Plan Review Notes
Plan Review Notes For Permit 05091467
Permit Number 05091467
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2005-11-18 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 4. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 5. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 6. TAMPER SWITCHES, CHAIN AND
 LOCKS ARE REQUIRED ON FIRE LINE
 BACKFLOW DEVICE.
  
 7. BUILDING ADDRESS NOT SHOWN
 ON ELEVATION. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 8. KNOX-BOX WILL BE REQUIRED.
  
 9. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR FIRE DEPARTMENT
 CONNECTIONS.
  
 10. ELEVATOR WARNING SIGNS ARE
 REQUIRED.
  
 11. STAIRWELL SIGNS ARE REQUIRED.
  
 12. TACTILE SIGNAGE REQUIRED.
  
 13. PLEASE INDICATE STRETCHER
 ACCESSIBLE ELEVATORS. APPROPRIATE
 SIGNAGE IS REQUIRED.
  
 14. PLEASE EXPLAIN EXIT DISCHARGE.
  
 15. PLEASE EXPLAIN GATES TO OPEN
 AUTOMATICALLY IN FIRE EMERGENCY. A-2.1.
  
 16. PLEASE EXPLAIN VENTILATION DUCTS
 RUNNING THRU STAIR STAIR # 1 NOTE ON
 PAGE A-2.2.
  
 17. EAST EXIT DISCHARGE SHOWN THRU
 LOADING DOCK. PLEASE EXPLAIN.
  
 18. WHO OWNS THE 14" ALLEY WHERE STAIR
 # 2 DISCHARGES. WHAT PREVENTS PEOPLE
 FROM GETTING HIT BY VEHICLES.
  
 19. HOW IS ACCESS OBTAINED TO STAIR # 1
 ON THE MEZZANINE LEVEL WITH ALL THE
 PARKING SPACES ON PAGE A-2.3.
  
 20. A TWO HOUR FIRE SEPERATION IS
 REQUIRED BETWEEN THE PARKING GARAGE
 AND OTHER AREAS OF THE BUILDING.
  
 21. TRASH CHUTE TO COMPLY WITH
 NFPA 82.
  
 22. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 23. PLEASE INDICATE OCCUPANT LOAD FOR
 ROOF TERRACE AREA.
  
 24. PLEASE INDICATE OCCUPANT LOAD FOR
 POOL LEVEL AND EXPLAIN EXITING.
  
 25. PLEASE EXPLAIN EXIT DISCHARGE INTO
 GARAGE AREA?
  
 26. HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF STAIRS.
  
 27. VOID AREA UNDER POOL STRUCTURE NOT
 TO BE USED FOR STORAGE UNLESS FIRE
 SPRINKLER PROTECTED.
  
 28. "NO EXIT" SIGNS WILL BE NEEDED ON
 DOORS LOCATED NEAR EXITS.
  
 29. PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE BUILDING.
  
 30. SURFACES USED FOR EXITING SHALL BE
 SLIP RESISTANT.
  
 31. BUILDING WILL BE REQUIRED TO MEET
 HIGH-RISE REQUIREMENT IF GREATER THAN
 75 FEET IN HEIGHT.
  
 32. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 33. GARAGE VENTILATION DUCTS IN STAIR
 #1. PLEASE XPLAIN WHAT CODE ALLOWS THIS
 TO OCCUR.
  
 34. PLEASE PROVIDE FLAME SPREAD FOR
 TRASH CHUTE INSULTATION.
  
 35. EXIT SIGNS SHALL NOT EXCEED 100
 FEET.
  
 36. AN EMERGENCY COMMNAD CENTER SHALL
 COMPLY WITH NFPA 1, 2003 EDITION,
 SECTION 11-9. PLEASE ILLUSTRATE
 COMPLIANCE.
  
 37. ITEMS APPEAR TO BE MISSING FROM
 COMMAND CENTER.
  
 38. EMERGENCY LIGHTING AND STANDBY
 POWER SHALL COMPLY WITH APPLICABLE
 CODE SECTIONS.
  
 39. NO EXIT SIGNS AT THE POOL LEVEL.
  
 40. THE SMOKE CONTROL PANEL SHALL
 PROVIDE A GRAPHIC REPRESENTATION OF THE
 BUILDING. HOA SWITHCES ONLY WILL
 NOT BE ACCEPTED.
  
 41. FIRE ALARM SYSTEM SHALL BE UL LISTED
 FOR CENTRAL STATION SERVICE. FIRE
 ALARM SYSTEM SHALL BE CLASS A OR BE
 FULLY ADDRESSABLE.
  
 42. DUCT DETECTORS SHALL BE CORRECTED
 TO THE ALARM.
  
 43. HOW ARE REPAIRS HANDLED FOR THE
 PUMP ROOM SINCE IT IS LOCATED ON THE
 MEZZANINE.
  
 44. THE FIRE ALARM SYSTEM SHALL MEET
 THE SURVIVABILITY REQUIREMENT.
  
 45. HOSE VALVES SHALL BE INSTALLED AT
 FLOORS IN THE STAIRWELLS NOT
 INTERMEDIATE FLOORS.
  
 46. PLEASE EXPLAIN TEST HEADER ON
 MEZZANINE LEVEL.
  
 47. SEVERAL INCORRECT NOTES IN FIRE
 SPRINKLER BOX ON PAGE FP-1.0.
  
 48. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER PLANS.
  
 49. NOTES REGARDING FIRE PUMP SIZES
 DIFFERS IN SEVERAL LOCATIONS.
  
 50. WHERE ARE THE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER