| Plan Review Notes For Permit 05091674 |
| Permit Number |
05091674 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | ******DENIED****** | | | | | | 1) SHTS A-1, A-2 AND A-3 INDICATE | | | INCORRECT CODE REFERENCE. NFPA 101, 2003 | | | EDITION SHALL BE REFERENCED. | | | | | | 2) ADDRESS NUMBERS ARE REQUIRED ON THE | | | BUILDINGS, TO BE A MINIMUM OF 6" IN | | | HEIGHT AND CONTRASTING WITH THE | | | BACKGROUND. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND MOUNTED AT DISTANCES TO | | | SATISFY THE 75' TRAVEL REQUIREMENT. | | | | | | 4) PLEASE ILLUSTRATE ALL EXISTING WATER | | | SUPPLIES PERTINENT TO THIS PROPERTY. | | | | | | 5) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241 AND | | | OTHER APPLICABLE CODES. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|