| Date |
Text |
| 2006-05-25 00:00:00 | PROVISO:2001 FBC/BUILDING 14/5 UNITS |
| | |
| | PLEASE REVISE PLANS TO REFLECT THE |
| | IMPLEMENTATION OF THE PROVISO'S. |
| | |
| | COMMENT #3:BOOSTER FAN WAS DELETED |
| | FROM TEH PLAN. SPECIFIC DRYER WAS CHOSEN |
| | TO MEET CODE REQUIREMENT.PLEASE NOTE |
| | SPECIFIC DRYER TO BE INSTALLED FOR FINAL |
| | INSPECTION PER 2001 FMC 504.6. |
| | |
| | COMMENT #5:OUTSIDE AIR CALCUALTIONS |
| | THAT ARE INDICATED ON PLAN SHEET M0.1 |
| | ARE BASED ON INFILTRATION RATE.THE |
| | INFILTRATION RATES ARE THE "MAXIMUM" |
| | ALLOWED BY CODE AND MAY NOT BE A "TRUE" |
| | RATE.PLEASE PROVIDE CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FMC 402.2, 402.2.1 |
| | OR TABLE 403.3.PLEASE NOTE, 6" OUTSIDE |
| | AIR DUCT IS INDICATED ON PLAN SHEET M2. |
| | PLEASE REMOVE FROM THE PLAN IF THIS WILL |
| | NOT BE INSTALLED. |
| | |
| | COMMENT #8:PLAN SHEET M0.1 AHU DETAIL |
| | NOTE 15 INDICATES NO COMBUSTIBLES |
| | ALLOWED IN THE AHU CLOSET WHICH SERVES |
| | AS THE RETURN AIR PLENUM.THE LOUVERED |
| | DOOR LISTED ON PLAN SHEET A-4.0.2 IS |
| | CONSTRUCTED OF WOOD.PLEASE NOTE, THE |
| | DOOR & FRAME SHALL ALSO MEET THE 25 |
| | FLAME/50 SMOKE INDEX AS SPECIFIED IN |
| | 2001 FMC 602.2.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |