| Date |
Text |
| 2006-06-02 00:00:00 | DENIED |
| | |
| | 1) THE PLANS MUST BE STAMPED BY PALM |
| | BEACH COUNTY FOR IMPACT FEES. THE PLAN |
| | REVIEW NUMBER ON THE PLANS MUST |
| | CORRESPOND WITH THE P.R. NUMBER ON THE |
| | IMPACT FEE RECEIPT. |
| | |
| | 2) SUBMIT FIRE SPRINKLER PLANS FOR THE |
| | REQUIRED NFPA 13 SYSTEM. THIS IS |
| | REQUIRED BY FBC 104.3.1.1 OF THE CITY OF |
| | W.P.B. AMENDMENTS TO THE 2001 FBC. |
| | |
| | 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN |
| | DETAIL 17 ON A 10.0.0 DOES NOT |
| | CORRESPOND TO THE FC 5517 FIRE RATED |
| | ASSEMBLY LISTED IN THE GYPSUM |
| | ASSOCIATION MANUAL. PLEASE CORRECT. |
| | |
| | 4) NUMBER 20 ON THE DOOR SCHEDULE |
| | SPECIFIES A VENTED GARAGE DOOR. THE |
| | PRODUCT APPROVAL FOR THE GARAGE DOOR |
| | DOES NOT INDICATE VENTS IN THE DOOR. |
| | |
| | 5) REVISE DETAIL 11 ON A 10.0.0 TO |
| | SPECIFY THE 2001 FBC AND NOT THE CURRENT |
| | EDITION OF THE STANDARD BUILDING CODE. |
| | |
| | 6) THE DRAWINGS ATTACHED TO THE STATE |
| | PRODUCT APPROVAL FOR THE STEEL DOOR FROM |
| | MASONITE INTERNATIONAL ARE FOR A 6'-8" |
| | DOOR AND THE PLAN SPECIFIES AN 8'-0" |
| | DOOR. SEE FL 4940.3 AND DRAWING |
| | DWG-MA-FLO 133-05. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE |
| | TRUSS CONNECTORS. (SIMPSON-HETAL 12 & |
| | 16, USP-USC) THE FL COVERSHEET SUBMITTED |
| | FOR THE USP HANGERS AND COLUMN BASES & |
| | CAPS HAS A WINDOW MULLION NOA ATTACHED |
| | TO IT. |
| | |
| | 8) THE MIAMI-DADE NOA FOR THE SINGLE |
| | HUNG WINDOWS IS INCOMPLETE. THERE ARE |
| | SHEETS WITH ANOTHER NOA NUMBER ATTACHED |
| | AT THE REAR OF THE SH WINDOW NOA. |
| | |
| | 9) THE DECORATIVE BAHAMA SHUTTERS WILL |
| | REQUIRE A SEPARATE PERMIT. |
| | |
| | 10) FS 713.13 IF THE IMPROVEMENT |
| | DESCRIBED IN THE NOTICE OF COMMENCEMENT |
| | IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE |
| | IS VOID AND OF NO FURTHER EFFECT. |
| | (THE NOC WILL NEED TO BE RE-RECORDED |
| | BEFORE THE PERMIT IS ISSUED.) |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |