| 2006-01-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED.THE NOC PROVIDED |
| | IS EXPIRED; OVER 90 DAYS WITHOUT |
| | COMMENCING WORK, FS713.13(2). |
| | |
| | 2.)SEPARATE PERMITS FOR EACH BUILDING |
| | AND THE DUMPSTER WILL BE REQUIRED FOR |
| | INSPECTION PURPOSES.SEPARATE PLANS ARE |
| | NOT REQUIRED. |
| | |
| | 3.)LANDSCAPE PLAN IS TO BE SIGNED AND |
| | SEALED IN ACCORDANCE WITH FS481.306, |
| | FAC61G10-11.010. |
| | |
| | 4.)FBC* 105.3RESIDENT INSPECTOR. |
| | SUBMIT INSPECTOR RESUME' AND LICENSE |
| | DOCUMENTS TO HAROLD PISKURA, 805-6711. |
| | ARESIDENT INSPECTOR PROGRAM IS |
| | REQUIRED, ON THIS PROJECT, DUE TO ONE OR |
| | MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION |
| | |
| | 5.)GOVERNING CODE EFFECTIVE OCTOBER 1, |
| | 2005 IS FBC2004.REVISE ALL REFERENCES. |
| | SOME STATE FBC2001, A1 STATES SBC. |
| | |
| | 6.)PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR PERMITTING, FBC*106.3.3. |
| | |
| | 7.)THE SOILS REPORT IS TO HAVE THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR |
| | THE FIRM, ALLTERRA, PRINTED ON EACH |
| | SHEET, FAC61G15-23.002. |
| | |
| | 8.)SHEET SP1, BUILDING DATA, DECLARES |
| | S1 OCCUPANCY, ORDINARY HAZARD.SEE |
| | FBC311.S1 IS MODERATE-HAZARD STORAGE. |
| | |
| | 9.) SHEET SP1, BUILDING DATA, DECLARE |
| | BUILDINGS AS TYPE VA OR VB, SO THAT |
| | COMPLIANCE WITH FBC TABLE 503, FBC TABLE |
| | 601 CAN BE DETERMINED. |
| | |
| | 10.)INDICATE ON SHEET SP1, BUILDING |
| | DATA, WHETHER THE BUILDINGS ARE |
| | SPRINKLED OR UNSPRINKLED. |
| | |
| | 11.)SHEET S1, UPLIFT CALCS, SHOW AN |
| | OVERHANG OF 6 FT, HALF TRUSS SPAN OF 1.2 |
| | FT.PLEASE CLARIFY. |
| | |
| | 12.)BAR JOIST PLANS MAKE REFERENCE TO |
| | WOOD TRUSSES AND CONNECTORS.PLEASE |
| | CLARIFY.NO WOOD TRUSSES SHOWN ON ROOF |
| | FRAMING PLAN OR WALL SECTIONS. |
| | |
| | 13.)ROOF DRAINAGE CALCS ARE TO COMPLY |
| | WITH FBC2004, S7. |
| | |
| | 14.)DECLARE AN OCCUPANT LOAD FOR EACH |
| | UNIT. |
| | |
| | 15.)SHOW THE ACCESSIBLE ROUTE, |
| | FBC11-4.1.2(1).SHOW MAXIMUM SLOPE. |
| | |
| | 16.)FOR THE ROOF, INDICATE WHICH |
| | APPROVED ASSEMBLY YOU ARE USING IN THE |
| | PRODUCT APPROVAL. |
| | |
| | |