| Plan Review Notes For Permit 05091639 |
| Permit Number |
05091639 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-19 00:00:00 | FAILED: | | | | | | 1. PLEASE SUBMIT CALCULATION FOR THE | | | PROPOSED STORM WATER SYS. | | | 2.PLEASE SUBMIT A COPY OF THE SFWMD | | | PERMIT FOR OUR RECORD. | | | 3. PLEASE NOTE THAT A POLLUTION | | | PREVENTION PLAN MUST BE INCLUDED IN | | | CIVIL, SILT FENCE, TURBIDITY BARRIER, | | | ETC. IT MUST BE IN PLACED PRIOR TO ANY | | | CONSTRUCTION ACTIVITIES. | | | 4. A SEPARATE PERMIT AT NO COST FOR ALL | | | THE WORK WITHIN PUBLIC R.O.W FROM PUBLIC | | | UTILITIES AND ENG. IS REQUIRED, CONTACT | | | WINDEL PALMER AT 494-1086, MOT MUST BE | | | PROVIDED AT THE TIME OF APPLICATION. | | | 5. SHEET C-8 SHOWSADDITIONAL WATER | | | CONNECTION FROM EXISTING 10" WM IN HANK | | | ARRON TO THE BUILDING 5, PLEASE VRIFY. | | | 6. SHEET C-8, COULD NOT FIND ANY WATER | | | SUPPLY CONNECTION FOR BUILDING 4, PLEASE | | | VERIFY. | | | 7. A CLEAN OUT FOR EACH SEWER LATERAL | | | MUST BE PROVIDED. | | | 8. PLEASE NOT THAT CIVIL PLAN MUST BE | | | APPROVED FOR ALL THE CONNECTIONS TO THE | | | CITY SERVICES BY THE PUBLIC UTILITIES & | | | ENG. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|