Plan Review Notes
Plan Review Notes For Permit 05091639
Permit Number 05091639
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-20 00:00:00********* UNSAT ************
  
  
 MIZNER LAKES BLDG #4.
  
  
 1)NOTE: PLEASE CORRELATE BLDG PLANS AND
 PERMIT APPLICATION WITH ELECTRICAL
 PLANS. PLEASE SEE BLDG SHEETS INDICATE
 120 UNITS, ALTHOUGH PERMIT APPLICATION
 AND ELECTRICAL PLANS INDICATE 117.
 PLEASE ALSO CORRELATE SQ FT FROM BLDG
 SHEET (A) WITH ELECTRICAL PLANS AS THE
 A/C SQ FT DO NOT SEEM TO MATCH UP.
  
 2)NOTE: PLEASE SEE ALL ARCHITECTUAL
 SHEETS CONTAIN A "RUBBER STAMP" IN LEIU
 OF THE REQUIRED ORIGINAL SIGNATURE FROM
 THE ARCHITECT OF RECORD. FS 481.221
 PLEASE ALSO SEE BLDG REVIEW COMMENTS.
 THIS IS NOT A KAMM CONSULTING COMMENT.
  
 3)NOTE: PLEASE BE SURE ALL ARCHITECTUAL
 AND ELECTRICAL SHEETS CONTAIN REFERENCE
 TO THE 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72, NFPA-20 2002 WITH ANY
 OTHER CODES CURRENTLY IN EFFECT NEEDED.
  
 4)NOTE: PLEASE SEE FP SHEETS AND A
 SHEETS INDICATE A FIRE PUMP AND FIRE
 HOUSE, HOWEVER THERE IS NOT INDICATION
 OF THIS ON ELECTRICAL RISER ETC.
 PLEASE KNOIW, AS PER DISCUSSION WITH
 CHIEF ELECTRICAL INSPECTOR AND FIRE
 MARSHAL'S OFFICE, GENERATOR BACK UP MAY
 BE REQUIRED IF ELECTRIC FIRE PUMP AND
 NOT DIESEL.
 IT WAS ALSO MENTIONED THERE MAY BE ONE
 FOR EACH BLDGOR ONE FOR BOTH?
 PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS
 AND 695 OF NEC.(2002).
  
 5)NOTE: IF AN ELECTRICAL FIRE PUMP IS
 INSTALLED, PLEASE SUBMIT ALL
 SPECS/MANUFACTURES CUT SHEETS FOR PUMP,
 FIRE PUMP CONTROLLER, GENERATOR AND ANY
 SUB-BASE FUEL TANKS.
 PLEASE BE SURE ALL SPECS/CUT SHEETS
 CONTAIN A LISTING FROM A NRTL.
  
 6)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL EGRESS PATHS,
 CORRIDORS, GARAGES, STAIRS TOWERS.
 PLEASE SEE 101, 7.8 WHICH REQUIRES A MIN
 OF 10 FT CANDLES UNDER NORMAL POWER AND
 1 FT CANDLE MIN UNDER EMERGENCY POWER OR
 BATTERY BACK UP.
  
 7)NOTE: PLEASE KNOW, A MIN BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN MAIN ELECTRICAL RM,
 ELECTRICAL RMS, FIRE PUMP RM/HOUSE,
 ELEVATOR EQUIPMENT RMS.
 700.16,7.8,7.9 ETC.
  
 8)NOTE:PLEASE SEE 620.23 WHICH ALSO
 REQUIRESDEDICATED BRANCH CIRCUIT(S)
 FOR RECEPT IN ELEVATOR MACHINE ROOM.
  
 9)NOTE: PLEASEIDENTIFY THE FIXTURE
 TYPES IN STAIR TOWERS. PLEASE LABEL.
  
 10)NOTE: PLEASE PROVIDE DETAIL FOR
 DISCONNECT(S) FOR ROOF TOP UNITS.
 440.11, MAY BE A "TYPICAL" DETAIL FOR
 CU'S.
  
 11)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS, INCLUDING ALL COMMON AREAS ,
 PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING.
 MOST ARE ON PLANS SOME ARE
 MISSING. SEE SOME REDLINED.
  
 12)NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS. NEED TO
 VERIFY FOR CIRCUITING OF DINING AREAS
 ETC.
  
 13)NOTE: PLEASE SEE 210.52B1 WHICH
 REQUIRES RECEPTS IN DINING AREAS/ROOMS T
 BE ON THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE LIGHTING ETC MAY
 NOT BE ON THESE CIRCUITS. THIS WOULD
 ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS.
  
 14)NOTE: PLEASE SEE SOME UNITS WHICH
 INDICATE "J-BOX" FOR HABITABLE
 RMS/EGRESS PATHS WILL BE REQUIRED TO
 CONTAIN SOME SORT OF LIGHT FIXTURE TO
 MEET 210.70, LS101 7.8
 PLEASE SEE REDLINED PLANS.
  
 15)NOTE: PLEASE BE SURE FIXTURE SCHEDULE
 CORRELATE WITH PLANS AND "LABELING" OF
 SOME SORT ALSO CORRELATES.
  
 16)NOTE: PLEASE SEE NFPA-72 11.5.1.1
 WHICH REQUIRES ALL SMOKE DETECTORS TO BE
 WIRED "INLINE", HOWVER PLEASE SEE
 REDLINED PLANS WHERE SD'S IN THE SAME
 UNITS ARE ON MORE THAN ONE CIRCUIT.
  
 17)NOTE: PLEASE CORRELATE ALL CIRCUITING
 OF SD'S ON PLANS WITH PANEL SCHEDULES.
 PLEASE SEE THERE ARE MANY SD'S SHOWN ON
 DIFFERENT CIRCUITS OTHE THAN WHAT IS
 LISTED ON PANEL SCHEDULE.
  
 18)NOTE: PLEASE SEE MANY SD'S WHICH DO
 NOT INDICATE THE REQUIRED ARC FAULT
 PROTECTION AS MANY OTHERS ARE SHOWN.
 MAY ALSO INDICATE LISTING OF REQUIRED
 ARC FAULT CIRCUITS IN PANEL SCHEDULES.
 210.12, 2002 NEC.
  
 19)NOTE: PLEASE SEE 210.11C, 220.16B
 WHICH REQUIRES A MIN OF 1.5KW FOR
 LAUNDRY/WASHER CIRCUITS.
 PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME
 SHOWN WITHOUT LOADS.
  
 20)NOTE: PLEASE SEE ONLY ONE UNIT PANEL
 SCHEDULE CONTAINS THE "**" AT LOAD
 LOCATIONS.(REDLINED)
  
 21)NOTE: PLEASE CORRELATE ALL SQ FT
 CALCULATIONS ON ELECTRICAL PLANS WITH
 "A" SHEETS WHICH DOES NOT CORRELATE WITH ELECTRICAL SQ
 FT.
  
 22)NOTE: PLEASE MOVE MANY SD'S INTO
 BEDRM AREAS. PLEASE SEE MANY UNITS SEEM
 TO INDICATE SOME SORT OF CEILING HEIGHT
 CHANGE LINE.
 PLEASE SEE NFPA-72 11.8.3.5 WHICH
 REQUIRES ALL SD;S TO BE LOCATED WITHIN
 12" OF A FLAT CEILING, AND WITHIN 3' OF
 THE PEAK OF A SLOPED CEILING.
 PLEASE ADJUST LOCATIONS.
 PLEASE SEE REDLINED PLANS. C3,C4 ETC
  
 23)NOTE: PLEASE SEE PANEL SCHEDULES NOTE
 SD'S AND KITCHEN LTS, HOWEVER MANY UNITS
 SHOWS SD'S TO OTHER BEDRM CIRCUITS.
 PLEASE ALSO SEE PREVIOUS NOTE LISTED
 ABOVE WITH RESPECT TOARC FAULT AND
 CIRCUIITNG.
  
 24)NOTE: PLEASE SEE LOCATIONS ON PLANS
 FOR MISSING RECEPTS PER 210.52, DINING
 RM WALL C-2, RAIL AREAS,WALLS BY STAIRS
 ETC.SEE OTHERS REDLINED.
  
 25)NOTE: PLEASE INDICATE THE REQUIRED
 GFI PROTECTION FOR JACUZZI TUB, RECEPT/BRKR.680.71
  
 26)NOTE: PLEASE IDENTIFY THE PANELS IF
 THEY ARE "TYPICAL" FOR MULTIPLE UNIT
 TYPES, (A,B, C ETC).
  
 27)NOTE: PLEASE SEE SOME CIRCUITING
 MISSING ON PLANS FOR BATH ETC C-5
  
 28)NOTE: PLEASE SEE 210.70 FOR MIN LT
 REQUIRED FOR A/C CLOSETS.
  
 29)NOTE: PLEASE SEE CLOTHES CLOSET FOR
 MIN CLEARENCE REQUIRED FOR LT
 FIXTURE(S).
 410.8, SEE REDLINED.
  
 30)NOTE: PLEASE SEE POSSIBLE MISSING
 RECEPT FOR KITCHEN COUNTERSPACE PER
 210.52C1, C-4
  
 31)NOTE: PLEASE VERIFY TYOE OF CONTROLS
 LABLED AS FUTURE FOR J-BOX RIGHT ON THE
 EDGE OF THE JACUZZI???
 PLEASE SEE 680 FOR MIN CLEARENCES FOR
 ANY PROPOSED DEVICES.
  
 32)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH GFI RECEPT(S) REQUIRED. TH3 ETC
  
 33)NOTE: PLEASE SEE 210.11C3 WHICH ONLY
 PERMITS TWO WAYS OF CIRCUITING FOR
 DEDICATED BATH CIRCUIT(S).
 PLEASE SEE PLANS INDICATE MORE THAN ONE
 BATH ON THE SAME CIRCUIT.
 TH3 ETC, PLEASE ADJUST ANY OTHERS AS
 NEEDED.
  
 34)NOTE: PLEASE PROVIDE MIN CURB DETAIL
 FOR THROUGH FLOOR PENETRATIONS.368.6
 FOR BUS-DUCT RISER.
  
 35)NOTE: PLEASE SEE MANY A/C HEAT LOADS
 ARE SHOWN AS "0"??
 PLEASE ALSO SEE OTHERS WHICH INDICATE
 65% OF 4KW AS 20KW? PLEASE RE-FIGURE
 LOADS FOR A/C'S AND PLEASE ADJUST PANELS
 AND LOAD CALCULATIONS.
  
 36)NOTE: PLEASE PLACE NOTE ON "ROOF TOP"
 PLANS WHICH WILL BE WORDED TO MENTION:
 ANY PROPOSED LIGHTNING PROTECTION
 SYSTEM, SHALL BE INSTALLEDPER
 NFPA-780" OR WORDS TO THAT AFFECT.
  
 37)NOTE: PLEASE VERIFY FEEDER CONDUCTOR
 TYPES FOR UNITS. COPPER, ALUMINUM.
  
 38)NOTE: PLEASE VERIFY WHY MSB AND SBA
 BOTH INDICATE GFP PROTECTION, WHEN
 240.13, 230.95 ETC DOES NOT SEEM TO
 TRIGGER THE REQUIREMENT. THIS IS NOT A
 CODE COMPLIANCE VIOLATION AND MAY BE
 DONE, IT IS ONLY NOTED, AS IF THIS IS
 SHOWN ON PLANS, THEN THIS WILL BE
 REQUIRED.
  
 39)NOTE: PLEASE SEE 200A OPC FROM MSB TO
 PANEL L1HB WHICH IS SHOWN AS A 125A
 PANEL.
  
 40)NOTE: PLEASE VERIFY MSB SCHEDULE
 INDICATES A "HOUSE PUMP" ON MSB-8,
 HOWEVER RISER DIAGRAM DOES NOT CORRELATE
 WITH THIS?
  
 41) NOTE:PLEASE VERIFY THE LAUNDRY
 CIRCUIT ON KITCHEN WALL? TH1
 SHOWN IN WHAT APPEARS TO BE LIVING RM IN
 TH2? PLEASE SEE OTHER LOCATIONS AND
 CORRELATE WITH ACTUAL LOCATIONS OF ANY
 SUCH WASHER/LAUNDRY UNITS.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED AT LOCATIONS OF
 COMMENTS ON ONE SET OF THE PLANS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTSFROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS COMPLETELY AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-19 00:00:00PLANS WILL GO INTO "F" STATUS,
 NOTES TO FOLLOW UPON COMPLETION OF
 REVIEW.
2005-12-15 00:00:00IN ELECTRICAL FOR REVIEW.