| 2005-12-20 00:00:00 | ********* UNSAT ************ |
| | |
| | |
| | MIZNER LAKES BLDG #4. |
| | |
| | |
| | 1)NOTE: PLEASE CORRELATE BLDG PLANS AND |
| | PERMIT APPLICATION WITH ELECTRICAL |
| | PLANS. PLEASE SEE BLDG SHEETS INDICATE |
| | 120 UNITS, ALTHOUGH PERMIT APPLICATION |
| | AND ELECTRICAL PLANS INDICATE 117. |
| | PLEASE ALSO CORRELATE SQ FT FROM BLDG |
| | SHEET (A) WITH ELECTRICAL PLANS AS THE |
| | A/C SQ FT DO NOT SEEM TO MATCH UP. |
| | |
| | 2)NOTE: PLEASE SEE ALL ARCHITECTUAL |
| | SHEETS CONTAIN A "RUBBER STAMP" IN LEIU |
| | OF THE REQUIRED ORIGINAL SIGNATURE FROM |
| | THE ARCHITECT OF RECORD. FS 481.221 |
| | PLEASE ALSO SEE BLDG REVIEW COMMENTS. |
| | THIS IS NOT A KAMM CONSULTING COMMENT. |
| | |
| | 3)NOTE: PLEASE BE SURE ALL ARCHITECTUAL |
| | AND ELECTRICAL SHEETS CONTAIN REFERENCE |
| | TO THE 2002 NFPA-70, 2003 NFPA-101, |
| | 2002 NFPA-72, NFPA-20 2002 WITH ANY |
| | OTHER CODES CURRENTLY IN EFFECT NEEDED. |
| | |
| | 4)NOTE: PLEASE SEE FP SHEETS AND A |
| | SHEETS INDICATE A FIRE PUMP AND FIRE |
| | HOUSE, HOWEVER THERE IS NOT INDICATION |
| | OF THIS ON ELECTRICAL RISER ETC. |
| | PLEASE KNOIW, AS PER DISCUSSION WITH |
| | CHIEF ELECTRICAL INSPECTOR AND FIRE |
| | MARSHAL'S OFFICE, GENERATOR BACK UP MAY |
| | BE REQUIRED IF ELECTRIC FIRE PUMP AND |
| | NOT DIESEL. |
| | IT WAS ALSO MENTIONED THERE MAY BE ONE |
| | FOR EACH BLDGOR ONE FOR BOTH? |
| | PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS |
| | AND 695 OF NEC.(2002). |
| | |
| | 5)NOTE: IF AN ELECTRICAL FIRE PUMP IS |
| | INSTALLED, PLEASE SUBMIT ALL |
| | SPECS/MANUFACTURES CUT SHEETS FOR PUMP, |
| | FIRE PUMP CONTROLLER, GENERATOR AND ANY |
| | SUB-BASE FUEL TANKS. |
| | PLEASE BE SURE ALL SPECS/CUT SHEETS |
| | CONTAIN A LISTING FROM A NRTL. |
| | |
| | 6)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTOMETRICS FOR ALL EGRESS PATHS, |
| | CORRIDORS, GARAGES, STAIRS TOWERS. |
| | PLEASE SEE 101, 7.8 WHICH REQUIRES A MIN |
| | OF 10 FT CANDLES UNDER NORMAL POWER AND |
| | 1 FT CANDLE MIN UNDER EMERGENCY POWER OR |
| | BATTERY BACK UP. |
| | |
| | 7)NOTE: PLEASE KNOW, A MIN BATTERY BACK |
| | UP FIXTURE OF SOME TYPE WILL ALSO BE |
| | REQUIRED IN MAIN ELECTRICAL RM, |
| | ELECTRICAL RMS, FIRE PUMP RM/HOUSE, |
| | ELEVATOR EQUIPMENT RMS. |
| | 700.16,7.8,7.9 ETC. |
| | |
| | 8)NOTE:PLEASE SEE 620.23 WHICH ALSO |
| | REQUIRESDEDICATED BRANCH CIRCUIT(S) |
| | FOR RECEPT IN ELEVATOR MACHINE ROOM. |
| | |
| | 9)NOTE: PLEASEIDENTIFY THE FIXTURE |
| | TYPES IN STAIR TOWERS. PLEASE LABEL. |
| | |
| | 10)NOTE: PLEASE PROVIDE DETAIL FOR |
| | DISCONNECT(S) FOR ROOF TOP UNITS. |
| | 440.11, MAY BE A "TYPICAL" DETAIL FOR |
| | CU'S. |
| | |
| | 11)NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS, INCLUDING ALL COMMON AREAS , |
| | PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING. |
| | MOST ARE ON PLANS SOME ARE |
| | MISSING. SEE SOME REDLINED. |
| | |
| | 12)NOTE: PLEASE PROVIDE ALL AREA AND |
| | ROOM DESIGNATIONS ON PLANS. NEED TO |
| | VERIFY FOR CIRCUITING OF DINING AREAS |
| | ETC. |
| | |
| | 13)NOTE: PLEASE SEE 210.52B1 WHICH |
| | REQUIRES RECEPTS IN DINING AREAS/ROOMS T |
| | BE ON THE ONE OR MORE SMALL APPLIANCE |
| | CIRCUITS. PLEASE SEE LIGHTING ETC MAY |
| | NOT BE ON THESE CIRCUITS. THIS WOULD |
| | ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS. |
| | |
| | 14)NOTE: PLEASE SEE SOME UNITS WHICH |
| | INDICATE "J-BOX" FOR HABITABLE |
| | RMS/EGRESS PATHS WILL BE REQUIRED TO |
| | CONTAIN SOME SORT OF LIGHT FIXTURE TO |
| | MEET 210.70, LS101 7.8 |
| | PLEASE SEE REDLINED PLANS. |
| | |
| | 15)NOTE: PLEASE BE SURE FIXTURE SCHEDULE |
| | CORRELATE WITH PLANS AND "LABELING" OF |
| | SOME SORT ALSO CORRELATES. |
| | |
| | 16)NOTE: PLEASE SEE NFPA-72 11.5.1.1 |
| | WHICH REQUIRES ALL SMOKE DETECTORS TO BE |
| | WIRED "INLINE", HOWVER PLEASE SEE |
| | REDLINED PLANS WHERE SD'S IN THE SAME |
| | UNITS ARE ON MORE THAN ONE CIRCUIT. |
| | |
| | 17)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | OF SD'S ON PLANS WITH PANEL SCHEDULES. |
| | PLEASE SEE THERE ARE MANY SD'S SHOWN ON |
| | DIFFERENT CIRCUITS OTHE THAN WHAT IS |
| | LISTED ON PANEL SCHEDULE. |
| | |
| | 18)NOTE: PLEASE SEE MANY SD'S WHICH DO |
| | NOT INDICATE THE REQUIRED ARC FAULT |
| | PROTECTION AS MANY OTHERS ARE SHOWN. |
| | MAY ALSO INDICATE LISTING OF REQUIRED |
| | ARC FAULT CIRCUITS IN PANEL SCHEDULES. |
| | 210.12, 2002 NEC. |
| | |
| | 19)NOTE: PLEASE SEE 210.11C, 220.16B |
| | WHICH REQUIRES A MIN OF 1.5KW FOR |
| | LAUNDRY/WASHER CIRCUITS. |
| | PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME |
| | SHOWN WITHOUT LOADS. |
| | |
| | 20)NOTE: PLEASE SEE ONLY ONE UNIT PANEL |
| | SCHEDULE CONTAINS THE "**" AT LOAD |
| | LOCATIONS.(REDLINED) |
| | |
| | 21)NOTE: PLEASE CORRELATE ALL SQ FT |
| | CALCULATIONS ON ELECTRICAL PLANS WITH |
| | "A" SHEETS WHICH DOES NOT CORRELATE WITH ELECTRICAL SQ |
| | FT. |
| | |
| | 22)NOTE: PLEASE MOVE MANY SD'S INTO |
| | BEDRM AREAS. PLEASE SEE MANY UNITS SEEM |
| | TO INDICATE SOME SORT OF CEILING HEIGHT |
| | CHANGE LINE. |
| | PLEASE SEE NFPA-72 11.8.3.5 WHICH |
| | REQUIRES ALL SD;S TO BE LOCATED WITHIN |
| | 12" OF A FLAT CEILING, AND WITHIN 3' OF |
| | THE PEAK OF A SLOPED CEILING. |
| | PLEASE ADJUST LOCATIONS. |
| | PLEASE SEE REDLINED PLANS. C3,C4 ETC |
| | |
| | 23)NOTE: PLEASE SEE PANEL SCHEDULES NOTE |
| | SD'S AND KITCHEN LTS, HOWEVER MANY UNITS |
| | SHOWS SD'S TO OTHER BEDRM CIRCUITS. |
| | PLEASE ALSO SEE PREVIOUS NOTE LISTED |
| | ABOVE WITH RESPECT TOARC FAULT AND |
| | CIRCUIITNG. |
| | |
| | 24)NOTE: PLEASE SEE LOCATIONS ON PLANS |
| | FOR MISSING RECEPTS PER 210.52, DINING |
| | RM WALL C-2, RAIL AREAS,WALLS BY STAIRS |
| | ETC.SEE OTHERS REDLINED. |
| | |
| | 25)NOTE: PLEASE INDICATE THE REQUIRED |
| | GFI PROTECTION FOR JACUZZI TUB, RECEPT/BRKR.680.71 |
| | |
| | 26)NOTE: PLEASE IDENTIFY THE PANELS IF |
| | THEY ARE "TYPICAL" FOR MULTIPLE UNIT |
| | TYPES, (A,B, C ETC). |
| | |
| | 27)NOTE: PLEASE SEE SOME CIRCUITING |
| | MISSING ON PLANS FOR BATH ETC C-5 |
| | |
| | 28)NOTE: PLEASE SEE 210.70 FOR MIN LT |
| | REQUIRED FOR A/C CLOSETS. |
| | |
| | 29)NOTE: PLEASE SEE CLOTHES CLOSET FOR |
| | MIN CLEARENCE REQUIRED FOR LT |
| | FIXTURE(S). |
| | 410.8, SEE REDLINED. |
| | |
| | 30)NOTE: PLEASE SEE POSSIBLE MISSING |
| | RECEPT FOR KITCHEN COUNTERSPACE PER |
| | 210.52C1, C-4 |
| | |
| | 31)NOTE: PLEASE VERIFY TYOE OF CONTROLS |
| | LABLED AS FUTURE FOR J-BOX RIGHT ON THE |
| | EDGE OF THE JACUZZI??? |
| | PLEASE SEE 680 FOR MIN CLEARENCES FOR |
| | ANY PROPOSED DEVICES. |
| | |
| | 32)NOTE: PLEASE SEE 210.52D FOR MISSING |
| | BATH GFI RECEPT(S) REQUIRED. TH3 ETC |
| | |
| | 33)NOTE: PLEASE SEE 210.11C3 WHICH ONLY |
| | PERMITS TWO WAYS OF CIRCUITING FOR |
| | DEDICATED BATH CIRCUIT(S). |
| | PLEASE SEE PLANS INDICATE MORE THAN ONE |
| | BATH ON THE SAME CIRCUIT. |
| | TH3 ETC, PLEASE ADJUST ANY OTHERS AS |
| | NEEDED. |
| | |
| | 34)NOTE: PLEASE PROVIDE MIN CURB DETAIL |
| | FOR THROUGH FLOOR PENETRATIONS.368.6 |
| | FOR BUS-DUCT RISER. |
| | |
| | 35)NOTE: PLEASE SEE MANY A/C HEAT LOADS |
| | ARE SHOWN AS "0"?? |
| | PLEASE ALSO SEE OTHERS WHICH INDICATE |
| | 65% OF 4KW AS 20KW? PLEASE RE-FIGURE |
| | LOADS FOR A/C'S AND PLEASE ADJUST PANELS |
| | AND LOAD CALCULATIONS. |
| | |
| | 36)NOTE: PLEASE PLACE NOTE ON "ROOF TOP" |
| | PLANS WHICH WILL BE WORDED TO MENTION: |
| | ANY PROPOSED LIGHTNING PROTECTION |
| | SYSTEM, SHALL BE INSTALLEDPER |
| | NFPA-780" OR WORDS TO THAT AFFECT. |
| | |
| | 37)NOTE: PLEASE VERIFY FEEDER CONDUCTOR |
| | TYPES FOR UNITS. COPPER, ALUMINUM. |
| | |
| | 38)NOTE: PLEASE VERIFY WHY MSB AND SBA |
| | BOTH INDICATE GFP PROTECTION, WHEN |
| | 240.13, 230.95 ETC DOES NOT SEEM TO |
| | TRIGGER THE REQUIREMENT. THIS IS NOT A |
| | CODE COMPLIANCE VIOLATION AND MAY BE |
| | DONE, IT IS ONLY NOTED, AS IF THIS IS |
| | SHOWN ON PLANS, THEN THIS WILL BE |
| | REQUIRED. |
| | |
| | 39)NOTE: PLEASE SEE 200A OPC FROM MSB TO |
| | PANEL L1HB WHICH IS SHOWN AS A 125A |
| | PANEL. |
| | |
| | 40)NOTE: PLEASE VERIFY MSB SCHEDULE |
| | INDICATES A "HOUSE PUMP" ON MSB-8, |
| | HOWEVER RISER DIAGRAM DOES NOT CORRELATE |
| | WITH THIS? |
| | |
| | 41) NOTE:PLEASE VERIFY THE LAUNDRY |
| | CIRCUIT ON KITCHEN WALL? TH1 |
| | SHOWN IN WHAT APPEARS TO BE LIVING RM IN |
| | TH2? PLEASE SEE OTHER LOCATIONS AND |
| | CORRELATE WITH ACTUAL LOCATIONS OF ANY |
| | SUCH WASHER/LAUNDRY UNITS. |
| | |
| | ** PLEASE SEE MANY OF THE ABOVE ITEMS |
| | HAVE BEEN REDLINED AT LOCATIONS OF |
| | COMMENTS ON ONE SET OF THE PLANS |
| | SUBMITTED. |
| | |
| | **PLEASE SEE ANY POSSIBLE COMMENTSFROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS COMPLETELY AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONE SET OF ALL |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-12-19 00:00:00 | PLANS WILL GO INTO "F" STATUS, |
| | NOTES TO FOLLOW UPON COMPLETION OF |
| | REVIEW. |
| 2005-12-15 00:00:00 | IN ELECTRICAL FOR REVIEW. |