Text |
| 2005-11-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 |
| | AND P-3.2.4 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASH MACHINES OF ALL |
| | UNITS. PER SECTION 604.9. - ALL WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE", |
| | NOT IN THE CEILING AS SHOWN IN SOME |
| | CASES. PDI-WH 201 AND MANUF INSTALLATION |
| | INSTRUCTIONS. |
| | 2. IF INDIVIDUAL METERS NO BACKFLOW |
| | DEVISE IS REQUIRED, BUT IF SINGLE METER |
| | AN RPZV BACKFLOW WILL BE REQUIRED ON THE |
| | WATER SERVICE. PLEASE CLARIFY. SECTION |
| | 608.13.2. |
| | 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR |
| | UNIT B. RISER DOES NOT REFLECT THE FLOOR |
| | PLAN, AND AS SHOWN, KITCHEN SINK ARMS |
| | ARE RUNNING IN FRONT OF THE RANGE ABOVE |
| | THE FLOOR. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2 |
| | AND P-3.2.4 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASH MACHINES OF ALL |
| | UNITS. PER SECTION 604.9. - ALL WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE", |
| | NOT IN THE CEILING AS SHOWN IN SOME |
| | CASES. PDI-WH 201 AND MANUF INSTALLATION |
| | INSTRUCTIONS. |
| | 2. IF INDIVIDUAL METERS NO BACKFLOW |
| | DEVISE IS REQUIRED, BUT IF SINGLE METER |
| | AN RPZV BACKFLOW WILL BE REQUIRED ON THE |
| | WATER SERVICE. PLEASE CLARIFY. SECTION |
| | 608.13.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |