| Date |
Text |
| 2006-05-25 00:00:00 | PROVISO:2001 FBC/BUILDING #18/4 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | COMMENT #6:PLAN SHEET M0.1 AHU DETAIL, |
| | NOTE 15 INDICATES NO COMUSTIBLES ALLOWED |
| | IN THE AHU CLOSET WHICH SERVES AS THE |
| | RETURN AIR PLENUM.THE LOUVERED DOOR |
| | LISTED ON PLAN SHEET A-4.0.2 IS |
| | CONSTRUCTED OF WOOD.PLEASE NOTE, THE |
| | DOOR & FRAME SHALL MEET THE 25 FLAME/50 |
| | SMOKE INDEX AS SPECIFIED IN 2001 FMC |
| | 602.2.1. |
| | |
| | COMMENT #9:OUTSIDE AIR CALCULATIONS |
| | THAT ARE INDICATED ON PLAN SHEET M0.1 |
| | ARE BASED ON INFILTRATION RATE.THE |
| | INFILTRATION RATES ARE THE "MAXIMUM" |
| | ALLOWED BY CODE AND MAY NOT BE A "TRUE" |
| | RATE.PLEASE PROVIDE CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FMC 402.2, 402.2.1 |
| | OR TABLE 403.3.PLEASE NOTE, 6" OUTSIDE |
| | AIR DUCT IS INDICATED ON PLAN SHEEET M2. |
| | PLEASE REMOVE FROM THE PLAN IF THE O.A. |
| | DUCT WILL NOT BE INSTALLED. |
| | |
| | PLEASE NOTE, SPECIFIC DRYERS INDICATED |
| | ON THE PLAN SHALL BE INSTALLED FOR FINAL |
| | INSPECTION. |
| | |