| Date |
Text |
| 2005-11-18 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 2. EXIT STAIRS ARE TO BE KEPT UP |
| | WITH CONSTRUCTION. |
| | |
| | 3. DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. |
| | |
| | 4. TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE |
| | STORIES OR 30 FEET IN HEIGHT. |
| | |
| | 5. WET FIRE HYDRANTS ARE REQUIRED |
| | PRIOR TO, DURING, AND AFTER |
| | CONSTRUCTION. |
| | |
| | 6. TAMPER SWITCHES, CHAIN AND |
| | LOCKS ARE REQUIRED ON FIRE LINE |
| | BACKFLOW DEVICE. |
| | |
| | 7. BUILDING ADDRESS NOT SHOWN |
| | ON ELEVATION. A MINIMUM OF AT LEAST |
| | 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 8. KNOX-BOX WILL BE REQUIRED. |
| | |
| | 9. KNOX-BOX LOCKING CAPS WILL BE |
| | REQUIRED FOR FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | 10. ELEVATOR WARNING SIGNS ARE |
| | REQUIRED. |
| | |
| | 11. STAIRWELL SIGNS ARE REQUIRED. |
| | |
| | 12. TACTILE SIGNAGE REQUIRED. |
| | |
| | 13. PLEASE INDICATE STRETCHER |
| | ACCESSIBLE ELEVATORS. APPROPRIATE |
| | SIGNAGE IS REQUIRED. |
| | |
| | 14. PLEASE EXPLAIN EXIT DISCHARGE. |
| | |
| | 15. PLEASE EXPLAIN GATES TO OPEN |
| | AUTOMATICALLY IN FIRE EMERGENCY. A-2.1. |
| | |
| | 16. PLEASE EXPLAIN VENTILATION DUCTS |
| | RUNNING THRU STAIR STAIR # 1 NOTE ON |
| | PAGE A-2.2. |
| | |
| | 17. EAST EXIT DISCHARGE SHOWN THRU |
| | LOADING DOCK. PLEASE EXPLAIN. |
| | |
| | 18. WHO OWNS THE 14" ALLEY WHERE STAIR |
| | # 2 DISCHARGES. WHAT PREVENTS PEOPLE |
| | FROM GETTING HIT BY VEHICLES. |
| | |
| | 19. HOW IS ACCESS OBTAINED TO STAIR # 1 |
| | ON THE MEZZANINE LEVEL WITH ALL THE |
| | PARKING SPACES ON PAGE A-2.3. |
| | |
| | 20. A TWO HOUR FIRE SEPERATION IS |
| | REQUIRED BETWEEN THE PARKING GARAGE |
| | AND OTHER AREAS OF THE BUILDING. |
| | |
| | 21. TRASH CHUTE TO COMPLY WITH |
| | NFPA 82. |
| | |
| | 22. PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 23. PLEASE INDICATE OCCUPANT LOAD FOR |
| | ROOF TERRACE AREA. |
| | |
| | 24. PLEASE INDICATE OCCUPANT LOAD FOR |
| | POOL LEVEL AND EXPLAIN EXITING. |
| | |
| | 25. PLEASE EXPLAIN EXIT DISCHARGE INTO |
| | GARAGE AREA? |
| | |
| | 26. HANDRAILS ARE REQUIRED ON BOTH |
| | SIDES OF STAIRS. |
| | |
| | 27. VOID AREA UNDER POOL STRUCTURE NOT |
| | TO BE USED FOR STORAGE UNLESS FIRE |
| | SPRINKLER PROTECTED. |
| | |
| | 28. "NO EXIT" SIGNS WILL BE NEEDED ON |
| | DOORS LOCATED NEAR EXITS. |
| | |
| | 29. PLEASE PROVIDE A LIFE SAFETY PLAN |
| | FOR THE BUILDING. |
| | |
| | 30. SURFACES USED FOR EXITING SHALL BE |
| | SLIP RESISTANT. |
| | |
| | 31. BUILDING WILL BE REQUIRED TO MEET |
| | HIGH-RISE REQUIREMENT IF GREATER THAN |
| | 75 FEET IN HEIGHT. |
| | |
| | 32. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 33. GARAGE VENTILATION DUCTS IN STAIR |
| | #1. PLEASE XPLAIN WHAT CODE ALLOWS THIS |
| | TO OCCUR. |
| | |
| | 34. PLEASE PROVIDE FLAME SPREAD FOR |
| | TRASH CHUTE INSULTATION. |
| | |
| | 35. EXIT SIGNS SHALL NOT EXCEED 100 |
| | FEET. |
| | |
| | 36. AN EMERGENCY COMMNAD CENTER SHALL |
| | COMPLY WITH NFPA 1, 2003 EDITION, |
| | SECTION 11-9. PLEASE ILLUSTRATE |
| | COMPLIANCE. |
| | |
| | 37. ITEMS APPEAR TO BE MISSING FROM |
| | COMMAND CENTER. |
| | |
| | 38. EMERGENCY LIGHTING AND STANDBY |
| | POWER SHALL COMPLY WITH APPLICABLE |
| | CODE SECTIONS. |
| | |
| | 39. NO EXIT SIGNS AT THE POOL LEVEL. |
| | |
| | 40. THE SMOKE CONTROL PANEL SHALL |
| | PROVIDE A GRAPHIC REPRESENTATION OF THE |
| | BUILDING. HOA SWITHCES ONLY WILL |
| | NOT BE ACCEPTED. |
| | |
| | 41. FIRE ALARM SYSTEM SHALL BE UL LISTED |
| | FOR CENTRAL STATION SERVICE. FIRE |
| | ALARM SYSTEM SHALL BE CLASS A OR BE |
| | FULLY ADDRESSABLE. |
| | |
| | 42. DUCT DETECTORS SHALL BE CORRECTED |
| | TO THE ALARM. |
| | |
| | 43. HOW ARE REPAIRS HANDLED FOR THE |
| | PUMP ROOM SINCE IT IS LOCATED ON THE |
| | MEZZANINE. |
| | |
| | 44. THE FIRE ALARM SYSTEM SHALL MEET |
| | THE SURVIVABILITY REQUIREMENT. |
| | |
| | 45. HOSE VALVES SHALL BE INSTALLED AT |
| | FLOORS IN THE STAIRWELLS NOT |
| | INTERMEDIATE FLOORS. |
| | |
| | 46. PLEASE EXPLAIN TEST HEADER ON |
| | MEZZANINE LEVEL. |
| | |
| | 47. SEVERAL INCORRECT NOTES IN FIRE |
| | SPRINKLER BOX ON PAGE FP-1.0. |
| | |
| | 48. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE SPRINKLER PLANS. |
| | |
| | 49. NOTES REGARDING FIRE PUMP SIZES |
| | DIFFERS IN SEVERAL LOCATIONS. |
| | |
| | 50. WHERE ARE THE PORTABLE FIRE |
| | EXTINGUISHER LOCATIONS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |