Plan Review Notes
Plan Review Notes For Permit 05091467
Permit Number 05091467
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-25 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.
 ********** UNSAT ************
  
 SKYLINE LOFTS.
  
 1)NOTE: PLEASE BE SURE PLANS MAKE
 REFERENCE TO CURRENT ELECTRICAL CODE IN
 EFFECT. NFPA-70 2002, 2002 NFPA-72
  
 2)NOTE: PLEASE BE SURE ALL SHEETS ARE
 SIGNED , DATED A ND SEALED AS REQUIRED
 UNDER FS 481.221, 471.025, AND 472.025
 PLEASE SEE PD-1, -2 AND WS SHEETS WHICH
 SOME ARE SEALED PHOTO-COPIES AND SOME
 ARE ONLY PHOTOCOPIES AND NOT SEALED OR
 DATED.
 THIS SIS REQUIRED FOR ALL SHEETS AND FRO
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION FOR M AND P SHEETS. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE WHICH
 REQUIRES THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON SAID TITLE BLOCK
 AS REQUIRED UNDER FS 471.023
 THIS IS NOT A COMMENT FOR THE ELECTRICAL
 ENGINEERING FIRM.
  
 4)NOTE: PLEASE CORRELATE THE NUMBER OF
 UNITS. PLEASE SEE STRUCTUAL CALCULATION
 BOOK SUBMITTED INDICATE 103 UNITS, AND
 ELECTRICAL PLANS INDICATE 99?
  
 5)NOTE: PLEASE OBTAIN A LETTER FROM MR.
 BILL HARTIGAN(FPL) WITH RESPECT TO THE
 APPROVAL OF THE FPL VAULT AS SHOWN.
 PLEASE SEE LOCATION AND SIZE IS TO BE
 DETERMINED BY FPL.
 IT IS NOT COMMON FOR THE VAULT TO BE
 LOCATED INSIDE BUILDING WITHOUT DIRECT
 ACCESS FROM OUTSIDE.
  
 6)NOTE: PLEASE ALSO KNOW, IT WILL BE
 REQUIRED TO BE IN FURTHER DISCUSSION
 WITH THE FIRE MARSHAL'S OFFICE WITH
 RESPECT TO THE LOCATION AND ACCESS TO
 THE MAIN ELECTRICAL ROOM. IT APPEARS
 FIRE DEPT PERSONNEL WOULD HAVE TO ENTER
 THROUGH THE BLDG AND POSSIBLY THE
 PARKING GARAGE FOR SOME DISTANCE IN
 ORDER TO SHUT DOWN MAINS ELECTRICAL
 SYSTEMS? THIS WOULD NOT BE PERMITTED. A
 DIRECT ACCESS (4HR RATED) WOULD BE
 REQUIRED. THIS WILL REQUIRED FURTHER
 REVIEW.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 ROOMS NOTED FOR ACCESS.(FIRE PUMP)
  
 7)NOTE: PLEASE SEEMAIN ELECTRICAL
 ROOM, GENERATOR RM, FIRE PUMP RM, WILL
 REQUIRE DOORS TO OPEN OUTWARD.
 THESE ROOMS WILL ALSO BE REQUIRED TO
 HAVE PANIC HARDWARE ON DOORS.
 PLEASE PROVIDE NOTE ON PLANS FOR DOOR
 HARDWARE.
 110.26, 90.4
  
 8)NOTE: PLEASE PROVIDE THE BUS-DUCT
 DETAIL AS SPECIFIED IN 368.6 FOR FLOOR
 PENETRATIONS. (4" CURBING ALL THE WAY
 AROUND).
  
 9)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL CORIDORS AND EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A MIN
 OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURES OF SOME SORT WILL BE REQUIRED
 IN STAIR TOWERE AND CORRIDORS TO MEET
 THE MIN 1 FT CANDLE UNDER EM POWER.
 PLEASE SEE 7.9 WHICH REQUIRES THIS IN
 ALLEAVIATING IN AREA BEING IN TOTAL
 DARKNESS UPON THE TRIPPING OF A SINGLE
 DEVICE, SWITCH, BRKR ETC.
  
 10)NOTE: PLEASE PROVIDE A BATTERY BACK
 UP FIXTURE IN ELECTRICAL ROOMS, GEN RMS,
 FIRE PUMP RM, AND FIRE COMMAND ROOM.
 IT IS KNOWN SOME OF THESE ROOMS CONTAIN
 SOME ALREADY.
 700.16,LS 101 7.8, 7.9.700.12E
  
 11)NOTE: PLEASE SEE FIRE REVIEW NOTES
 WITH RESPECT TO FIRE COMMAND ROOM AND
 MISSING EQUIPMENT AS REQUIRED UNDER
 HIGH-RISEREQUIREMENTS IN 11.9 LS 101
 PLEASE ALSO VERIFY WITH FIRE MARSHAL'S
 OFFICE THE MIN SIZING OF ROOM WHICH MAY
 BE REQUIRED. PLEASE SEE SPACE ABOUT
 THESE CONTROL PANELS SEEM TO BE LIMITTED
 ON ANGLES OF ROOMS AND WITH OTHER ITEMS
 TO BE INSTALLED THIS MAY BE AN ISSUE.
  
 12)NOTE: PLEASE SEE FIRE REVIEW NOTES
 PERTAINING TO ALLEY WAY IN REAR OF BLDG.
 PLEASE SEE 14' ALLEY SHOWN, IS THIS
 PUBLIC? PRIVATE ?
 IF PRIVATE PLEASE SEE 7.8,7.9 LS 101,
 WHICH REQUIRES ILLUMINATION TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE ALSO SEE ORIG FIRE NOTE WITH
 RESPECT TO VEHICULAR TRAFFIC.
  
 13)NOTE: PLEASE SEE 620.23 REQUIRE STHE
 LTS AND RECEPTS IN THE ELEVATOR MACHINE
 ROOM TO BE ON A DEDICATED CIRCUIT. THIS
 NOTED ON PANEL SCHEDULE, HOWEVER THE
 CIRCUITING ON PLANS SEEMS TO BE MISSING?
  
 14)NOTE: PLEASE SEE 110.26 FOR ALL
 ELECTRICAL ROOMS SHOWN.
 PLEASE SEE ALL MIN CLEARENCES WILL BE
 REQUIRED , EVEN FOR BUS-DUCT. PLEASE SEE
 REDLINED PLANS FOR LOCATIONS OF CONCERN.
  
 15)NOTE: PLEASE PROVIDE A DETAIL FOR THE
 MIN DISCONNECTING MEANS FOR ROOF TOP
 CU'S. THIS DETAIL MAY BE "TYPICAL".
 440.11
  
 16)NOTE: PLEASE SEE THAT THE
 PHOTOMETRICS SHOWN FOR THE POOL AREA
 MUST BE SUBMITTED FOR REVIEW AND
 STAMPING BY THE PALM BEACH COUNTY HEALTH
 DEPT.
 PLEASE KNOW, THE POOL IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
  
 17)NOTE: PLEASE PROVIDE A NOTE ON
 ROOFTOP PLANS WITH RESPECT TO ANY
 LIGHTNING PROTECTION SYSTEM WHICH MAY BE
 PROPOSED.
 PLEASE MAKE NOTE TO ANY SYETM SHALL
 COMPLY COMPLETELY WITH NFPA-780 WITH
 WORDS TO THAT AFFECT.
  
 18)NOTE:PLEASE SEE UNITS WHICH ARE
 MISSING COUNTERSPACE GFI RECEPTS AS
 REQUIRED PER 210.52C1.
 SOME UNITS ARE SHOWING GFI'S WHERE
 COUNTERS AMY BE LESS THAN 12" AND SOME
 ARE SHOWN, YET OTHERS WHICH ARE MORE
 THAN 12" DO NOT CONTATIN ANY.
 PLEASE SEE MANY UNITS SEEM TO HAVE THESE
 RECEPTS LOCATED BEHIND THE FRIG??
 PLEASE MANY OF THESE HAVE BEEN REDLINED
 ON PLANS.
 ** PLEASE ALSO SEE RELDINED UNIT WHERE
 MICRO/HOOD CIRCUIT IS MISPLACED WITH
 SMALL APPL.(L101)
  
 19)NOTE: PLEASE SEE SOME CIRCUITING
 MISSING IN UNITS FOR DEVICES.
 215.5 PLEASE COMPLETE.
  
 20)NOTE: PLEASE SEE RECEPTS MISSNG FOR
 WALL SPACE PER 210.52. MANY OF THESE
 HAVE BEEN REDLINED.
 PLEASE SEE MOST ALL UNITS ARE MISSING
 DOORS, SO SOME MAY BE REQUIRED FURTHER
 ONCE DOOR OVERLAY HAS BEEN CORRECTED.
 PLEASE ALSO SEE AREAS WHICH APPEAR TO
 SHOW FIXED GLASS PANELS/WALLS WHICH ARE
 CONSIDERED WALL SPACE AND WOULD REQUIRE
 A RECEPT WITHIN 6' OF DOORWAY.
 SEE REDLINES.
  
 21)NOTE: PLEASE SEE LOFT UNITS NEED TO
 INDICATE THE MEANS OF EGRESS CONTROLL
 FOR LIGHTING LEADING TO FLOOR ABOVE.
 SOME SHOW "S" BUT NO S/3". 210.70 ETC.
  
 22)NOTE: PLEASE SEE MISSING FIRST LEVEL
 OF LOFT 6/7? 2.12
 NO REVIEW.
  
 23)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE REQUIRED FOR CLOSETLTS.
 REDLINED.
  
 24)NOTE: PLEASE SEE MISSING SD'S OUTSIDE
 ALL SLEEPING RMS AS REQUIRED PER NFPA-72
 11.5.1.1
 PLEASE ALSO SEE FBC 905
 PLEASE ALSO PROVIDE A NOTE ON ALL UNIT
 SHEETS WHICH REFERENCES NFPA-72 11.8.3.5
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE A
 MIN OF 3' FROM BATH AND KITCHEN DOOR'S,
 3' FROM SUPPLYAND 5' FROM RETURN AIR
 GRILLES.
 PLEASE ALSO SEE SD'S ARE ALSO REQUIRED
 TOBE A MIN OF 20' FROM COOKING
 APPLIANCES, WITH EXCEPTIONS.
  
 25)NOTE: PLEASE SEE UNIT 203, MASTER
 BATH GFI WHICH IS SHOWN ON SMALL
 APPLIANCE CIRCUIT. PLEASE SEE 210.52B1 ,
 NO OTHERS PERMITTED.
 THIS APPEARS TO BE A MISPRINT AS, THE
 BATH GFI CIRCUIT IS #2.
  
 26)NOTE: PLEASE SEE 210.52B1 WHICH DOES
 NOT PERMIT ANY OTHER OUTLETS/DEVICES ON
 THE ONE OR MORE SMALL APPL CIRCUITS.
 PLEASE SEE SOME DINING AREAS APPEAR TO
 CONTAIN OTHER GEN LT CIRCUIT.
 PLEASE DEFINE DINING AREA.
  
 27)NOTE: PLEASE SEE NOTE #29 ON RISER
 INDICATES SD'S TO BE WIRED TO THE
 BATH/KITCHEN LIGHTING CIRCUIT??
 PLEASE VERIFY THIS AS THE #'S DO NOT
 MATCH UP.
 THIS IS PERMITTED, HOWEVER THEN THE
 KITCHEN/BATH LTS WOULD ALSO BE ARC
 FAULT.210.12
  
 28)NOTE: PLEASE SEE REDLINED METER
 CENTER CALCULATIONS, PLEASE CORRLEATE
 ALL . 532/538 ETC
  
 29)NOTE: PLEASE SEE THE FEEDER FOR THE
 FIRE PUMP FROM THE GENERATOR SHALL ALSO
 BE ENCASED IN CONCRETE UNLESS "OUTSIDE"
 THE BLDG.695.6, LS 101 9.3
  
 30)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHETS FOR GENERATOR, ATS, FIRE
 PUMP, FIRE PUMP CONTROLLER AND SUB-BASE
 FUEL TANK. PLEASE KNOW, REVIEW FOR MANY
 ITEMS FOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME AS NONE WERE
 SUBMITTED.
 PLEASE ALSO VERIFY AND NOTE SETTING FOR
 LOCKED ROTOR PER 695.4B1
 PLEASE SEE NFPA-20 CHAPTERS 9 AND 10.
 PLEASE KNOW, THE SUB-BASE FUEL TANK WILL
 BE REVIEWED BY OTHERS.
  
  
 31)NOTE: PLEASE SEE NFPA-20 WHICH
 REQUIRES A MIN OF 8HRS RUNNING TIME AT
 100% LOAD FOR THE FIRE PUMP.
 9.6.2.2
 PLEASE ALSO BARE IN MIND THE MIN RUNNINF
 TIME AT 100% FOR ALL OTHER EMERGENCY
 LOADS.
  
 32)NOTE: PLEASE SEE 450.13 FOR MIN.
 SIZING OF CONDCUTORS FROM GENERATOR TO
 THE FIRST MEANS OF OCP.
 PLEASE VERIFY IF THE GENERATOR COMES
 WITH THE BUILT IN OCP IN LEIU OF
 ADDITIONAL DISCONNECTS.
  
 33)NOTE: PLEASE SEE "WHITE-OUT" ON E4.0
 FOR EDR, EDP AND MDP.
 PLEASE SEE FS 471. THIS IS TO BE
 CORRECTED WHEN RE-PRINTING PLANS.
  
 34)NOTE: PLEASE SEE L4E IS SBEING SHOWN
 AS BEING FED WITH 3/0'S FROM A 225A CB.
 PLEASE SEE 310.16, 3/0'S ONLY RATED AT
 200A'S. PLEASE ADJUST FEEDERS.
 PLEASE ALSO CORRECT RISER DIAGRAM.
  
 35)NOTE: PLEASE SEE RISER APPEARS TO
 SHOWS ALL SEC'S'A ND CONDUITS BEING
 ROUTED OVERHEAD FROM FPL VAULT INTO MAIN
 EQUIPMENT. PLEASE KNOW, THAT NO MORE
 THAN 8' OF UNPROTECTED CONDUCTORS ARE
 PERMITTED "INSIDE" THE BLDG. THIS
 INCLUDES THE MAIN ELECTRICAL ROOM.
 230.70
 IF MORE THAN 8' OF CONDUCTORS, THEN
 THESE WILL ALSO BE REQUIRED TO BE
 "ENCASED" IN CONCRETE.
  
 36)NOTE: PLEASE SEE MDP WHICH LISTS OCP
 AND FEED TO PANEL L-4, HOWEVER NOTE FOR
 THIS FEEDER MENTIONS "NOT USED" ON
 LEGEND?
 PLEASE ADJUST AND CORRELATE.
  
 37)NOTE: PLEASE SEE POOL PANEL IS BEING
 SHOWN ON PANEL SCHEDULE L-4, HOWEVER
 THIS IS NOT ON RIER DIAGRAM.
  
 38)NOTE: PLEASE SEE A PANEL L2E IS BEING
 SHOWN ON RISER DIAGRAM COMING FROM PANEL
 EDR, HOWEVER EDR DOES NOT INDICATE THIS
 PANEL, OCP ETC.
 PLEASE ADJUST.
  
 39)NOTE: PLEASE SEE EDP, WILL BE
 REQUIRED TO CONTAIN A MCB FOR GROUPING
 OF MAINS. IF THE EM MAIN IS SHUT DOWN,
 THE GENERATOR WOULD THEN TURN ON, AND
 SEND POWER TOEDP.
 PLEASE KNOW, A SHUNT TRIP WILL NOT BE
 PERMITTED.
 230.76,230.79, 230.72
  
 40)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS @125%.
 LIGHTING/POOL MOTOR, LARGEST MOTORS ETC.
 215.3, 230.42
 THIS WILL AFFECT ALL LOADS ON ALL
 PANELS.
  
 41)NOTE: PLEASE VERIFY LOAD ON PANEL FOR
 UNITS OF 1150 SQ FT.
 LOAD SHOWN AFTER ALL DERATING, IS 124A'S
 WHICH IS VERLY CLOSE TO THE MAX LOAD OF
 125A BRKR WHICH SUPPLIES UNIT.
 PLEASE KNOW, SOME ROOM FOR FUTURE LOADS
 SHOWN BE ALLOTTED FOR UNITS AND SHOULD
 NOT BE DESIGNED THIS CLOSE.
 PLEASE VERIFY THE LOADS FOR APPLICANCES,
 DISH, DISP ETC.
 215.5
  
 42)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATER UNITS SHALL BE SIZED AT
 125%.422.13
 PLEASE ADJSUT OCP IN PANELS AND AWG
 WHERE NEEDED.
  
 43)NOTE: PLEASE SEE ANY COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON THE ELECTRICAL PLANS.
  
 44)NOTE: PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE KNOW, FURTHER INFORMATION MAY
 BE NEEDED FOR THE LOCATION MAIN
 ELECTRICAL ROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]