SIDE OF THE W/C. |
| | |
| | 4. SHT P-1 PLUMBING RISER FOR BUILDING 1 |
| | DOES NOT REFLECT THE FLOOR PLAN. |
| | BUILDING 1 SHOWS 12 BAYS ON SHT A-1, BUT |
| | RISER DIAGRAM SHOWS ONLY 10 BAYS. BAYS |
| | 1, 3, 5, 7, & 10 STACK IS SHOWN ON THE |
| | OPPOSITE SIDE OF THE TOILET ROOM THAN |
| | THE LAV & L/T. SHOW ALL PIPE SIZES, SHOW |
| | THE LAV STACKS VENTING THE W/C'S. - L/T |
| | SHALL NOT DRAIN THROUGH THE WET VENT OF |
| | THE BATHROOM FIXTURES, BUT SHALL CONNECT DOWNSTREAM OF |
| | THE BATHROOM GROUP. |
| | SECTION 909.1. (SEE RED LINE EXAMPLE ONE |
| | SET OF PLANS). |
| | ****RESPONSE NOTED, BUT BAYS 9, 10, 13, |
| | 17, 20 DO NOT REFLECT THE FLOOR PLANS. |
| | THE FIXTURES ARE TURNED TO THE WRONG |
| | SIDE OF THE VENT PIPING. SEE FLOOR PLAN. |
| | - SHOW ALL PIPE SIZES. |
| | |
| | 5. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| | BUILDING 2 DOES NOT REFLECT THE FLOOR |
| | PLAN. (SEE PREVIOUS COMMENT AND ADJUST |
| | RISER TO FLOOR PLAN AND PIPE PER CODE. |
| | SECTIONS 106.1.1 & 909.1. |
| | ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| | SIZES. |
| | |
| | 6. SHT P-1 PLUMBING RISER DIAGRAM FOR |
| | BUILDING 3 DOES NOT REFLECT THE FLOOR |
| | PLAN. (SEE COMMENT #4 AND ADJUST RISER |
| | TO REFLECT THE FLOOR PLAN, AND PIPE PER |
| | CODE. SECTIONS 106.1.1 & 909.1. |
| | ****RESPONSE NOTED, BUT SHOW ALL PIPE |
| | SIZES. |
| | |
| | 7. SHT P-1 TYPICAL COLD RISER DOES NOT |
| | REFLECT THE FLOOR PLANS. SUBMIT A WATER |
| | RISER DIAGRAM FOR EACH BUILDING THAT |
| | REFLECT THE FLOOR PLAN OF THAT BUILDING. |
| | SHOW ALL PIPE SIZES, VALVES, INDICATE |
| | BAY NUMBER, INDICATE PIPING MATERIAL. |
| | INDICATE IF WATER IS UNDERGROUND OR |
| | ABOVE GROUND. - AN RPZV BACKFLOW IS |
| | REQUIRED FOR EACH BUILDING. SECTIONS |
| | 106.1.1, 606.1, 606.2, 608.13.2. |
| | ****RESPONSE NOTED, BUT THE WATER RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN. |
| | THE FIXTURES ARE LOCATED EAST TO WEST IN |
| | THE TOILET ROOM AND THE FIXTURE LAYOUT |
| | ON THE RISER IS FROM SOUTH TO NORTH. |
| | WATER SERVICE IS NOT AS SHOWN ON THE C-1 |
| | SHEET. SEPARATE BACKFLOW REQUIRED FOR |
| | EACH BUILDING. SHOW ALL PIPE SIZES. |
| | INDICATE PIPING MATERIAL. |
| | |
| | 8. OK |
| | **************NEW COMMENTS************** |
| | |
| | 1B. DRINKING FOUNTAINS ARE REQUIRED. |
| | WATER BOTTLES NOT APPROVED FOR OVER 50% |
| | OF THE FIXTURES REQUIRED. TABLE 403.1. |
| | |
| | 2B. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | INCLUDING 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | |
| | 3B. SHT A-4 TYPICAL GUTTER DRAIN DETAIL. |
| | INDICATE WIDTH OF OPENING TO DETERMINE |
| | THE OPENING SIZE TO COMPLY WITH TABLE |
| | 1106.3. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |