| Plan Review Notes For Permit 05091647 |
| Permit Number |
05091647 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-15 00:00:00 | ***** UNSAT******* | | | | | | 1) NOTE: PLEASE SEE BUILDING TYPE AND | | | NUMBER OF UNITS INDICATED ON PLANS ID | | | FOR FOUR UNITS, AND SERVICE SUBMITTED IS | | | FOR 6 UNITS. PLEASE CORRELATE AND | | | REVISE.215.5 | | | | | | 2) NOTE:PLEASE SEE NO, SERVICE | | | ENTRANCE CONDUIT OR SERVICE ENTRANCE | | | CONDUCTORS ARE SHOWN ON RISER FROM FPL | | | TO 1000A SERVICE MAIN. | | | PLEASE SEE SEC'S ARE NOTED IN FAULT | | | CURRENT CALCS ONLY. | | | 215.5 | | | | | | 3) NOTE: PLEASE SEE #4 GEC SHOWN. PLEASE | | | SEE 250.66 FOR MIN SIZE REQ'D. BASED ON | | | SEC'S SHOWN ON FAULT CURRENT CALCS,3/0 | | | MIN REQ'D. | | | | | | 4) NOTE: PLEASE SEE 424.3B FOR MIN OCP | | | SHALL BE 125% FOR AHU'S. PLEASE SEE OCP | | | HAS NOW BEEN DECREASED TO 40A'S??? | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|