| 2006-06-06 00:00:00 | PROVISO:2001 FBC/BUIDLING 7/5 UNITS |
| | |
| | PLEASE REVISE THE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | 1.PLAN SHEET M0.1, DETAIL ON THE AHU |
| | MOUNTING NOTE #15 STATES "NO |
| | COMBUSTIBLES ALLOWED IN THE MECHANICAL |
| | CLOSET" AS IT SERVES AS A PLENUM.THE |
| | DOOR SCHEDULE ON PLAN SHEET A-4.7.3 |
| | INDICATES THE AHU CLOSET DOOR AS A WOOD |
| | LOUVERED DOOR.PLEASE CLARIFYNWITH THE |
| | DOOR MANUFACTURE THAT THIS DOOR MEETS |
| | THE 25 FLAME/50 SMOKE INDEX AS SPECIFIED |
| | IN 2001 FMC 602.2.1. |
| | |
| | 2.O.A. CALCULATIONS INDICATED ON PLAN |
| | SHEET M0.1 ARE BASED ON INFILTRATION |
| | RATES.THE INFILTRATION RATES ARE THE |
| | MAXIMUM ALLOWED BY CODE AND MAY NOT |
| | REFLECT A "TRUE" RATE.PLEASE PROVIDE |
| | CALCS IN ACCORDANCE WTIH 2001 FMC 402.2, |
| | 402.2.1 OR TABLE 403.3.PLEASE NOTE, |
| | PLAN SHEET M2 INDICATES A 6" O.A. DUCT. |
| | PLEASE DELETE FROM THE PLAN IF THIS IS |
| | NOT GOING TO BE INSTALLED. |
| | |
| | 3.SPECIFICDRYERS AS TO BE INSTALLED |
| | BY FINAL INSPECTION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |