| 2006-01-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | CITY WPB CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS: THE |
| | PERSONAL SEAL, SIGNATURE, AND THE DATE |
| | THE ARCHITECT SHALL APPEAR ON ALL |
| | DOCUMENTS TO BE FILED FOR PUBLIC RECORD. |
| | THE SIGNATURE IS A "STAMP OF THE |
| | SIGNATURE" AND AS SUCH IS NOT APPROVED. |
| | THERE IS NOT DATE ON THE SEAL WHEN IT |
| | WAS AFFIXED TO THE PLANS. FAC |
| | 61G1-16.003 61G1-16.004(5) & FS 481.2055 |
| | 2. SHT A.003 DETAILS 1(A)(B)(C)(D), |
| | 2(A)(B), & 4(A)(B(C)(D), WATER CLOSETS |
| | ADJACENT TO WALLS SHALL BE 1'6", NOT |
| | 1'6" MINIMUM. THIS IS AN ABSOLUTE |
| | MEASUREMENT. SEE PAGES 6.3 & 6.5 FHA |
| | DESIGN MANUAL. |
| | 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS |
| | PER REQUIREMENTS #6 & 7B FHA DESIGN |
| | MANUAL. THE CLEAR FLOOR SPACE FOR THE |
| | SHOWERS SHALL BE PARALLEL WITH THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL. |
| | SEE PAGE 7.56 FHA DESIGN MANUAL. |
| | 4. SHT A.003 UNIT DETAILS INDICATE |
| | "APPLICABLE TO UNITS A, B, C, D ETC. BUT |
| | FLOOR PLANS INDICATE UNITS C1, C2, C3, |
| | C4 ETC. PLEASE CORRELATE FLOOR PLANS |
| | WITH TYPICAL DETAILS. SECTION 104.2.1. |
| | 5. SHT A.003 INDICATE WHICH POWDER ROOM |
| | DETAILS APPLY TO WHICH "TH" UNITS. |
| | SECTION 104.2.1. |
| | 6. SHT A.003 DETAIL 1(C) PER HUD, THE |
| | BIDET HAS NO REQUIREMENTS, BUT THE BIDET |
| | SHALL NOT ENCROACH INTO THE CLEAR FLOOR |
| | SPACE OF THE WATER CLOSET. |
| | 7. SHT A-106 BUSINESS OFFICE (553) |
| | ACCESS TO TOILET FACILITIES SHALL BE |
| | LOCATED NOT MORE THAN ONE STORY ABOVE OR |
| | BELOW THE EMPLOYEES REGULAR WORK AREA. |
| | SECTION 403.4. |
| | 8. SHT A-108 SUBMIT CALCULATION FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | THE SF FOR EACH AREA DRAINED, ALONG WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS AND ANY |
| | AREA OF ROOF THAT DRAINS ONTO THE ROOF |
| | FROM ABOVE. SECTIONS 1106 & 1107 AND ALL |
| | SUBSECTIONS. |
| | 9. SHTS A-801 THRU A-802C & A-808 ALL |
| | "TH" UNITS: PRIMARY LEVEL TO BE COVERED |
| | PER FHA DESIGN MANUAL. SHOW THE FLOOR |
| | PLAN FOR EACH TYPE OF "TH" UNIT WITH |
| | CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43 |
| | & 7.47. ALSO SHOW MAX HIEGHT FOR LAV AT |
| | 34" REQUIRED ON PAGE 7.52 FHA DESIGN |
| | MANUAL. |
| | 10. SHTS A-803 THRU A-807A INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT - |
| | BATHROOM AS REQUIRED ON PAGES 7.34 & |
| | 7.44 OF THE FHA DESIGN MANUAL. |
| | 11. SUBMIT A FINISH SCHEDULE FOR PUBLIC |
| | - COMMON USE TOILET FACILITIES ON THE |
| | THIRD FLOOR. SECTIONS 1204.2 & 104.2.1. |
| | 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS |
| | P2.6.1, P2.6.2, P2.7.1, P2.7.2, P2.8.1, |
| | P2.8.2, & P3.6.1 SHOWN ON THE INDEX HAVE |
| | |
| | NOT BEEN SUBMITTED. - P1.1 NOT SHOWN ON |
| | THE INDEX. P5.1.5 & P5.1.6 DO NOT |
| | REFLECT THE INDEX SHEETS. - SHTS P5.1.4, |
| | P5.1.5, & P6.1.4 HAVE BEEN SUBMITTED BUT |
| | ARE NOT ON THE PLUMBING SHEET INDEX. - |
| | SHT P5.1.3 ARE SANT. RISERS, BUT ARE |
| | INDICATED AS STORM. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 13. ALL PLUMBING SHEETS: INDICATE RISER |
| | NUMBER FOR EACH SYSTEM THROUGH ALL |
| | FLOORS IN ORDER TO TRACE RISERS THROUGH |
| | BUILDING. SECTION 104.2.1. |
| | 14. SHT P2.1.1 SD UP RISER NEXT TO 4" |
| | SAN DOWN (70DFU) SHOWS NO PIPING TO |
| | BUILDING DRAIN. SECTION 104.2.1. |
| | 15. P2.1.2 FLOOR DRAINS IN THE TRASH |
| | ROOM/AREA AND IN THE CORRIDOR SHALL BE |
| | VENTED. SECTION 901.2.1. - 3/4" |
| | CONDENSATE UP NOT SHOWN ON THE FLOOR |
| | ABOVE. - SANT. UP NOT SHOWN ON THE |
| | FLOOR ABOVE. (S.W. CORNER). - RISERS |
| | STATE "DOWN" BUT PLUMBING LEGEND SHOWS |
| | "UP". (THIS IS ALSO SHOWN ON SHT P2.1.2) |
| | PLEASE CLARIFY SECTION 104.2.1. |
| | 16. SHT P2.2.2 SANT. RISERS #24 & #26 |
| | ARE NOT SHOWN ON FLOOR PLAN. - TWO SETS |
| | OF STORM RISERS SHOWN ON THE FLOOR PLAN |
| | WERE NOT SHOWN ON PREVIOUS LEVEL FLOOR |
| | PLAN. - ONE SET OF STORM RISERS SHOWN ON |
| | THE FLOOR PLAN WERE NOT SHOWN ON THE |
| | FOLLOWING LEVEL FLOOR PLAN. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 17. SHT P2.3.1 SHOW THE LOCATION OF ALL |
| | SECONDARY DRAINS REQUIRED BY SECTION |
| | 1107. SUBMIT CALCULATION FOR PRIMARY AND |
| | SECONDARY DRAINS PER 1106 & 1107. SEE |
| | COMMENT NUMBER 8. |
| | 18. RETAIL SPACES ARE SHELL ONLY THIS |
| | PERMIT. SEPARATE PERMITS ARE REQUIRED |
| | FOR THE BUILDOUT FOR THE TENANT SPACES. |
| | THIS IS INFORMATIONAL ONLY. |
| | 19. SHT P2.3.2 INDICATES 1-1/2" CD |
| | RISER, (NEXT TO LOBBY), BUT NOT SHOWN ON |
| | FLOOR PLAN ABOVE. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 20. SHT P2.4.2 CONDENSATE LINE BETWEEN |
| | ROOMS 433 & 407 IS NOT SHOWN. |
| | 21. SHT P2.5.1 INDICATE CONDENSATE PLAN |
| | NOTE NUMBER FOR AHU IN UNIT C-5A(720) - |
| | CONDO UNIT C-2(515) INDICATES PLAN NOTE |
| | #3. PLEASE CLARIFY. SECTION 104.2.1. |
| | 22. SHT P2.5.2 CONDENSATE RISER IN |
| | UNIT C-1(730) INDICATES PLAN NOTE #2. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 23. FIRST SHT P2.5.1 DOES NOT INDICATE A |
| | FLOOR LAVEL, SECOND SHT P2.5.1 SHOW THE |
| | LOCATION FOR ALL VENTS THRU ROOF AND |
| | INDICATE RISER NUMBER FOR EACH. - |
| | SUBMIT CALCULATION FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SEE COMMENT #8. |
| | SECTIONS 1106 & 1107 AND ALL SUBSECTONS. |
| | 24.SECOND SHT P2.5.2 SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS. |
| | SEE COMMENT #8. SECTIONS 1106 & 1107. - |
| | DRAINS FOR CCC UNITS SHALL BE LOCATED |
| | UNDER THE UNITS TO PREVENT TRIPPING |
| | HAZARDS AND TO KEEP STORM WATER FROM |
| | DRAINING INTO THE SANT. SYSTEM. ONE |
| | DRAIN FOR EACH UNIT REQUIRED. CITY CODE |
| | 90-125(5). |
| | 25. SHT P3.1.2 COLD WATER UP TO CHUTE |
| | WASHDOWN REQUIRES BACKFLOW PROTECTION. |
| | INDICATE METHOD OF PROTECTION. SECTION |
| | 608. |
| | 26. PLEASE CHECK SHEET NUMBERS AS THERE |
| | ARE REPEAT NUMBERS. ALSO CHECK THE SHEET |
| | NUMBERS AGAINST THE PLUMBING SHEET INDEX |
| | TO MAKE SURE ALL SHEETS ARE SUBMITTED |
| | AND TO MAKE SURE ALL SHEETS SUBMITTED |
| | ARE ON THE INDEX. SECTION 104.2.1. |
| | 27. SHT P3.3.1 SEPARATE BACKFLOW |
| | PROTECTION REQUIRED FOR POOL FILL LINE. |
| | AN RPZV BACKFLOW IS REQUIRED. SECTION |
| | 608.13.2. |
| | 28. SHEET INDICATING WATER SUPPLY PLAN |
| | 4TH FLOOR-NORTH SECTION MIS-NUMBERED. |
| | PLEASE CLARIFY/CORRELATE WITH PLUMBING |
| | SHEET INDEX. SECTION 104.2.1. |
| | 29. SHT INDICATING WATER SUPPLY PLAN 5TH |
| | FLOOR "SOUTH" SECTION, PREVIOUS SHEETS |
| | WERE DESIGNATED AS "EAST" OR "WEST". |
| | THIS IS ALSO THE THIRD SHEET NUMBERED |
| | P3.4.2. - INDICATE WHAT DESIGNATION WSCB |
| | & WSH ETC STANDS FOR. - NOTE STATES "SEE |
| | UNIT LAYOUTS ON SHEET P4.1". SHT P4.1 |
| | NOT SUBMITTED. SECTION 104.2.1. |
| | 30. SHT P4.1.1INDICATES TWO "TYPICAL |
| | UNIT "C2" FOR THE WATER SUPPLY. ONLY ONE |
| | C2 FLOOR PLAN FOUND. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 31. PLEASE SUBMIT WATER SUPPLY PLANS AND |
| | FLOOR PLANS FOR THE FOLLOWING UNITS: |
| | C-1A, C-2A, C-2B, C-2C, C-2D, C-2E, |
| | C-2F, C-2G, C-2H, C-5A, TH-1A, TH-1B, |
| | TH-1C, TH-1D, TH-2A, TH-2B, TH-2C. |
| | 32. SHT P5.1.1 VENTS ARE REQUIRED ON THE |
| | FLOOR DRAINS IN THE TRASH ROOM/AREA & |
| | CORRIDOR. SECTION 901.2.1. - CLEANOUTS |
| | REQUIRED IN BLDG PLUMBING DRAIN MAXIMUM |
| | 100' SECTION 708.3.2. - DFU'S FOR SOME |
| | RISERS DO NOT RELFECT THE FLOOR PLANS. - |
| | RISER DOES NOT REFLECT THE FLOOR PLAN |
| | WHERE RISER #13 CONNECTS TO THE BUILDING |
| | DRAIN. - INDICATE RISER # FOR VENT |
| | CONNECTION FOR M/B IN UNIT UPSTREAM OF |
| | RISER #12. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 33. CLEANOUTS FOR BUILDING DRAIN SHALL |
| | BE INSTALLED A MAXIMUM OF 100'. SECTION |
| | 708.3.2. - CLEANOUT AT END OF RUN BY |
| | SANT. RISER #8 NOT SHOWN. - BLDG DRAIN |
| | DOES NOT REFLECT THE FLOOR PLAN WHERE |
| | THE DRAIN SPLITS TOWARD RISERS #1 & |
| | RISERS 4 THRU 8. SECTION 104.2.1. |
| | 34. SHTS P5.1.3 THRU P5.1.5, EVERY VENT |
| | STACK SHALL CONNECT TO THE BASE OF THE |
| | DRAINAGE STACK. ALL RISERS WITH VENT |
| | STACKS SHALL COMPLY. SECTION 903.4. |
| | 35. SHT P5.1.3 SANT RISER #2 DOES NOT |
| | REFLECT THE FLOOR PLAN. AN EXTRA LAV IS |
| | SHOWN. SECTION 104.2.1. |
| | 36. SHT P5.1.3 SANT RISER #4 DOES NOT |
| | REFLECT THE FLOOR PLAN. SHOWS A SHOWER, |
| | BUT A TUB IS ON FLOOR PLAN.- A VENT IS |
| | REQUIRED ON LAV IN THE MASTER BATH. |
| | SECTIONS 104.2.1 & 901.2.1. |
| | 37. SHT P5.1.3 SANT RISER #6 DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE RISERS |
| | & BRANCH LINES CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | 38. SHT P5.1.3 SANT. RISER #8 DOES NOT |
| | REFLECT THE FLOOR PLAN FOR 2 BATHROOM |
| | GROUPS ALL FLOORS, AND THE FIRST |
| | BATHROOM GROUP 3RD FLOOR. SECTION |
| | 104.2.1. |
| | 39. SHT P5.1.4 SANT. RISER #9 DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE RISERS |
| | AND BRANCH LINES CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | 40. SHT P5.1.4 SANT. RISER #10 DOES NOT |
| | REFLECT THE FLOOR PLAN AT LAV ARMS BY |
| | JAC2. SECTION 104.2.1. |
| | 41. SHT P5.1.4 SANT. RISER #12 DOES NOT |
| | REFLECT THE FLOOR PLAN AT LAV ARMS BY |
| | JAC2, NOR WHERE THE RISERS & BRANCH |
| | LINES CONNECT TTO THE BUILDING DRAIN. |
| | SECTION 104.2.1. |
| | 42. SHT P5.1.4 SANT. RISER #13 DOES NOT |
| | REFLECT THE FLOOR PLAN. 1ST & 2ND FLOORS |
| | ARE NOT SHOWN ON RISER. SECTION 104.2.1. |
| | 43. SHT P5.1.4 SANT. RISER #14 DOES NOT |
| | REFLECT THE FLOOR PLAN AT LAV ARM NEXT |
| | TO JAC2. SECTION 104.2.1. |
| | 44. SHT P5.1.4 SANT. RISERS #'S 16 & 20 |
| | DRAIN REQUIRED FOR EACH CCC UNIT ON THE |
| | ROOF LOCATED UNDERNEATH THE UNITS TO |
| | PREVENT A TRIPPING HAZARD AND TO PREVENT |
| | STORM WATER FROM ENTERING THE SANT. |
| | SYSTEM. |
| | 45. SHT P5.1.4 SANT RISER #17 BATHROOM |
| | GROUPS DO NOT REFLECT THE FLOOR PLAN 3RD |
| | THRU 7TH FLOORS. SECTION 104.2.1. |
| | 46. SHT P5.1.5 SANT. RISER #18 DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| | 47. SHT P5.1.5 SANT. RISER #21 DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE RISERS |
| | AND BRANCH LINES CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | 48. SHT P5.15 SANT. RISER #22 DOES NOT |
| | REFLECT THE FLOOR PLAN ON THE 1ST FLOOR |
| | AT TH W/C AND LAV. SECTION 104.2.1. |
| | 49. SHT P5.1.5 SANT. RISER #23 DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| | 50. SHTS P5.2.1, P5.2.2 & P5.2.3 - |
| | SECONDARY DRAINS ARE NOT SHOWN FOR THE |
| | POOL DECK LEVEL AS REQUIRED BY SECTION |
| | 1107. DISCHARGE SHALL BE ABOVE GRADE IN |
| | A LOCATION WHICH WOULD NORMALLY BE |
| | OBSERVED BY THE BUILDING OCCUPANTS OR |
| | MAINTENANCE PERSONAL, AND SEPARATE |
| | SYSTEMS ARE REQUIRED FOR PRIMARY AND |
| | SECONDARY DRAINS. SECTION 1107.2- |
| | SIZING OF STORM SYSTEM TO BE CHECKED |
| | AFTER CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS ARE SUBMITTED. |
| | SECTION 1106 & 1107. |
| | 51. SUBMIT STORM BLDG. DRAIN ISOMETRIC |
| | RISER DIAGRAM SHOWING ALL PIPE SIZES, |
| | I.D. ALL RISERS & SHOW SF AS IT |
| | ACCUMULATES IN THE SYSTEM. |
| | 52. SHT P6.1.3 TYPICAL UNIT "C1" WATER |
| | HAMMER ARRESTORS ARE REQUIRED ON ICE |
| | MAKER LINE, AND ON BOTH HOT & COLD LINES |
| | FOR THE W/M & KITCHEN SINK. SECTION |
| | 604.9. |
| | 53. SHT P6.1.3 TYPICAL UNIT "C2" WATER |
| | HAMMER ARRESTOR REQUIRED ON COLD WATER |
| | AT KITCHEN SINK FOR ICE MAKER. SECTION |
| | 604.9. |
| | 54. SHT P6.1.3 TYPICAL UNIT "C3" WATER |
| | HAMMER ARRESTOR REQUIRED ON HOT WATER |
| | AT KITCHEN SINK & FOR ICE MAKER LINE. - |
| | RISER DOES NOT REFLECT THE FLOOR PLAN AT |
| | THE SHOWER IN M/B. SECTIONS 104.2.1 & |
| | 604.9. |
| | 55. SHT P6.1.3 TYPICAL UNIT "TH-1" WATER |
| | HAMMER REQUIRED ON ICE MAKER LINE. |
| | SECTION 604.9. |
| | 56. SHT P6.1.3 SHOWS 2 OTHER "TYPICAL |
| | UNITS C1". THESE DO NOT REFLECT ANY |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 57. SUBMIT WATER ISOMETRICS FOR THE |
| | FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B, |
| | C-2C, C-2D, C-2E, C-2F, C-2G, C-2H, |
| | C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2, |
| | TH-2A, TH-2B, TH-2C. |
| | 58.SHT P6.1.4 GAS PIPING ISOMETRIC: |
| | SUBMIT APPROVED TABLES FOR SIZING PIPE |
| | PER FBC-2001 FUEL GAS CODE. |
| | 59. INFORMATIONAL: PLANS DO NOT APPEAR |
| | TO BE COMPLETE AT THIS TIME. MORE |
| | COMMENTS MAY BE FORTHCOMING UPON NEXT |
| | SUBMITTAL OF PLAN AND DEPENDING UPON |
| | COMMENT RESPONSES. |
| | 60. SUBMIT A DETAIL FOR THE BOILERS. |
| | SHOW ALL PIPING WITH PIPE SIZES, VALVES, |
| | ETC. PIPING SHALL INDICATE THAT ALL |
| | BOILERS SHALL BE DRAWN FROM |
| | SIMULTANEOUSLY. SECTION 104.2.1. |
| | 61. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS APPLICATION FOR |
| | PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGHTS PER FBC-2001 |
| | FUEL GAS. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | L. IF REGULATORS ARE USED, SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE REGULATORS. IF |
| | REGULATORS ARE VENTED, SUBMIT ISOMETRICS |
| | SHOWING SIZE, MATERIAL, AND LOCATION OF |
| | VENT TERMITATIONS. SECTION 104.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |