| Plan Review Notes For Permit 05091674 |
| Permit Number |
05091674 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-15 09:41:14 | ***** REDLINED ****** | | | | | | 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR | | | FOR EACH BLDGS 1 AND 2 IS NOT LARGE ENOUGH PER TABLES | | | IN 250.66. REDLINED MIN SIZE FOR EACH OF THESE SHALL BE | | | 2/0 MIN. THERE IS NO NEED TO REVISE PLANS UNLESS THERE | | | ARE OTHER REVISIONS DURING THE CONSTRUCTION AND BEFORE | | | SLAB/FOOTER ELECTRICAL INSPECTION. | | | THIS HOWEVER SHALL BE A MIN OF 2/0 TO THE FOOTER | | | STEEL. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|