Plan Review Notes
Plan Review Notes For Permit 05091639
Permit Number 05091639
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-11-30 00:00:00******DENIED******
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED AFTER JAN. 1, 2005.
  
 2) PERMIT APPLICATION INDICATES 117
 UNITS AND SHT A-002 SHOWS 120. PLEASE
 CORRULATE.
  
 3) DO THE TURN AROUNDS MEET THE 50'
 RADIUSREQUIREMENTS OF NFPA 1?
  
 4) PARKING GARAGE TO MEET SEPARATION AND
 ALL OTHER REQUIREMENTS OF FBC AND NFPA
 88A.
  
 5) PLEASE INDICATE TYPE AND QUANTITY OF
 STORAGE PLANNED FOR POOL EQUIPMENT AREA.
  
  
 6) THE LOBBY ENTRANCE DOORS AT END OF
 CORRIDERS APPEAR TO SWING AGAINST THE
 DIRECTION OF TRAVEL.
  
 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 8) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) THE DOORS LEADING FROM POOL AREA TO
 CORRIDOR SWING AGAINST THE DIRECTION OF
 TRAVEL BASED ON OCCUPANT LOAD OF >50.
  
 10) OCCUPANT LOADS SHOWN AT STAIRS AND
 LIVING UNITS DON'T CORRULATE.
  
 11) WILL CARD READING DEVICES IMPACT
 REQUIRED EXITING?
  
 12) PLEASE REVIEW ALL DOOR SWINGS THAT
 SERVE AREAS WITH OCCUPANT LOADS GREATER
 THAN 50.
  
 13) AN ADDRESS IS REQUIRED ON BUILDING
 THAT SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 14) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION OF WALL AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 15) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED TO CAUSE A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 16) EXIT SIGNS ARE MISSING IN CORRIDORS
 ON SHT E-2.3.2
  
 17) EXIT SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100' APART.
  
 18) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 19) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 20) FIRE ALARM TO BE CLASS A, STYLE D OR
 FULLY ADDRESSABLE.
  
 21) PLANS DON'T SHOW SMOKE DETECTORS IN
 CORRIDORS. PLEASE EXPLAIN.
  
 22) ARE AUDIBLE DEVICES PLANNED FOR
 LIVING UNITS?
  
 23) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 24) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION.
  
 25) SEPARATE SHOP DRAWINGS AND PERMITS
 WITH MANUFACTURER SPEC SHEETS REQUIRED
 FOR FIRE PUMP.
  
 26) A 1000 GPM FIRE PUMP IS PROPOSED.
 PLEASE PROVIDE INFORMATION REGARDING THE
 MEETING WITH THE CITY FIRE MARSHAL AND
 WHAT ARRANGEMENT HAS BEEN ACCEPTED BY
 THIS OFFICE. PLEASE PROVIDE TOTAL OF
 WHAT BUILDINGS THE FIRE PUMP WILL
 SUPPLY.
  
 27) FDV'S ON STANDPIPES ARE REQUIRED TO
 BE 2 1/2" TO 1 1/2" REDUCER WITH CHAIN.
  
 28) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH A LOCK AND CHAIN.
  
 29) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 30) PLANS INDICATE THAT THE BUILDING
 HEIGHT IS LESS THAN 75'. THAT WOULD NOT
 MEET THE REQUIREMENTS FOR HIGHRISE.
 PLEASE VERIFY.
  
 31) KNOX BOX WILL BE REQUIRED ON
 BUILDING AT FRONT ENTRANCE.
  
 32) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE BUREAU OF
 FIRE PREVENTION AND COMPLIANCE WITH NFPA
 51B.
  
 33) LOCKING KNOX BOX CAPS REQUIRED ON
 FIRE DEPARTMENT CONNECTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  