| Date |
Text |
| 2005-12-01 00:00:00 | DENIED:BUILDING 12 / 2001 FBC |
| | 1.PLAN SHEET A-0.0.0 PROJECT |
| | INFORMATION INDICATES TYPE VI, |
| | UNPROTECTED SPRINKLERED.PLEASE |
| | INDICATE WHIHC SYSTEM WILL BE UTILIZED |
| | (13, 13R, 13D?).PLEASE NOTE, |
| | ADDITIONAL COMMENTS MAY BE GENERATED BY |
| | THE RESPONSES GIVEN. |
| | |
| | 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND, |
| | ITEM #25 '1HR CHASE REFER TO 11/A-13'. |
| | PLAN SHEET A-13 WAS NOT SUBMITTED FOR |
| | REVIEW. |
| | |
| | 3.PLEASE CLARIFY FIRE RATING OF THE |
| | WALL SEPARATING THE GARAGE & THE |
| | RESIDENCE, DOES THE RATING CONTINUE TO |
| | THE SLAB OR THE RATED CEILING? |
| | |
| | 4.PLAN SHEET M1 INDICATES SUPPLY & |
| | EXHAUST DUCT PENETRATING RATED WALL. |
| | DUCT SHALL COMPLY WITH 2001 FMC 607.1.3 |
| | #3 ITEMS 1 THROUGH 4. |
| | |
| | 5.PLAN SHEET M2 INDICATES DRYER |
| | EXHAUST GOING THROUGH THE AHU CLOSET |
| | WHICH APPEARS TO BE A PLENUM.PER 2001 |
| | FMC 601.3 EXHAUST DUCT OR VENTS SHALL |
| | NOT EXTEND INTO OR PASS THROUGH A |
| | PLENUM. |
| | |
| | 6.DRYER EXHAUST EXCEEDS THE 25FT |
| | MAXIMUM LENGTH WITH THE 5FT REDUCTION |
| | FOR EACH 90.PLAN SHEET E2.2.4 |
| | INDICATES 'BF' (BOOSTER FAN?).PLEASE |
| | NOTE, INSTALLATION OF DRYER BOOSTER FANS |
| | WILL BE REVIEWED BY THE BUILDING |
| | OFFICIAL UNDER "ALTERNATE MATERIALS & |
| | METHODS" 2001 FMC 103.7.1.PLEASE |
| | PROVIDE THE FOLLOWING INFORMATION FOR |
| | REVIEW:1) A LETTER FRON AN ENGINEER |
| | EMPLOYED BY THE DRYER MANUFACTURER |
| | STATING THE INSTALLATION OF THE DRYER |
| | BOOSTER FAN IS ACCEPTABLE AND WILL NOT |
| | VOID THE WARRANTY OF THE DRYER.2) |
| | MEANS OF NOTIFYING THE OWNER SHOULD THE |
| | BOOSTER FAN FAIL.3) MANUFACTURER'S |
| | SUBMITTAL & INSTALLATION INSTRUCTIONS |
| | FOR THE BOOSTER FAN.4) PROVIDE ALL |
| | PERTINENT INFORMATION FOR ALL TRADES |
| | MECHANICAL, ELECTRICAL, FIRE, ETC. FOR |
| | THE INSTALLATION OF THE BOOSTER FANS. |
| | |
| | 7.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER TABLE 403.3 OFTHE 2001 |
| | FMC. |
| | |
| | 8.PLEASE PROVIDE A DETAIL OF THE AHU |
| | LOCATED IN THE CLOSET.PLEASE NOTE, |
| | MECHANICAL CLOSET SHALL BE CONTRUCTED |
| | PER 2001 FMC 603.9.NO COMBUSTIBLES |
| | ALLOWED IN THE RETURN AIR PLENUM PER |
| | 2001 FMC 602.2.1. |
| | |
| | 9.PLEASE PROVIDE A DETAIL OF THE |
| | ANCHORING OF THE CONDENSING UNIT PER |
| | 2001 FMC 301.13. |
| | |
| | 10. R/A TRANSFER GRILLES SHALL BE SIZED |
| | IN ACCORDANCE WITH 2001 FMC 601.4 |
| | EXCEPTION 2 & 3, THIS IS A REQUIRED |
| | MINIMUM. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |