| 2005-11-29 00:00:00 | DENIED:BUILDING 17 / 2001 FBC |
| | 1.PLAN SHEET A-0.0.0 PROJECT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED SPRINKLERED.PLEASE |
| | INDICATE WHICH SYSTEM WILL BE USED (13, |
| | 13R, 13D ETC).PLEASE NOTE, ADDITIONAL |
| | COMMENTS MAY BE GENERATED BY THE |
| | RESPONSE GIVEN. |
| | |
| | 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| | ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| | PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 3.PLAN SHEET M-1 IDNCIATES 8" SUPPLY |
| | DUCT & 3" EXHAUST PENETRATING THE RATED |
| | WALL BETWEEN THE GARAGE AND THE |
| | ERESIDENCE.THE ARCHITECTURAL PLANS ARE |
| | NOT CLEAR IF THE WALL CONTINUES PAST THE |
| | RATED CEILING.PLEASE NOTE, EXHAUST |
| | DUCTS PENETRATING A FIRE REATED WALL |
| | SHALL COMPLY WITH 2001 FMC 607.1.3 #3. |
| | |
| | 4.PLAN SHEET M2 DRYER EXHAUST EXCEEDS |
| | THE 25 FT REQUIREMENT WITH REDUCTIONS |
| | FOR 90'S PER 2001 FMC 504.6.PLAN SHEET |
| | E2.2.4 INDICATES 'BF' (BOOSTER FAN?). |
| | PLEASE NOTE, INSTALLATION OF BOOSTER |
| | FANS WILL BE REVIEWED BY THE BUILDING |
| | OFFICIAL UNDER "ALTERNATE MATERIALS & |
| | METHODS" 2001 FMC 103.7.1.PLEASE |
| | PROVIDE THE FOLLOWING INFORMATION FOR |
| | REVIEW:1) A LETTER FROM AN ENGINEER |
| | EMPLOYED BY THE DRYER MANUFACTURER |
| | STATING THE INSTALLATION OF THE BOOSTER |
| | FAN IS ACCEPTABLE AND WILL NOT VOID THE |
| | WARRANTY OF THE DRYER.2) MEANS OF |
| | NOTIFYING THE OWNER SHOULD THE BOOSTER |
| | FAN FAIL.3) MANUFACTURER'S SUBMITTAL & |
| | INSTALLATION DATA FOR THE BOOSTER FAN. |
| | 4) PROVIDE ALL PERTINENT INFORMATION FOR |
| | ALL TRADES MECHANICAL, ELECTRICAL, FIRE, |
| | ETC. FOR THE INSTALLATION OF BOOSTER |
| | FANS. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH TABLE |
| | 403.3 OF THE 2001 FMC. |
| | |
| | 6.PLEASE PROVIDE DETAIL FOR THE AHU |
| | LOCATED IN IN THE CLOSET.PLEASE NOTE |
| | MECHANICAL CLOSET SHALL BE CONSTRUCTED |
| | PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF |
| | CHAPTER 13 OF THE 2001 FBC. |
| | |
| | 7.PLAN SHEET M2, THE DRYER EXHAUST |
| | APPEARS TO RUN THROUGH THE PLENUM IN THE |
| | AHU CLOSET.PLEASE CLARIFY.PER 2001 |
| | FMV 601.3, EXHAUST DUCTS SHALL NOT |
| | EXTEND INTO OR PASS THROUGH RETURN AIR |
| | PLENUMS. |
| | |
| | 8.PLEASE NOTE, TRANSFER GRILLES FROM |
| | THE BEDROOM AREAS SHALL COMPLY WITH 2001 |
| | FMC 601.4 EXCEPTION 2 & 3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |