| Plan Review Notes For Permit 05091636 |
| Permit Number |
05091636 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-08 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHT A0.01 CODE INFORMATION: CODE | | | REFERENCE SHALL BE FBC-2004 AS PLANS | | | WERE NOT SUBMITTED FOR APPLICATION PRIOR | | | TO 10-1-05. | | | 2. ALL ARCHITECTURAL SHEETS SHALL SHOW | | | THE FIRM LICENSE NUMBER IN THE TITLE | | | BLOCK AND THE PRINTED NAME OF THE PERSON | | | SEALING THE DOCUMENT. ALSO THE SEAL | | | SHALL HAVE THE SIGNATURE AND THE DATE | | | SEAL WAS AFFIXED TO THE DOCUMENT. NO | | | DATE ON SEAL. FAC 61G1-16.004(2)(5)(6) | | | AND FS 481.219 - 481.2055 | | | 3. SHT P0.1 DOMESTIC WATER ISOMETRIC, | | | THE WATER HAMMER ARRESTORS SHALL BE | | | LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | | SHOWN. PDI-WH 201 AND MANUF. INSTALL. | | | INSTRUCTIONS. (SEE PLUMBING NOTE #13). - | | | THERMAL EXPANSION CONTROL MAY BE | | | REQUIRED ON THE WATER HEATER. | | | 4. SHT P0.1 PLUMBING NOTES #1 SHALL READ | | | FBC-2004 NOT 2001 AS SHOWN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|