| 2005-11-30 00:00:00 | DENIED:BUILDING 18 / 2001 FBC |
| | 1.PLAN SHEET A-0.0.0 PROJECT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED SPRINKLERED.PLEASE |
| | INDICATE WHICH SYSTEM WILL BE UTILIZED |
| | (13, 13R, 13D?).PLEASE NOTE, |
| | ADDITIONAL COMMENTS MAY BE GENERATED BY |
| | RESPONSES GIVEN. |
| | |
| | 2.PLAN SHEET A-4.0.1 KEY NOTES/LEGEND, |
| | ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| | PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 3.PLEASE CLARIFY FIRE RATING OF THE |
| | WALL SEPARATING THE GARAGE & THE |
| | RESIDENCE, DOES THE RATING CONTINUE TO |
| | THE SLAB OR STOP AT THE RATED CEILING? |
| | |
| | 4.PLAN SHEET M1 INDICATES SUPPLY DUCT |
| | & EXHAUST PENETRATING A RATED WALL. |
| | DUCT SHALL COMPLY WITH 2001 FMC 607.1.3 |
| | #3 ITEMS 1 THROUGH 4. |
| | |
| | 5.PLAN SHEET M2 THE DRYER EXHAUST |
| | APPEARS TO RUN THROUGH THE MECHANICAL |
| | CLOSET WHICH IS A PLENUM.PER 2001 FMC |
| | 601.3 EXHAUST DUCT OR VENTS SHALL NOT |
| | EXTEND INTO OR PASS THROUGH PLENUMS. |
| | |
| | 6.AHU CLOSET SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH 2001 FMC 603.9.NO |
| | COMBUSTIBLES ALLOWED IN THE RETURN AIR |
| | PLENUM PER 2001 FMC 602.2.1. |
| | |
| | 7.PLEASE PROVIDE A DETAIL OF THE AHU |
| | CLOSET. |
| | |
| | 8.PLEASE PROVIDE A DETAIL FOR THE |
| | MOUNTING OF THE CONDESING UNITS.SHOW |
| | COMPLIANCE WITH 2001 FMC 301.13. |
| | |
| | 9.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER TABLE 403.3 OF THE 2001 |
| | FMC. |
| | |
| | 10. R/A TRANSFER GRILLES SHALL COMPLY |
| | WITH 2001 FMC 601.4 EXCEPTION 2 & 3 FOR |
| | PROPER SIZING. |
| | |