| Plan Review Notes For Permit 05091660 |
| Permit Number |
05091660 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-11-28 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. | | | | | | 2- PROVIDE KEY PLAN AND COMPLETE | | | INSTALLATION SCHEDULE FOR PROPOSED | | | INSTALLATION. | | | | | | 3- CLEARLY MARK ON DRAWINGS ANCHOR | | | SCHEDULE SPECIFIC ANCHOR TYPE AND | | | SPACING TO BE USED ACCORDING TO DESIGN | | | PRESSURES, SHUTTER SPAN, EDGE DISTANCE, | | | CONNECTION TYPE, GLASS SEPARATION, AND | | | STRUCTURE TO BE ATTACHED TO (CONCRETE, | | | CONCRETE BLOCK OR WOOD). | | | | | | 4- WIND LOAD CHART NEEDS TO BE SIGNED | | | AND SEALED BY THE ENGINEER OR ARCHITECT | | | WHO MADE THE CALCULATIONS USING ASCE | | | 7-98. SEC. 104.2.1.2 CITY AMENDMENTS TO | | | FBC 2001. | | | NOTE: FOR BUILDINGS WITH MEAN ROOF | | | HEIGHT OF LESS THAN 30'-0" TABLE 1606.2B | | | FROM THE FBC 2001 MAY BE USED AND | | | ENGINEERING IS NOT REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|