| 2005-11-30 00:00:00 | ******DENIED****** |
| | |
| | 1) NFPA 101, 2003 EDITION SHALL BE |
| | REFERENCED AFTER JAN. 1, 2005. |
| | |
| | 2) PERMIT APPLICATION INDICATES 117 |
| | UNITS AND SHT A-002 SHOWS 120. PLEASE |
| | CORRULATE. |
| | |
| | 3) DO THE TURN AROUNDS MEET THE 50' |
| | RADIUSREQUIREMENTS OF NFPA 1? |
| | |
| | 4) PARKING GARAGE TO MEET SEPARATION AND |
| | ALL OTHER REQUIREMENTS OF FBC AND NFPA |
| | 88A. |
| | |
| | 5) PLEASE INDICATE TYPE AND QUANTITY OF |
| | STORAGE PLANNED FOR POOL EQUIPMENT AREA. |
| | |
| | |
| | 6) THE LOBBY ENTRANCE DOORS AT END OF |
| | CORRIDERS APPEAR TO SWING AGAINST THE |
| | DIRECTION OF TRAVEL. |
| | |
| | 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 8) STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 9) THE DOORS LEADING FROM POOL AREA TO |
| | CORRIDOR SWING AGAINST THE DIRECTION OF |
| | TRAVEL BASED ON OCCUPANT LOAD OF >50. |
| | |
| | 10) OCCUPANT LOADS SHOWN AT STAIRS AND |
| | LIVING UNITS DON'T CORRULATE. |
| | |
| | 11) WILL CARD READING DEVICES IMPACT |
| | REQUIRED EXITING? |
| | |
| | 12) PLEASE REVIEW ALL DOOR SWINGS THAT |
| | SERVE AREAS WITH OCCUPANT LOADS GREATER |
| | THAN 50. |
| | |
| | 13) AN ADDRESS IS REQUIRED ON BUILDING |
| | THAT SHALL BE A MINIMUM OF 3" IN HEIGHT |
| | AND CONTRASTING TO BACKGROUND. |
| | |
| | 14) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION OF WALL AND CEILINGS IN |
| | TERMS OF CLASS A,B OR C. |
| | |
| | 15) IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, DUCT SMOKE DETECTORS SHALL |
| | BE WIRED TO CAUSE A GENERAL FIRE ALARM |
| | WHEN ACTIVATED. |
| | |
| | 16) EXIT SIGNS ARE MISSING IN CORRIDORS |
| | ON SHT E-2.3.2 |
| | |
| | 17) EXIT SIGNS TO BE MOUNTED AT |
| | DISTANCES NOT TO EXCEED 100' APART. |
| | |
| | 18) COOLING TOWERS TO COMPLY WITH NFPA |
| | 214. |
| | |
| | 19) FIRE ALARM SYSTEM TO BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | 20) FIRE ALARM TO BE CLASS A, STYLE D OR |
| | FULLY ADDRESSABLE. |
| | |
| | 21) PLANS DON'T SHOW SMOKE DETECTORS IN |
| | CORRIDORS. PLEASE EXPLAIN. |
| | |
| | 22) ARE AUDIBLE DEVICES PLANNED FOR |
| | LIVING UNITS? |
| | |
| | 23) SEPARATE SHOP DRAWINGS AND PERMITS |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. |
| | |
| | 24) FIRE PUMP TO COMPLY WITH NFPA 20, |
| | 2003 EDITION. |
| | |
| | 25) SEPARATE SHOP DRAWINGS AND PERMITS |
| | WITH MANUFACTURER SPEC SHEETS REQUIRED |
| | FOR FIRE PUMP. |
| | |
| | 26) A 1000 GPM FIRE PUMP IS PROPOSED. |
| | PLEASE PROVIDE INFORMATION REGARDING THE |
| | MEETING WITH THE CITY FIRE MARSHAL AND |
| | WHAT ARRANGEMENT HAS BEEN ACCEPTED BY |
| | THIS OFFICE. PLEASE PROVIDE TOTAL OF |
| | WHAT BUILDINGS THE FIRE PUMP WILL |
| | SUPPLY. |
| | |
| | 27) FDV'S ON STANDPIPES ARE REQUIRED TO |
| | BE 2 1/2" TO 1 1/2" REDUCER WITH CHAIN. |
| | |
| | 28) IN ADDITION TO ELECTRONIC SWITCHES, |
| | THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL |
| | BE SECURED WITH A LOCK AND CHAIN. |
| | |
| | 29) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 30) PLANS INDICATE THAT THE BUILDING |
| | HEIGHT IS LESS THAN 75'. THAT WOULD NOT |
| | MEET THE REQUIREMENTS FOR HIGHRISE. |
| | PLEASE VERIFY. |
| | |
| | 31) KNOX BOX WILL BE REQUIRED ON |
| | BUILDING AT FRONT ENTRANCE. |
| | |
| | 32) NO CUTTING OR WELDING OPERATIONS TO |
| | OCCUR WITHOUT APPROVAL OF THE BUREAU OF |
| | FIRE PREVENTION AND COMPLIANCE WITH NFPA |
| | 51B. |
| | |
| | 33) LOCKING KNOX BOX CAPS REQUIRED ON |
| | FIRE DEPARTMENT CONNECTION. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |