2005-12-28 00:00:00PLAN DENIED
 1) PLEASE HAVE SEER OF A/C EQUIPMENT ON
 ENERGY CALCULATIONS.
 2) PLEASE REFER TO TABLE 403.3 PRIVATE
 GARAGES.2001 FBC(M)
 3) PLEASE PROVIDE A COPEY OF
 INSTALLATION INSTRUCTIONS FOR A/C
 EQUIPMENT
 4) PAGE M-2.1 CFM ON VEF-5 DOES NOT
 MATCH
 VENTILATION FAN SCHEDULE ON PAGE M-4.4.
 5) PAGE M-2.2 GENRATOR.PLEASE REFER TO
 SECTION 1305.7VENT PIPING.2001 FBC (M)
 6) PAGE M-2.3 BATHROOM EXHAUST MUST
 TERMINATE OUT DOORS.SECTION 501.3 2001
 FBC (M).
 7) PAGE M-2.3 CAN NOT BRING FRESH AIR
 FROM GARAGE INTO MECH/ELEC ROOMS.
 8) PAGE M-2.8 PLEASE REFER TO SECTION
 1511.7 AND TABLE 1511.7 2001
 FBC.CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS.
 9) PAGE M-3.0 PLEASE REFER TO SECTION
 504.6 DRYER EXHAUST.
 10) PAGE M-3.2 PLEASE REFER TO SECTION
 602.2.1 MATERIALS EXPOSED IN PLENUMS
 (A/C CLOSIT DOORS ARE PART OF PLENUM)
 11) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.
 12) PLEASE SHOW CALCULATIONS ON PLANS
 FROM TABLE 1103.1 2001 FBC(M)ON
 REFRIGERANT LINES AND 2HR SHAFTS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732