| 2006-05-23 00:00:00 | PROVISO:2001 FBC/BUILDING 16/6 UNITS |
| | RESPONSE TO COMMENTS FROM REVIEW DATED |
| | 11/29/05: |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | COMMENT #4:OUTSIDE AIR CALCULATIONS |
| | ARE INDICATED ON PLAN SHEET M0.1. PLEASE |
| | NOTE, INFLITRATION RATES ARE "MAXIMUM" |
| | RATES AND MAY NOT ACTUALLY EXIST. PLEASE |
| | SHOW COMPLIANCE WITH 2001 FMC 402.2, |
| | 402.2.1 OR TABLE 403.3.PLEASE NOTE, |
| | PLAN SHEET M2 ALSO INDICATES O.A. DUCT. |
| | PROVIDE CALCULATIONS. |
| | |
| | COMMENT #5:RESPONSE TO COMMENT |
| | INDICATES DRYER DUCT WILL BE ABOVE THE |
| | AHU CLOSET.PLAN SHEET M0.1 THE AHU |
| | MOUNTING DETAIL ALSO STATES NO |
| | COMBUSTIBLES ALLOWED IN THE AHU CLOSET |
| | AS IT SERVES AS A PLENUM.THE DOOR |
| | SCHEDULE INDICATES THE LOUVERED DOOR IS |
| | WOOD.PLEASE CLARIFY IF THIS WILL MEET |
| | THE 25 FLAME/50 SMOKE INDEX WHEN TESTED |
| | IN ACCORDANCE WITH ASTM 84. |
| | |
| | COMMENT 6:OK. PLEASE NOTE, SPECIFIC |
| | DRYERS ARE TO BE INSTALLED FOR FINAL |
| | INSPECTION. |
| | |
| | COMMENT #7: OK.PLEASE NOTE, PLAN SHEET |
| | M1 UNIT #46 A(R) DOES NOT REFLECT THE |
| | ARCHITECTURAL PLAN SHOWN ON A-2.0.1 & |
| | A-4.0.1. |
| | |