| Date |
Text |
| 2006-05-25 00:00:00 | PROVISO: 2001 FBC/BUILDING 17/5 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | COMMENT #4: REVISED PLANS REMOVED THE |
| | BOOSTER FANS.PLANS REFLECT SPECIFIC |
| | DRYER TO BE INSTALLED PER MANUFACTURE'S |
| | INSTRUCTIONS TO COMPLY WITH 2001 FMC |
| | 504.6.PLEASE NOTE, SPECIFIC DRYER TO |
| | BE INSTALLED FOR FINAL INSPECTION. |
| | |
| | COMMENT #5:OUTSIDE AIR CALCULATIONS |
| | ARE INDICATED ON PLAN SHEET M0.1. |
| | PLEASE NOTE, INFILTRATION RATES ARE |
| | "MAXIMUM" RATES AND MAY NOT ACTUALLY |
| | EXIST AT THE RATE SPECIFIED ON THE PLAN. |
| | PLEASE SHOW COMPLIANCE WITH 2001 FMC |
| | 402.2, 402.2.1 OR TABLE 403.3.PROVIDE |
| | CALCUATIONS.PLAN SHEET M2 INDICATES A |
| | 6" O.A. DUCT, PLEASE REMOVE IF THIS IS |
| | NOT BEING INSTALLED. |
| | |
| | COMMENT #6:AHU CLOSET IS TO BE |
| | CONSTRUCTED IN ACCORDANCE WITH 2001 FMC |
| | 603.9 & 610.1.ABC.3.7 OF CHAPTER 13 OF |
| | THE 2001 FBC.THIS INCLUDES THE |
| | LOUVERED DOOR & FRAME ALSO. |
| | ARCHITECTURAL PLAN A-4.0.2 SHOWS THE |
| | LOUVERED DOOR AS WOOD.THE DOOR & FRAME |
| | MUST HAVE A FLAME SPREAD INDEX NOT |
| | GREATER THAN 25 & A SMOKE DEVELOPED |
| | INDEX NOT MORE THAN 50 WHEN TESTED IN |
| | ACCORDANCE WITH ASTM 84. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |