| Plan Review Notes For Permit 05091648 |
| Permit Number |
05091648 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-15 00:00:00 | ***** NOTES REDLINED ******* | | | | | | | | | | | | | | | ** PLEASE SEE #1 GEC SHOWN, WHERE A 2/0 | | | MIN IS REQUIRED PER 250.66BASED ON THE | | | SEC'S SHOWN ON RISER. | | | | | | ** PLEASE SEE 424.3B FOR MIN OCP SHALL | | | BE 125% FOR AHU'S. PLEASE SEE OCP HAS | | | NOW BEEN DECREASED TO 40A'S??? | | | | | | PLEASE KNOW, THE ABOVE NEED ONLY BE | | | REVISED IF MAKING OTHER ELECTRICAL | | | REVISIONS. ALL ELECTRICAL REVISIONS, | | | MUST BE SUBMITTED FOR REVIEW BEFORE | | | ROUGH ELECTRICAL INSPECTION. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|