Plan Review Notes
Plan Review Notes For Permit 05091639
Permit Number 05091639
Review Stop M
Sequence Number 1
Notes
Date Text
2006-01-12 00:00:00PLAN DENIED BLDG. #4
 1)PLEASE MARK DUCT SIZE ON THE PLANS FOR
 FLEX DUCT.
 2) NEED RETURN GRILL SIZE ON THE PLANS
 FOR UNIT C-2 PAGE M4.1.IN THE MASTER
 BEDROOM.
 3) MISSING BATHROOM EXHAUST IN GUEST
 BATHROOM.UNITS C-1 AND C-3 PAGE M4.1
 4) PLEASE REFER TO SECTION 504.6
 DONESTIC DRYERS.(25 FT.RUN)
 5) PLEASE EXPLAIN MECHANICAL PLANS FOR
 LOBBY PAGE M4.4
 6) PLEASE REFER TO TABLE 403.3 2001 FBC
 (M) PRIVIT GARAGE.
 7) PLEASE PROVIDE TYPE OF METRIALS USED
 CONDENSER WATER PIPING ON THE PLANS.
 8) PLEASE REFER TO SECTION 602.2.1
 MATERIALS EXPOSED WITHIN PLENUMS.
 (DOORS ONMECHANICAL CLOSETS MUST BE
 NONCOMBUSTIBLE)
 9) PLEASE SUBMIT MANUFACTURERS
 INSTRUCTIONS ON AHU,CCC,AND RTU WITH
 THE PLANS.
 10)PLEASE REFER TO SECTION 306.1
 CLEARANCE FOR MAINTENANCE AND
 REPLACEMENT.
 11)PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 12)PLEASE INDECATE ON PLANS WITCH RTU IS
 NUMBER TWO.
 13)PLEASE SUBMIT DETAIL ON AHU ON THE
 PLANS.
  
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  
  
  