| 2005-11-29 00:00:00 | DENIED:BUILDING 7 / 2001 FBC |
| | 1.PLAN SHEET A-0.0.0 PROJECT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED SPRINKLERED.PLEASE |
| | INDICATE WHICH SYSTEM WILL BE USED |
| | (13,13R, 13D ETC).PLEASE NOTE, |
| | ADDITIONAL COMMENTS MAY BE GENERATED BY |
| | THE RESPONSE GIVEN. |
| | |
| | 2.PLAN SHEET A-4.6.2 KEY NOTES/LEGEND, |
| | ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| | PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 3.PLAN SHEET M0.1 EQUIPMENT SCHEDULE |
| | INDICATES AHU-1 AS A 5 TON UNIT.NOTE |
| | #2 INDICATES AREA SMOKE DETECTORS TO |
| | SHUT DOWN AHU.PLEASE INDICATE THIS ON |
| | THE ELECTRICAL PLANS FOR UNITS 97D & |
| | 93D. |
| | |
| | 4.PLEASE CLARIFY RATING OF THE WALL |
| | BETWEEN THE GARAGE & THE RESIDENCE.THE |
| | ARCHITECTURAL PLANS ARE NOT CLEAR AS TO |
| | WHERE THE 1HR RATING ENDS (AT THE SLAB |
| | OR AT THE RATED CEILING). |
| | |
| | 5.PLAN SHEET M1 R/A JUMPER FROM THE |
| | GUEST SUITE IN UNITS 97D & 93D IS NOT |
| | SIZE IN ACCORDANCE WITH 2001 FMC 601.4 |
| | EXCEPTION 1 & 3. R/A JUMPER FROM THE |
| | GUEST SUITE SHALL BE A MINIMUM OF 12". |
| | |
| | 6.PLAN SHEET M3 R/A TRANSFER GRILLES |
| | ARE NOT SIZED PROPERLY.SHOW COMPLIANCE |
| | WITH 2001 FMC 601.4 EXCEPTION 2 & 3. |
| | |
| | 7.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| | TABLE 403.3. |
| | |
| | 8.PLAN SHEET M3, THE DRYER EXHAUST |
| | EXCEEDS THE REQUIRED 25FT MAXIMUM |
| | DISTANCE PER 2001 FMC 504.6. |
| | |
| | 9.PLEASE PROVIDE A DETAIL FOR THE AHU |
| | LOCATED IN THE 2ND FLOOR CLOSET.SHOW |
| | COMPLIANCE WITH 2001 FMC 603.9 & |
| | 610.1.ABC.3.7 OF THE 2001 FBC. |
| | |