| 2005-12-28 00:00:00 | PLAN DENIED | | | 1) PLEASE HAVE SEER OF A/C EQUIPMENT ON | | | ENERGY CALCULATIONS. | | | 2) PLEASE REFER TO TABLE 403.3 PRIVATE | | | GARAGES.2001 FBC(M) | | | 3) PLEASE PROVIDE A COPEY OF | | | INSTALLATION INSTRUCTIONS FOR A/C | | | EQUIPMENT | | | 4) PAGE M-2.1 CFM ON VEF-5 DOES NOT | | | MATCH | | | VENTILATION FAN SCHEDULE ON PAGE M-4.4. | | | 5) PAGE M-2.2 GENRATOR.PLEASE REFER TO | | | SECTION 1305.7VENT PIPING.2001 FBC (M) | | | 6) PAGE M-2.3 BATHROOM EXHAUST MUST | | | TERMINATE OUT DOORS.SECTION 501.3 2001 | | | FBC (M). | | | 7) PAGE M-2.3 CAN NOT BRING FRESH AIR | | | FROM GARAGE INTO MECH/ELEC ROOMS. | | | 8) PAGE M-2.8 PLEASE REFER TO SECTION | | | 1511.7 AND TABLE 1511.7 2001 | | | FBC.CLEARANCE BELOW RAISED ROOF MOUNTED | | | MECHANICAL UNITS. | | | 9) PAGE M-3.0 PLEASE REFER TO SECTION | | | 504.6 DRYER EXHAUST. | | | 10) PAGE M-3.2 PLEASE REFER TO SECTION | | | 602.2.1 MATERIALS EXPOSED IN PLENUMS | | | (A/C CLOSIT DOORS ARE PART OF PLENUM) | | | 11) PLEASE REFER TO SECTION 601.4 | | | BALANCED RETURN AIR. | | | 12) PLEASE SHOW CALCULATIONS ON PLANS | | | FROM TABLE 1103.1 2001 FBC(M)ON | | | REFRIGERANT LINES AND 2HR SHAFTS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|