Plan Review Notes
Plan Review Notes For Permit 05091467
Permit Number 05091467
Review Stop Z
Sequence Number 1
Notes
Date Text
2006-01-19 00:00:001. THE BUILDING IS SET BACK MORE THAN 5
 FEET FROM THE PREPERTY LINE ALONG
 SAPODILLA AVENUE. A VARIANCE FROM DAC IS
 REQUIRED.
 2. PARKING GARAGE EXHAUST VENTILATION
 CAN NOT BE LOCATED ON THE PLAZA. PLEASE
 RELOCATE.
 3.FIRST FLOOR UNITS ARE EXCEEDING THE
 MAXIMUM FINISHED FLOOR TO FINISHED FLOOR
 HEIGHT ALLOWED. A VARIANCE FROM DAC IS
 REQUIRED.
 4. MANAGER'S ROOM AND BATHROOMS ARE NOT
 ALLOWED AT THE MEZZANNINE LEVEL. ONLY
 MEZZANNINES INSIDE THE UNITS AND NOT
 LIVING SPACES IN THE PARKING AREA ARE
 ALLOWED.
 5. VEHICULAR ENTRIES ARE NOT PERMITTED
 ON PRIMARY STREETS
 6. PLEASE PROVIDE A DIAGRAM SHOWING THE
 AREA COUNTED AS OPEN SPACE. THE 10 FEET
 SIDEWALK REQUIREMENT CANNOT BE COUNTED
 AS PART OF THE OPEN SPACE.
 7. DEAD-END PARKING SHALL HAVE A MINIMUM
 OF 5 FEET BACK UP SPACE.
 8. PLEASE SUBMITT INFORMATION TO CONFIRM
 UNITY OF TITLE.
 9. EXPOSED TIE JOINTS PATTERN FOR THE
 EXPOSED ARCHITECTURAL CONCRETE EYEBROW
 MUST BE ALLIGNED.
 10. PLEASE REVIEW THE PLAZA DESIGN TO
 MAKE IT MOR INVITING FOR THE GENERAL
 PUBLIC AND LESS AS AN ENTRY FOR YOUR
 BUILDING. OPEN SPACE SHALL INCLUDE A
 DRINKING FOUNTAIN.