| Plan Review Notes For Permit 05091663 |
| Permit Number |
05091663 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-06 00:00:00 | PANEL VA IS SHOWN WITH EQUIPMENT IN | | | FRONT.110.26 SHALL APPLY AND 30" W | | | INFRONT BY 36"D IN FRONT SHALL BE | | | MAINTAINED. | | | | | | ALL OUTLETS WITHIN 6' OF A SINK SHALL BE | | | GFCI PROTECTED. | | | | | | JAKE LEAHY 644-7291 |
|