2005-11-23 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 STORM SHUTTERS AS REQUIRED BY RULE 9B-72
 OF DCA AS OF OCT. 1ST 2004. SBCCI REPORT
 ALONE IS NOT AUTOMATICALLY AN STATEWIDE
 FLORIDA PRODUCT APPROVAL. SEE WEBSITE
 WWW.FLORIDABUILDING.ORG FOR MORE PRODUCT
 APPROVAL INFO. AND REQUIREMENTS.
  
 2- A) UPDATE INSTALLATION SCHEDULE
 SHEET. SEE ATTACHED COPY.
 B) PROVIDE COMPLETE INFORMATION ON
 INSTALLATION SCHEDULE. EG: DESIGN
 PRESSURES & SPECIFIC ANCHOR TO BE USED.
 C) REVISE INFORMATION WRITTEN ON
 INSTALLATION SCHEDULE FORM. SEE CORRECT
 SBCCI REPORT. USE UPDATED FORM. IT
 SHOULD SAY FLORIDA PRODUCT APPROVAL #.
  
 3- ANCHOR SCHEDULE ON SHEET 5 OF 8 OF
 STORM PANELS: CIRCLE ONLY THE INFO. THAT
 APPLIES TO THIS PROJECT. ALSO, CIRCLE
 ANCHOR TYPE AND SPACING ACCORDING TO THE
 CORRECT DESIGN PRESSURES.
  
 4- STORM PANELS WHICH ARE 115" AND 117"
 LONG EXCEED THE MAXIMUM PANEL SPAN
 ACCORDING TO TABLE 1 ON SHEET 6 OF 8 OF
 STORM PANELS.REVISE AS REQUIRED.
  