| Date |
Text |
| 2005-12-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB CODE |
| | |
| | 1. SHT A-G.0 NOT SIGNED, SEALED AND |
| | DATED AS REQUIRED BY FAC 61G1-16.003 AND |
| | FS 481.2055. |
| | 2. ALL ARCHITECTURAL SHEETS REQUIRE THE |
| | PERSONAL SIGNATURE OF THE ARCHITECT. |
| | PLEASE SUBMIT DRIVERS LICENSE, VOTERS |
| | REGISTRATION, OR OTHER PROOF OF LEGAL |
| | SIGNATURE. INITIALS ARE NOT APPROVED. IF |
| | THAT IS INDEED YOUR LEGAL SIGNATURE, |
| | SUBMIT A SIGNED, SEALED, DATED, PROPERLY |
| | NOTERIZED LETTER INDICATING LEGAL |
| | SIGNATURE FOR OUR FILES. |
| | 3. SHTS PD1, PD2, WS1, WS2, WS3, & WS4 - |
| | SEAL INFORMATION REQUIRED BY FAC |
| | 61G1-16.001 & .002 AND FS 481.321 IS NOT |
| | IMPRESSED ON THE PLANS. PLEASE RESEAL |
| | ALL SHEETS IMPRESSING REQUIRED |
| | INFORMATION. SIGNATURE IS A PHOTOCOPY |
| | AND SHALL BE A WET SIGNATURE. THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER |
| | REQUIRED BY FS 481.319(C) AND FAC |
| | 61G1-16.004(2) SHALL BE ON EACH SHEET. |
| | 4. SHT WS1 INDICATE TYPE OF DRAINAGE FOR |
| | THE TRENCH DRAIN. IF STORM DRAINAGE, IT |
| | WILL DRAIN TO STORM SEWER. CITY WPB CODE |
| | 90-125(5). |
| | 5. SHTS A-2.4, A-2.7, A-2.8, A-2.9 AND |
| | A-2.23. SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS. SHOW THE SF |
| | OF EACH AREA WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS, AND |
| | THE AREA OF ROOFS THAT DRAIN FROM ABOVE |
| | ON TO THE ROOF AREA IN THE CALCULATIONS. |
| | SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. |
| | 6. INFORMATIONAL - SEPARATE POOL PERMIT |
| | REQUIRED. PLANS SHALL BE ROUTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPT. PRIOR TO |
| | BEING SUBMITTED TO THE CITY FOR REVIEW. |
| | PLANS SHALL BE STAMPED BY HEALTH DEPT. |
| | (MINIMUM TWO COPIES). |
| | 7. SHTS A-2.10 THRU A-2.12 & A-2.15 THRU |
| | A-2.20.5. THE CLEAR FLOOR SPACE |
| | DIMENSIONS ARE TO BE APPLIED OR |
| | SUPERIMPOSED OVER A PLAN DURING THE |
| | DESIGN PROCESS TO DETERMINE IF SPACE |
| | REQUIREMENTS AT THE TOILETS ARE BEING |
| | MET. SEE PAGE 7.43. |
| | 8. SHTS A-2.15 THRU A-2.20.5. THE 30" X |
| | 48" CLEAR FLOOR SPACE FOR THE SHOWERS |
| | MUST BE PARALLEL TO THE FIXTURE & FLUSH |
| | WITH THE CONTROL WALL. SEE PAGE 7.56. |
| | 9. ALL UNITS - SPECIFICATION "A" OR "B" |
| | SHALL BE INDICATED FOR THE BATHROOMS OF |
| | EACH UNIT. SEE PAGE 7.35. |
| | 10. SHTS A-2.3 & A-2.25 TOILET ROOMS |
| | SHALL BE ACCESSIBLE. PLEASE SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | 11. SHT A-2.25 SUBMIT A DETAIL FOR THE |
| | ACCESSIBLE DRINKING FOUNTAIN. SHOW |
| | COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS. |
| | 12. SHT A-4.0 CALLS OUT SHT A-X.X FOR |
| | DETAILS AND TYPICAL SPECS FOR ALUMINUM |
| | RAININGS. SHT A-X.X WAS NOT FOUND OR |
| | INDICATED ON THE INDEX SHEET. PLEASE |
| | CLARIFY. MORE INFORMATION IS REQUIRED. |
| | SECTION 104.2.1. |
| | 13. SHT A-7.0 DETAIL #9 INDICATES A 4" X |
| | 10" SCUPPER, BUT SHTS A-2.21 & A-2.22 |
| | SHOW 14" X 6" SCUPPERS. PLEASE CLARIFY |
| | AND CORRELATE DETAILS AND ROOF PLANS. |
| | SECTION 104.2.1. |
| | 14. SHT A-8.3 INTERIOR FININSH #032 |
| | INDICATES PAINT ON GREEN BOARD DRYWALL. |
| | PLEASE INDICATE HOW THIS WILL MEET THE |
| | REQUIREMENTS OF SECTION 1204.2 |
| | (NONABSORBENT MATERIAL TO A HEIGHT OF |
| | 4FT ABOVE THE FLOORL. |
| | 15. ALL PLUMBING & MECHANICAL SHEETS. |
| | THE CERTIFICATE OF AUTHROIZATION NUMBER |
| | IS REQUIRED ON EACH SHEET PER FAC |
| | 61G15-23.002(2) AND FS 471.025. |
| | 16. SHT P-1 THE SAND/OIL INTERCEPTOR |
| | SHALL BE SIZED BY LYNN MASSON |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT |
| | HER AT (561) 822-2271, OR FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. |
| | WASTE ORD. 3434. |
| | 17. P-1 MORE INFORMATION IS REQUIRED FOR |
| | THE WET-WELL PRECAST CONCRETE BASIN. |
| | SUBMIT MANUF. SPECIFICATION SHEETS. |
| | SECTION 104.2.1.2. |
| | 18. THE SAND/OIL INTERCEPTOR SHALL BE |
| | LOCATED UPSTREAM OF THE PUMP SYSTEM. |
| | 19. SHT P-1 SHOW SF OF ALL RISERS, ALL |
| | SF AS IT ACCUMULATES IN THE SYSTEM, AND |
| | ALL PIPE SIZES. |
| | 20. SHT P-1 RISER AT COL. LINE C/3 IS |
| | NOT SHOWN ON SHT P-2. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 21. SHT P-2 G.D. AT COL. LINE C/2 NOT |
| | SHOWN ON SHT P-1. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 22. SHT P-2 RISER AT COL. LINE E/4 IS |
| | SHOWN AS 6" 1860SF, BUT ON SHTS P-1 & |
| | P-3 IT IS SHOWN AS 4" 930SF. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 23. SHT P-2 4" DOWNSTREAM OF S/2, S/6, |
| | S/4D SHOWS 4" DN, BUT ENDS AT THAT |
| | POINT. PLEASE CLARIFY. SECTION 104.2.1. |
| | 24. SHT P-2 12" SD AS IT EXITS THE |
| | BUILDING STATES "CONNECT CW LINE". |
| | PLEASE INDICATE WHAT CW MEANS. |
| | 25. SHT P-3 F.D.'S IN TRASH ROOM ARE NOT |
| | SHOWN ON THE SANT. RISER DIAGRAM. |
| | SECTION 104.3.1.1. |
| | 26. SHT P-3 RWL #3 SHOWN ON P-3 NOT |
| | SHOWN ON SHT P-2. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 27. SHT P-3 AAV SHOWN ON THE COL. LINE C |
| | BETWEEN COLS. 4 & 5 REQUIRES A RELIEF |
| | VENT PER SECTION 617.3.2. |
| | 28. SHT P-3 RPZV BACKFLOW SHALL BE |
| | LOCATED AS CLOSE TO THE METER AS |
| | POSSIBLE ON PRIVATE PROPERTY. PLEASE |
| | CONTACT ORVILLE POLK AT THE BACKFLOW |
| | DEPARTMENT (561) 822-2240 FOR PROPER |
| | LOCATION OF BACKFLOW PREVENTER. |
| | 29. SHT P-4 MEN'S & WOMEN'S TOILET ROOMS |
| | AND FLOOR DRAINS IN THE PUMP ROOM ARE |
| | NOT SHOWN ON THE SANT. RISER DIAGRAMS. |
| | SECTION 104.3.1.1. |
| | 30. SHT P-4 AAV SHOWN ON COL LINE C |
| | BETWEEN COLS. 4 & 5 REQUIRE A RELIEF |
| | VENT PER SECTION 617.3.2. |
| | 31 SHT P-4 SUBMIT MANUF. SPECIFICATIONS |
| | FOR DOMESTIC WATER BOOSTER PUMPS. PUMPS |
| | SHALL BE LISTED. SECTION 303.4. |
| | 32. SHT P-5 RWL #1 IS NOT SHOWN ON THE |
| | FLOOR PLAN BELOW. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 33. SHT P-5 RISER S/4 AT COL. LINE 3 |
| | WEST OF COL. E.4 IN INDICATED AS RISER |
| | S/4A ON SHT P-4. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 34. SHT P-5. INDICATE ALL RISER NUMBERS |
| | AT KITCHEN SINKS. RISERS NOT SHOWN ON |
| | PREVIOUS FLOOR PLAN SHEET. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 35. SHT P-6 RISERS FOR KITCHEN SINKS ARE |
| | NOT SHOWN. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 36. SHT P-7 RISER S/4 SHOWN OFFSETTING |
| | IN CEILING. SHT P-7 INDICATES 3-6 |
| | LEVELS. IS THIS OFFSET ON EACH FLOOR? |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 37. SHTS P-7 THRU P-11 KITCHEN SINKS |
| | RISERS ARE NOT SHOWN. PLEASE INDICATE |
| | THE RISER NUMBER FOR KITCHEN SINKS. |
| | SECTION 104.2.1. |
| | 38. SHT P-8 OFFSET FOR S/4A AT COL. LINE |
| | D BETWEEN COLS. 5 & 6 IS NOT SHOWN. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 39. SHT P-8 RISER S/6 NOT SHOWN ON |
| | PREVIOUS FLOOR PLAN. (P-6) PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 40. ALL PIPES 3" AND LARGER ARE NOT |
| | APPROVED IN BLOCK WALLS. SECTION |
| | 1907.3.6. |
| | 41. SHTS P-12 & P-13 SHOW THE LOCATION |
| | OF ALL VENTS THRU THE ROOF. SECTION |
| | 104.2.1. |
| | 42. SHT P-15 TOILET ROOMS AND SERVICE |
| | SINK ARE NOT SHOWN ON THE RISER DIAGRAM. |
| | SECTION 104.3.1.1. |
| | 43. SUBMIT STORM RISER DIAGRAMS IN |
| | ISOMETRIC FORM. SHOW ALL PIPE SIZES, |
| | OFFSETS, & INDICATE SF AS IT ACCUMULATES |
| | IN RISER. SECTION 104.3.1.1. |
| | 44. SUBMIT CONDENSATE RISER DIAGRAMS |
| | SHOWING ALL PIPE SIZES, OFFSETS ECT. |
| | 45 SUBMIT A CONDENSATE BLDG DRAIN |
| | ISOMETRIC SHOWING THE LOCATION OF ALL |
| | CONDENSATE RISERS AND THE TERMINATION |
| | POINT OF THE CONDENSATE SYSTEM. SECTION |
| | 104.3.1.1. |
| | 46.SHTS P-16 & P-17 IF THERE ARE VENT |
| | THRU THESE ROOFS, PLEASE SHOW THE |
| | LOCATION OF EACH. SECTION 104.2.1. |
| | 47. SHT P-18 INDICATES LEVEL 9 & LEVEL |
| | 10. THE BUILDING IS ONLY 8 STORIES HIGH. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 48. SHT P-18 RISER S/1 DOES NOT REFLECT |
| | THE FLOOR PLAN. NO TUBS SHOWN. SECTION |
| | 104.2.1. PLEASE CORRELATE RISER & FLOOR |
| | PLAN. |
| | 49. SHT P-18 RISER S/2 DOES NOT REFLECT |
| | THE FLOOR PLAN. RISER SHOWS KITCHEN |
| | SINKS AND FLOOR PLAN SHOWS W/M'S. PLEASE |
| | CORRELATE RISERS & FLOOR PLANS. SECTION |
| | 104.2.1. |
| | 50. SHT P-18 RISER S/2A NOT FOUND ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 51. SHT P-18 RISER S/2B NOT LOCATED ON |
| | THE FLOOR PLAN. UNABLE TO LOCATE UNIT H |
| | ON THE FLOOR PLAN. INDICATE UNIT |
| | DESIGNATION FOR EACH UNIT. A RELIEF VENT |
| | IS REQUIRED FOR THE AAV AT KITCHEN SINK |
| | ON THE 4TH (?) LEVEL. SECTION 917.3.2. |
| | AND SECTION 104.2.1. |
| | 52. SHT P-18 RISER S/3 DOES NOT REFLECT |
| | THE FLOOR PLAN. W/C, SHR & LAV ON FLOOR |
| | PLAN, W/M ON RISER DIAGRAM. CORRELATE |
| | RISER & FLOOR PLAN. SECTION 104.2.1. |
| | 53. SHT P-18 RISER S/3A UNABLE TO LOCATE |
| | ON THE FLOOR PLAN. INDICATE FLOOR |
| | ELEVATION, UNIT DESIGNATION ETC. |
| | INDICATE RISER VENT WILL CONNECT TO AND |
| | SHOW CONNECTION AT RISER CONNECTING TO. |
| | SECTION 104.2.1. |
| | 54. SHT P-18 RISER S/4 DOES NOT REFLECT |
| | THE FLOOR PLAN. NO TUBS SHOWN ON THE |
| | FLOOR PLAN. SECTION 104.2.1. PLEASE |
| | CORRELATE RISER & FLOOR PLAN. |
| | 55. SHT P-18 RISER S/5 DOES NOT REFLECT |
| | THE FLOOR PLAN. W/C, SHR, & LAV ONLY ON |
| | FLOOR PLAN. CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1. |
| | 56. SHT P-18 THE FOLLOWING RISER |
| | DIAGRAM SHOWN ON THE FLOOR PLAN WERE |
| | NOT SUBMITTED. S/1R, S/2R, S/4A, S/4B, |
| | S/4C, S/4D, S/6, S/6A, S/7 & S/9. PLEASE |
| | SUBMIT RISER DIAGRAMS FOR ALL RISERS |
| | INDICATED ON THE FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 57. ALL SANITARY RISER DIAGRAMS: PLEASE |
| | SHOW ALL PIPE SIZES, OFFSETS, OFFSET |
| | VENTS, FIXTURE UNITS, (RECHECK FU ON ALL |
| | RISER DIAGRAMS), VENTS, RELIEF VENTS, |
| | (WHERE REQUIRED), ETC. SECTIONS 104.2.1 |
| | & 104.3.1.1. |
| | 58. SHT P-19 ALL WATER RISER DIAGRAMS: |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | ALL AIR CHAMBERS FROM ALL RISER |
| | DIAGRAMS. WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT EACH DISH WASHER, WASH |
| | MACHINE, AND REFRIGERATOR. PDI-WH 201. |
| | SECTION 604.9 INDICATE UNIT TYPE FOR |
| | EACH WATER RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 59. SHT P-20 OVERALL SANITARY ISOMETRIC: |
| | SHOW ALL PIPE SIZES, ALL DFU'S FOR EACH |
| | RISER AND AS THEY ACCUMULATE IN THE |
| | SYSTEM, AND ALL FIXTURES THAT CONNECT TO |
| | THE BUILDING DRAIN NOT SHOWN ON THE |
| | RISERS. SECTIONS 104.2.1 & 104.3.1.1. |
| | 60. SHT P-21 OVERALL WATER ISOMETRIC: |
| | SHOW ALL PIPE SIZES, RISER DESIGNATIONS, |
| | VALVES, (SEE SECTION 606.1(1)(2)(3)(4)). |
| | SUBMIT MANUF. SPECIFICATIONS FOR THE |
| | DOMESTIC WATER BOOSTER PUMP. SECTION |
| | 303.4. BACKFLOW TO BE LOCATED PER |
| | BACKFLOW DEPT. CITY WPB. |
| | 61. SHT P-22 PARTIAL GARAGE DRAINAGE |
| | ISOMETRIC: SHOW SF AS IT ACCUMULATES IN |
| | THE SYSTEM. DOES NOT REFLECT THE FLOOR |
| | PLAN. SAND/OIL INTERCEPTOR SHALL BE |
| | UPSTREAM OF THE PUMP/EJECTOR. 4" SD UP |
| | IS SHOWN AS 6" ON THE FLOOR PLAN. PLEASE |
| | CORRELATE RISERS AND FLOOR PLANS. |
| | SECTION 104.2.1. |
| | 63. SHT P-23 RECHECK ALL ADDITION FOR |
| | SQUARE FOOTAGE. - INDICATE WHAT CW |
| | STANDS FOR WHERE STORM EXITS BUILDING. |
| | SECTION 104.2.1. |
| | 64. SHT P-23 PUMPS CONNECTED TO THE |
| | DRAINAGE SYSTEM SHALL CONNECT TO THE |
| | BUILDING SEWER OR SHALL CONNECT TO A WYE |
| | FITTING IN THE BUILDING DRAIN A MINIMUM |
| | OF 10 FEET FROM THE BASE OF ANY SOIL |
| | STACK, WASTE STACK OR FIXTURE DRAIN. |
| | WHERE THE DISCHARGE LINE CONNECTS INTO |
| | THE HORIZONTAL DRAINAGE PIPING, THE |
| | CONNECTOR SHALL BE MADE THROUGH A WYE |
| | FITTING INTO THE TOP OF THE DRAINAGE |
| | PIPING. SECTION 712.3.5. |
| | 65. SHT P-24 SAND/OIL INTERCEPTOR DETAIL |
| | TWO WAY CLEANOUTS ARE REQUIRED AS THE |
| | WATER ENTERS THE INTERCEPTOR AND AS THE |
| | WATER EXITS THE INTERCEPTOR. A VENT |
| | CONNECTION IS SHOWN, THE INTERCEPTOR |
| | SHALL BE INSTALLED IN ACCORDANCE WITH |
| | MANUF. INSTRUCTIONS. SECTION 1003.2 AND |
| | UTILITY STANDARDS. |
| | 66. SHT P-24 PLUMBING GENERAL NOTES: 1B |
| | REFERENCES THE SOUTH FLORIDA BUILDING |
| | CODE AS WELL AS THE PLUMBING FIXTURE |
| | SCHEDULE #1). THESE SHALL REFERENCE THE |
| | FLORIDA BUILDING CODE-2001 AS WE HAVE |
| | BEEN IN THIS CODE STATEWIDE SINCE MARCH |
| | 1, 2002. |
| | 67. SHT P-24 PLUMBING GENERAL NOTES: 4. |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | FROM REFERENCE. SECTION 604.9. |
| | 68. SHT P-24 GARAGE AREA DRAIN SUMP PUMP |
| | DETAIL: SHOWS THE SUMP PIT TO BE |
| | 18"X18"X18". SECTION 712.3.2 STATES THE |
| | SUMP PIT SHALL NOT BE LESS THAN 24" |
| | DEEP. PLEASE INDICATE ON DETAIL. |
| | 69. ALL SANT., WATER, STORM, CONDENSATE |
| | RISER DIAGRAMS SHALL BE SHOWN ON EACH |
| | FLOOR AND SHALL REFLECT THE RISER |
| | DIAGRAMS FOR EACH SYSTEM. SOME RISERS |
| | ARE NOT SHOWN ON ONE FLOOR BUT APPEAR ON |
| | ANOTHER FLOOR. PLEASE CORRELATE ALL |
| | RISERS WITH THE FLOOR PLANS. |
| | 70. PLANS DO NOT APPEAR TO BE COMPLETE |
| | AT THIS TIME AND MORE COMMENTS MAY BE |
| | GENERATED ACCORDING TO THE COMMENT |
| | RESPONSES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |