Plan Review Notes
Plan Review Notes For Permit 05091636
Permit Number 05091636
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-17 00:00:00************* UNSAT *****************
  
 **************************************
  
 PLEASE KNOW, PLANS WERE ONLY SUBMITTED
 FOR "PLAN REVIEW" BEFORE THE OCTOBER
 1ST, 2005. THEDEADLINE FOR THE CODE
 CHANGE TO THE 2004 FBC.
 PLEASE KNOW, PLANS WILL BE REQUIRED TO
 BE SUBMITTED FOR PERMIT UNDER THE 2004
 FBC AND MUST GENERATE A NEW PERMIT
 NUMBER.
 THE EXISTING "PROJECT" NUMBER WILL NO
 LONGER BE IN EFFECT.
 *************************************
  
 1)NOTE: PLEASE SEE NOTE ABOVE AND PLEASE
 ADJUST ALL CODES REFERENCED IN PLANS FOR
 THE 2001 FBC.
 PLEASE ALSO KNOW, AS OF JAN 1ST, 2005 ,
 THE STATE ADOPTED THE 2003 LS CODE
 NFPA-101, NFPA-72, IS NOW THE 2002
 EDITION.
 PLEASE SEE ALL OTHER LOCATIONS ON PLANS
 FOR ALL TRADES.
 PLEASE SEE THAT ELECTRICAL PLANS
 REFERENCE THE CURRENT NEC UNDER ADOPTION
 BY THE STATE. (2002).
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. PLEASE SEE FLORIDA ADMINISTRATIVE
 CODE, FAC 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUES FOR
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER REQUIRED.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS CONTAINING THE
 TITLE BLOCKS OF SAID FIRM INCLUSIVE OF
 MEP'S.
 THIS COMMENT IS NOT FOR KAMM CONSULTING
 ENGINEERS.
  
 3)NOTE: PLEASE SEE 2002 NECWHICH
 REQUIRES THE GFI PROTECTION FOR ALL
 15A,20A 120V RECEPTS IN KITCHENS.
 PLEASE SEE CC-18
  
 4)NOTE: PLEASE SEE PANEL "CC2" WHICH
 DOES NOT SEEM TO MEET 110.26 FOR MIN
 CLEARNECE TO THE LEFT AND RIGHT OF PANEL
 WITH WH SHOWN AT LOCATION ON PLANS.
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 215.3,230.42 ETC.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]