2005-12-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1. SHT A-G.0 NOT SIGNED, SEALED AND
 DATED AS REQUIRED BY FAC 61G1-16.003 AND
 FS 481.2055.
 2. ALL ARCHITECTURAL SHEETS REQUIRE THE
 PERSONAL SIGNATURE OF THE ARCHITECT.
 PLEASE SUBMIT DRIVERS LICENSE, VOTERS
 REGISTRATION, OR OTHER PROOF OF LEGAL
 SIGNATURE. INITIALS ARE NOT APPROVED. IF
 THAT IS INDEED YOUR LEGAL SIGNATURE,
 SUBMIT A SIGNED, SEALED, DATED, PROPERLY
 NOTERIZED LETTER INDICATING LEGAL
 SIGNATURE FOR OUR FILES.
 3. SHTS PD1, PD2, WS1, WS2, WS3, & WS4 -
 SEAL INFORMATION REQUIRED BY FAC
 61G1-16.001 & .002 AND FS 481.321 IS NOT
 IMPRESSED ON THE PLANS. PLEASE RESEAL
 ALL SHEETS IMPRESSING REQUIRED
 INFORMATION. SIGNATURE IS A PHOTOCOPY
 AND SHALL BE A WET SIGNATURE. THE
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED BY FS 481.319(C) AND FAC
 61G1-16.004(2) SHALL BE ON EACH SHEET.
 4. SHT WS1 INDICATE TYPE OF DRAINAGE FOR
 THE TRENCH DRAIN. IF STORM DRAINAGE, IT
 WILL DRAIN TO STORM SEWER. CITY WPB CODE
 90-125(5).
 5. SHTS A-2.4, A-2.7, A-2.8, A-2.9 AND
 A-2.23. SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW THE SF
 OF EACH AREA WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS, AND
 THE AREA OF ROOFS THAT DRAIN FROM ABOVE
 ON TO THE ROOF AREA IN THE CALCULATIONS.
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS.
 6. INFORMATIONAL - SEPARATE POOL PERMIT
 REQUIRED. PLANS SHALL BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH DEPT. PRIOR TO
 BEING SUBMITTED TO THE CITY FOR REVIEW.
 PLANS SHALL BE STAMPED BY HEALTH DEPT.
 (MINIMUM TWO COPIES).
 7. SHTS A-2.10 THRU A-2.12 & A-2.15 THRU
 A-2.20.5. THE CLEAR FLOOR SPACE
 DIMENSIONS ARE TO BE APPLIED OR
 SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE
 REQUIREMENTS AT THE TOILETS ARE BEING
 MET. SEE PAGE 7.43.
 8. SHTS A-2.15 THRU A-2.20.5. THE 30" X
 48" CLEAR FLOOR SPACE FOR THE SHOWERS
 MUST BE PARALLEL TO THE FIXTURE & FLUSH
 WITH THE CONTROL WALL. SEE PAGE 7.56.
 9. ALL UNITS - SPECIFICATION "A" OR "B"
 SHALL BE INDICATED FOR THE BATHROOMS OF
 EACH UNIT. SEE PAGE 7.35.
 10. SHTS A-2.3 & A-2.25 TOILET ROOMS
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 11. SHT A-2.25 SUBMIT A DETAIL FOR THE
 ACCESSIBLE DRINKING FOUNTAIN. SHOW
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS.
 12. SHT A-4.0 CALLS OUT SHT A-X.X FOR
 DETAILS AND TYPICAL SPECS FOR ALUMINUM
 RAININGS. SHT A-X.X WAS NOT FOUND OR
 INDICATED ON THE INDEX SHEET. PLEASE
 CLARIFY. MORE INFORMATION IS REQUIRED.
 SECTION 104.2.1.
 13. SHT A-7.0 DETAIL #9 INDICATES A 4" X
 10" SCUPPER, BUT SHTS A-2.21 & A-2.22
 SHOW 14" X 6" SCUPPERS. PLEASE CLARIFY
 AND CORRELATE DETAILS AND ROOF PLANS.
 SECTION 104.2.1.
 14. SHT A-8.3 INTERIOR FININSH #032
 INDICATES PAINT ON GREEN BOARD DRYWALL.
 PLEASE INDICATE HOW THIS WILL MEET THE
 REQUIREMENTS OF SECTION 1204.2
 (NONABSORBENT MATERIAL TO A HEIGHT OF
 4FT ABOVE THE FLOORL.
 15. ALL PLUMBING & MECHANICAL SHEETS.
 THE CERTIFICATE OF AUTHROIZATION NUMBER
 IS REQUIRED ON EACH SHEET PER FAC
 61G15-23.002(2) AND FS 471.025.
 16. SHT P-1 THE SAND/OIL INTERCEPTOR
 SHALL BE SIZED BY LYNN MASSON
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT
 HER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. 3434.
 17. P-1 MORE INFORMATION IS REQUIRED FOR
 THE WET-WELL PRECAST CONCRETE BASIN.
 SUBMIT MANUF. SPECIFICATION SHEETS.
 SECTION 104.2.1.2.
 18. THE SAND/OIL INTERCEPTOR SHALL BE
 LOCATED UPSTREAM OF THE PUMP SYSTEM.
 19. SHT P-1 SHOW SF OF ALL RISERS, ALL
 SF AS IT ACCUMULATES IN THE SYSTEM, AND
 ALL PIPE SIZES.
 20. SHT P-1 RISER AT COL. LINE C/3 IS
 NOT SHOWN ON SHT P-2. PLEASE CLARIFY.
 SECTION 104.2.1.
 21. SHT P-2 G.D. AT COL. LINE C/2 NOT
 SHOWN ON SHT P-1. PLEASE CLARIFY.
 SECTION 104.2.1.
 22. SHT P-2 RISER AT COL. LINE E/4 IS
 SHOWN AS 6" 1860SF, BUT ON SHTS P-1 &
 P-3 IT IS SHOWN AS 4" 930SF. PLEASE
 CLARIFY. SECTION 104.2.1.
 23. SHT P-2 4" DOWNSTREAM OF S/2, S/6,
 S/4D SHOWS 4" DN, BUT ENDS AT THAT
 POINT. PLEASE CLARIFY. SECTION 104.2.1.
 24. SHT P-2 12" SD AS IT EXITS THE
 BUILDING STATES "CONNECT CW LINE".
 PLEASE INDICATE WHAT CW MEANS.
 25. SHT P-3 F.D.'S IN TRASH ROOM ARE NOT
 SHOWN ON THE SANT. RISER DIAGRAM.
 SECTION 104.3.1.1.
 26. SHT P-3 RWL #3 SHOWN ON P-3 NOT
 SHOWN ON SHT P-2. PLEASE CLARIFY.
 SECTION 104.2.1.
 27. SHT P-3 AAV SHOWN ON THE COL. LINE C
 BETWEEN COLS. 4 & 5 REQUIRES A RELIEF
 VENT PER SECTION 617.3.2.
 28. SHT P-3 RPZV BACKFLOW SHALL BE
 LOCATED AS CLOSE TO THE METER AS
 POSSIBLE ON PRIVATE PROPERTY. PLEASE
 CONTACT ORVILLE POLK AT THE BACKFLOW
 DEPARTMENT (561) 822-2240 FOR PROPER
 LOCATION OF BACKFLOW PREVENTER.
 29. SHT P-4 MEN'S & WOMEN'S TOILET ROOMS
 AND FLOOR DRAINS IN THE PUMP ROOM ARE
 NOT SHOWN ON THE SANT. RISER DIAGRAMS.
 SECTION 104.3.1.1.
 30. SHT P-4 AAV SHOWN ON COL LINE C
 BETWEEN COLS. 4 & 5 REQUIRE A RELIEF
 VENT PER SECTION 617.3.2.
 31 SHT P-4 SUBMIT MANUF. SPECIFICATIONS
 FOR DOMESTIC WATER BOOSTER PUMPS. PUMPS
 SHALL BE LISTED. SECTION 303.4.
 32. SHT P-5 RWL #1 IS NOT SHOWN ON THE
 FLOOR PLAN BELOW. PLEASE CLARIFY.
 SECTION 104.2.1.
 33. SHT P-5 RISER S/4 AT COL. LINE 3
 WEST OF COL. E.4 IN INDICATED AS RISER
 S/4A ON SHT P-4. PLEASE CLARIFY. SECTION
 104.2.1.
 34. SHT P-5. INDICATE ALL RISER NUMBERS
 AT KITCHEN SINKS. RISERS NOT SHOWN ON
 PREVIOUS FLOOR PLAN SHEET. PLEASE
 CLARIFY. SECTION 104.2.1.
 35. SHT P-6 RISERS FOR KITCHEN SINKS ARE
 NOT SHOWN. PLEASE CLARIFY. SECTION
 104.2.1.
 36. SHT P-7 RISER S/4 SHOWN OFFSETTING
 IN CEILING. SHT P-7 INDICATES 3-6
 LEVELS. IS THIS OFFSET ON EACH FLOOR?
 PLEASE CLARIFY. SECTION 104.2.1.
 37. SHTS P-7 THRU P-11 KITCHEN SINKS
 RISERS ARE NOT SHOWN. PLEASE INDICATE
 THE RISER NUMBER FOR KITCHEN SINKS.
 SECTION 104.2.1.
 38. SHT P-8 OFFSET FOR S/4A AT COL. LINE
 D BETWEEN COLS. 5 & 6 IS NOT SHOWN.
 PLEASE CLARIFY. SECTION 104.2.1.
 39. SHT P-8 RISER S/6 NOT SHOWN ON
 PREVIOUS FLOOR PLAN. (P-6) PLEASE
 CLARIFY. SECTION 104.2.1.
 40. ALL PIPES 3" AND LARGER ARE NOT
 APPROVED IN BLOCK WALLS. SECTION
 1907.3.6.
 41. SHTS P-12 & P-13 SHOW THE LOCATION
 OF ALL VENTS THRU THE ROOF. SECTION
 104.2.1.
 42. SHT P-15 TOILET ROOMS AND SERVICE
 SINK ARE NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 104.3.1.1.
 43. SUBMIT STORM RISER DIAGRAMS IN
 ISOMETRIC FORM. SHOW ALL PIPE SIZES,
 OFFSETS, & INDICATE SF AS IT ACCUMULATES
 IN RISER. SECTION 104.3.1.1.
 44. SUBMIT CONDENSATE RISER DIAGRAMS
 SHOWING ALL PIPE SIZES, OFFSETS ECT.
 45 SUBMIT A CONDENSATE BLDG DRAIN
 ISOMETRIC SHOWING THE LOCATION OF ALL
 CONDENSATE RISERS AND THE TERMINATION
 POINT OF THE CONDENSATE SYSTEM. SECTION
 104.3.1.1.
 46.SHTS P-16 & P-17 IF THERE ARE VENT
 THRU THESE ROOFS, PLEASE SHOW THE
 LOCATION OF EACH. SECTION 104.2.1.
 47. SHT P-18 INDICATES LEVEL 9 & LEVEL
 10. THE BUILDING IS ONLY 8 STORIES HIGH.
 PLEASE CLARIFY. SECTION 104.2.1.
 48. SHT P-18 RISER S/1 DOES NOT REFLECT
 THE FLOOR PLAN. NO TUBS SHOWN. SECTION
 104.2.1. PLEASE CORRELATE RISER & FLOOR
 PLAN.
 49. SHT P-18 RISER S/2 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS KITCHEN
 SINKS AND FLOOR PLAN SHOWS W/M'S. PLEASE
 CORRELATE RISERS & FLOOR PLANS. SECTION
 104.2.1.
 50. SHT P-18 RISER S/2A NOT FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 51. SHT P-18 RISER S/2B NOT LOCATED ON
 THE FLOOR PLAN. UNABLE TO LOCATE UNIT H
 ON THE FLOOR PLAN. INDICATE UNIT
 DESIGNATION FOR EACH UNIT. A RELIEF VENT
 IS REQUIRED FOR THE AAV AT KITCHEN SINK
 ON THE 4TH (?) LEVEL. SECTION 917.3.2.
 AND SECTION 104.2.1.
 52. SHT P-18 RISER S/3 DOES NOT REFLECT
 THE FLOOR PLAN. W/C, SHR & LAV ON FLOOR
 PLAN, W/M ON RISER DIAGRAM. CORRELATE
 RISER & FLOOR PLAN. SECTION 104.2.1.
 53. SHT P-18 RISER S/3A UNABLE TO LOCATE
 ON THE FLOOR PLAN. INDICATE FLOOR
 ELEVATION, UNIT DESIGNATION ETC.
 INDICATE RISER VENT WILL CONNECT TO AND
 SHOW CONNECTION AT RISER CONNECTING TO.
 SECTION 104.2.1.
 54. SHT P-18 RISER S/4 DOES NOT REFLECT
 THE FLOOR PLAN. NO TUBS SHOWN ON THE
 FLOOR PLAN. SECTION 104.2.1. PLEASE
 CORRELATE RISER & FLOOR PLAN.
 55. SHT P-18 RISER S/5 DOES NOT REFLECT
 THE FLOOR PLAN. W/C, SHR, & LAV ONLY ON
 FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 56. SHT P-18 THE FOLLOWING RISER
 DIAGRAM SHOWN ON THE FLOOR PLAN WERE
 NOT SUBMITTED. S/1R, S/2R, S/4A, S/4B,
 S/4C, S/4D, S/6, S/6A, S/7 & S/9. PLEASE
 SUBMIT RISER DIAGRAMS FOR ALL RISERS
 INDICATED ON THE FLOOR PLAN. SECTION
 104.2.1.
 57. ALL SANITARY RISER DIAGRAMS: PLEASE
 SHOW ALL PIPE SIZES, OFFSETS, OFFSET
 VENTS, FIXTURE UNITS, (RECHECK FU ON ALL
 RISER DIAGRAMS), VENTS, RELIEF VENTS,
 (WHERE REQUIRED), ETC. SECTIONS 104.2.1
 & 104.3.1.1.
 58. SHT P-19 ALL WATER RISER DIAGRAMS:
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 ALL AIR CHAMBERS FROM ALL RISER
 DIAGRAMS. WATER HAMMER ARRESTORS ARE
 REQUIRED AT EACH DISH WASHER, WASH
 MACHINE, AND REFRIGERATOR. PDI-WH 201.
 SECTION 604.9 INDICATE UNIT TYPE FOR
 EACH WATER RISER DIAGRAM. SECTION
 104.2.1.
 59. SHT P-20 OVERALL SANITARY ISOMETRIC:
 SHOW ALL PIPE SIZES, ALL DFU'S FOR EACH
 RISER AND AS THEY ACCUMULATE IN THE
 SYSTEM, AND ALL FIXTURES THAT CONNECT TO
 THE BUILDING DRAIN NOT SHOWN ON THE
 RISERS. SECTIONS 104.2.1 & 104.3.1.1.
 60. SHT P-21 OVERALL WATER ISOMETRIC:
 SHOW ALL PIPE SIZES, RISER DESIGNATIONS,
 VALVES, (SEE SECTION 606.1(1)(2)(3)(4)).
 SUBMIT MANUF. SPECIFICATIONS FOR THE
 DOMESTIC WATER BOOSTER PUMP. SECTION
 303.4. BACKFLOW TO BE LOCATED PER
 BACKFLOW DEPT. CITY WPB.
 61. SHT P-22 PARTIAL GARAGE DRAINAGE
 ISOMETRIC: SHOW SF AS IT ACCUMULATES IN
 THE SYSTEM. DOES NOT REFLECT THE FLOOR
 PLAN. SAND/OIL INTERCEPTOR SHALL BE
 UPSTREAM OF THE PUMP/EJECTOR. 4" SD UP
 IS SHOWN AS 6" ON THE FLOOR PLAN. PLEASE
 CORRELATE RISERS AND FLOOR PLANS.
 SECTION 104.2.1.
 63. SHT P-23 RECHECK ALL ADDITION FOR
 SQUARE FOOTAGE. - INDICATE WHAT CW
 STANDS FOR WHERE STORM EXITS BUILDING.
 SECTION 104.2.1.
 64. SHT P-23 PUMPS CONNECTED TO THE
 DRAINAGE SYSTEM SHALL CONNECT TO THE
 BUILDING SEWER OR SHALL CONNECT TO A WYE
 FITTING IN THE BUILDING DRAIN A MINIMUM
 OF 10 FEET FROM THE BASE OF ANY SOIL
 STACK, WASTE STACK OR FIXTURE DRAIN.
 WHERE THE DISCHARGE LINE CONNECTS INTO
 THE HORIZONTAL DRAINAGE PIPING, THE
 CONNECTOR SHALL BE MADE THROUGH A WYE
 FITTING INTO THE TOP OF THE DRAINAGE
 PIPING. SECTION 712.3.5.
 65. SHT P-24 SAND/OIL INTERCEPTOR DETAIL
 TWO WAY CLEANOUTS ARE REQUIRED AS THE
 WATER ENTERS THE INTERCEPTOR AND AS THE
 WATER EXITS THE INTERCEPTOR. A VENT
 CONNECTION IS SHOWN, THE INTERCEPTOR
 SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUF. INSTRUCTIONS. SECTION 1003.2 AND
 UTILITY STANDARDS.
 66. SHT P-24 PLUMBING GENERAL NOTES: 1B
 REFERENCES THE SOUTH FLORIDA BUILDING
 CODE AS WELL AS THE PLUMBING FIXTURE
 SCHEDULE #1). THESE SHALL REFERENCE THE
 FLORIDA BUILDING CODE-2001 AS WE HAVE
 BEEN IN THIS CODE STATEWIDE SINCE MARCH
 1, 2002.
 67. SHT P-24 PLUMBING GENERAL NOTES: 4.
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9.
 68. SHT P-24 GARAGE AREA DRAIN SUMP PUMP
 DETAIL: SHOWS THE SUMP PIT TO BE
 18"X18"X18". SECTION 712.3.2 STATES THE
 SUMP PIT SHALL NOT BE LESS THAN 24"
 DEEP. PLEASE INDICATE ON DETAIL.
 69. ALL SANT., WATER, STORM, CONDENSATE
 RISER DIAGRAMS SHALL BE SHOWN ON EACH
 FLOOR AND SHALL REFLECT THE RISER
 DIAGRAMS FOR EACH SYSTEM. SOME RISERS
 ARE NOT SHOWN ON ONE FLOOR BUT APPEAR ON
 ANOTHER FLOOR. PLEASE CORRELATE ALL
 RISERS WITH THE FLOOR PLANS.
 70. PLANS DO NOT APPEAR TO BE COMPLETE
 AT THIS TIME AND MORE COMMENTS MAY BE
 GENERATED ACCORDING TO THE COMMENT
 RESPONSES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS