| 2005-12-25 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW. |
| | ********** UNSAT ************ |
| | |
| | SKYLINE LOFTS. |
| | |
| | 1)NOTE: PLEASE BE SURE PLANS MAKE |
| | REFERENCE TO CURRENT ELECTRICAL CODE IN |
| | EFFECT. NFPA-70 2002, 2002 NFPA-72 |
| | |
| | 2)NOTE: PLEASE BE SURE ALL SHEETS ARE |
| | SIGNED , DATED A ND SEALED AS REQUIRED |
| | UNDER FS 481.221, 471.025, AND 472.025 |
| | PLEASE SEE PD-1, -2 AND WS SHEETS WHICH |
| | SOME ARE SEALED PHOTO-COPIES AND SOME |
| | ARE ONLY PHOTOCOPIES AND NOT SEALED OR |
| | DATED. |
| | THIS SIS REQUIRED FOR ALL SHEETS AND FRO |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE MISSING LICENSING |
| | INFORMATION FOR M AND P SHEETS. PLEASE |
| | SEE FLORIDA ADMINISTRATIVE CODE WHICH |
| | REQUIRES THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON SAID TITLE BLOCK |
| | AS REQUIRED UNDER FS 471.023 |
| | THIS IS NOT A COMMENT FOR THE ELECTRICAL |
| | ENGINEERING FIRM. |
| | |
| | 4)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | UNITS. PLEASE SEE STRUCTUAL CALCULATION |
| | BOOK SUBMITTED INDICATE 103 UNITS, AND |
| | ELECTRICAL PLANS INDICATE 99? |
| | |
| | 5)NOTE: PLEASE OBTAIN A LETTER FROM MR. |
| | BILL HARTIGAN(FPL) WITH RESPECT TO THE |
| | APPROVAL OF THE FPL VAULT AS SHOWN. |
| | PLEASE SEE LOCATION AND SIZE IS TO BE |
| | DETERMINED BY FPL. |
| | IT IS NOT COMMON FOR THE VAULT TO BE |
| | LOCATED INSIDE BUILDING WITHOUT DIRECT |
| | ACCESS FROM OUTSIDE. |
| | |
| | 6)NOTE: PLEASE ALSO KNOW, IT WILL BE |
| | REQUIRED TO BE IN FURTHER DISCUSSION |
| | WITH THE FIRE MARSHAL'S OFFICE WITH |
| | RESPECT TO THE LOCATION AND ACCESS TO |
| | THE MAIN ELECTRICAL ROOM. IT APPEARS |
| | FIRE DEPT PERSONNEL WOULD HAVE TO ENTER |
| | THROUGH THE BLDG AND POSSIBLY THE |
| | PARKING GARAGE FOR SOME DISTANCE IN |
| | ORDER TO SHUT DOWN MAINS ELECTRICAL |
| | SYSTEMS? THIS WOULD NOT BE PERMITTED. A |
| | DIRECT ACCESS (4HR RATED) WOULD BE |
| | REQUIRED. THIS WILL REQUIRED FURTHER |
| | REVIEW. |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR |
| | ROOMS NOTED FOR ACCESS.(FIRE PUMP) |
| | |
| | 7)NOTE: PLEASE SEEMAIN ELECTRICAL |
| | ROOM, GENERATOR RM, FIRE PUMP RM, WILL |
| | REQUIRE DOORS TO OPEN OUTWARD. |
| | THESE ROOMS WILL ALSO BE REQUIRED TO |
| | HAVE PANIC HARDWARE ON DOORS. |
| | PLEASE PROVIDE NOTE ON PLANS FOR DOOR |
| | HARDWARE. |
| | 110.26, 90.4 |
| | |
| | 8)NOTE: PLEASE PROVIDE THE BUS-DUCT |
| | DETAIL AS SPECIFIED IN 368.6 FOR FLOOR |
| | PENETRATIONS. (4" CURBING ALL THE WAY |
| | AROUND). |
| | |
| | 9)NOTE: PLEASE PROVIDE COMPLETE |
| | PHOTOMETRICS FOR ALL CORIDORS AND EGRESS |
| | PATHS, STAIR TOWERS. |
| | PLEASE SEE 2003 NFPA-101 7.8 AND 7.9 |
| | WHICH REQUIRES A MIN OF 10 FT CANDLES |
| | FOR STAIRS UNDER NORMAL POWER AND A MIN |
| | OF 1 FT CANDLE UNDER EM POWER. |
| | PLEASE ALSO KNOW THAT BATTERY BACK UP |
| | FIXTURES OF SOME SORT WILL BE REQUIRED |
| | IN STAIR TOWERE AND CORRIDORS TO MEET |
| | THE MIN 1 FT CANDLE UNDER EM POWER. |
| | PLEASE SEE 7.9 WHICH REQUIRES THIS IN |
| | ALLEAVIATING IN AREA BEING IN TOTAL |
| | DARKNESS UPON THE TRIPPING OF A SINGLE |
| | DEVICE, SWITCH, BRKR ETC. |
| | |
| | 10)NOTE: PLEASE PROVIDE A BATTERY BACK |
| | UP FIXTURE IN ELECTRICAL ROOMS, GEN RMS, |
| | FIRE PUMP RM, AND FIRE COMMAND ROOM. |
| | IT IS KNOWN SOME OF THESE ROOMS CONTAIN |
| | SOME ALREADY. |
| | 700.16,LS 101 7.8, 7.9.700.12E |
| | |
| | 11)NOTE: PLEASE SEE FIRE REVIEW NOTES |
| | WITH RESPECT TO FIRE COMMAND ROOM AND |
| | MISSING EQUIPMENT AS REQUIRED UNDER |
| | HIGH-RISEREQUIREMENTS IN 11.9 LS 101 |
| | PLEASE ALSO VERIFY WITH FIRE MARSHAL'S |
| | OFFICE THE MIN SIZING OF ROOM WHICH MAY |
| | BE REQUIRED. PLEASE SEE SPACE ABOUT |
| | THESE CONTROL PANELS SEEM TO BE LIMITTED |
| | ON ANGLES OF ROOMS AND WITH OTHER ITEMS |
| | TO BE INSTALLED THIS MAY BE AN ISSUE. |
| | |
| | 12)NOTE: PLEASE SEE FIRE REVIEW NOTES |
| | PERTAINING TO ALLEY WAY IN REAR OF BLDG. |
| | PLEASE SEE 14' ALLEY SHOWN, IS THIS |
| | PUBLIC? PRIVATE ? |
| | IF PRIVATE PLEASE SEE 7.8,7.9 LS 101, |
| | WHICH REQUIRES ILLUMINATION TO THE |
| | PUBLIC RIGHT OF WAY. |
| | PLEASE ALSO SEE ORIG FIRE NOTE WITH |
| | RESPECT TO VEHICULAR TRAFFIC. |
| | |
| | 13)NOTE: PLEASE SEE 620.23 REQUIRE STHE |
| | LTS AND RECEPTS IN THE ELEVATOR MACHINE |
| | ROOM TO BE ON A DEDICATED CIRCUIT. THIS |
| | NOTED ON PANEL SCHEDULE, HOWEVER THE |
| | CIRCUITING ON PLANS SEEMS TO BE MISSING? |
| | |
| | 14)NOTE: PLEASE SEE 110.26 FOR ALL |
| | ELECTRICAL ROOMS SHOWN. |
| | PLEASE SEE ALL MIN CLEARENCES WILL BE |
| | REQUIRED , EVEN FOR BUS-DUCT. PLEASE SEE |
| | REDLINED PLANS FOR LOCATIONS OF CONCERN. |
| | |
| | 15)NOTE: PLEASE PROVIDE A DETAIL FOR THE |
| | MIN DISCONNECTING MEANS FOR ROOF TOP |
| | CU'S. THIS DETAIL MAY BE "TYPICAL". |
| | 440.11 |
| | |
| | 16)NOTE: PLEASE SEE THAT THE |
| | PHOTOMETRICS SHOWN FOR THE POOL AREA |
| | MUST BE SUBMITTED FOR REVIEW AND |
| | STAMPING BY THE PALM BEACH COUNTY HEALTH |
| | DEPT. |
| | PLEASE KNOW, THE POOL IS REQUIRED TO BE |
| | UNDER A SEPARATE PERMIT. |
| | |
| | 17)NOTE: PLEASE PROVIDE A NOTE ON |
| | ROOFTOP PLANS WITH RESPECT TO ANY |
| | LIGHTNING PROTECTION SYSTEM WHICH MAY BE |
| | PROPOSED. |
| | PLEASE MAKE NOTE TO ANY SYETM SHALL |
| | COMPLY COMPLETELY WITH NFPA-780 WITH |
| | WORDS TO THAT AFFECT. |
| | |
| | 18)NOTE:PLEASE SEE UNITS WHICH ARE |
| | MISSING COUNTERSPACE GFI RECEPTS AS |
| | REQUIRED PER 210.52C1. |
| | SOME UNITS ARE SHOWING GFI'S WHERE |
| | COUNTERS AMY BE LESS THAN 12" AND SOME |
| | ARE SHOWN, YET OTHERS WHICH ARE MORE |
| | THAN 12" DO NOT CONTATIN ANY. |
| | PLEASE SEE MANY UNITS SEEM TO HAVE THESE |
| | RECEPTS LOCATED BEHIND THE FRIG?? |
| | PLEASE MANY OF THESE HAVE BEEN REDLINED |
| | ON PLANS. |
| | ** PLEASE ALSO SEE RELDINED UNIT WHERE |
| | MICRO/HOOD CIRCUIT IS MISPLACED WITH |
| | SMALL APPL.(L101) |
| | |
| | 19)NOTE: PLEASE SEE SOME CIRCUITING |
| | MISSING IN UNITS FOR DEVICES. |
| | 215.5 PLEASE COMPLETE. |
| | |
| | 20)NOTE: PLEASE SEE RECEPTS MISSNG FOR |
| | WALL SPACE PER 210.52. MANY OF THESE |
| | HAVE BEEN REDLINED. |
| | PLEASE SEE MOST ALL UNITS ARE MISSING |
| | DOORS, SO SOME MAY BE REQUIRED FURTHER |
| | ONCE DOOR OVERLAY HAS BEEN CORRECTED. |
| | PLEASE ALSO SEE AREAS WHICH APPEAR TO |
| | SHOW FIXED GLASS PANELS/WALLS WHICH ARE |
| | CONSIDERED WALL SPACE AND WOULD REQUIRE |
| | A RECEPT WITHIN 6' OF DOORWAY. |
| | SEE REDLINES. |
| | |
| | 21)NOTE: PLEASE SEE LOFT UNITS NEED TO |
| | INDICATE THE MEANS OF EGRESS CONTROLL |
| | FOR LIGHTING LEADING TO FLOOR ABOVE. |
| | SOME SHOW "S" BUT NO S/3". 210.70 ETC. |
| | |
| | 22)NOTE: PLEASE SEE MISSING FIRST LEVEL |
| | OF LOFT 6/7? 2.12 |
| | NO REVIEW. |
| | |
| | 23)NOTE: PLEASE SEE 410.8 FOR MIN |
| | CLEARENCE REQUIRED FOR CLOSETLTS. |
| | REDLINED. |
| | |
| | 24)NOTE: PLEASE SEE MISSING SD'S OUTSIDE |
| | ALL SLEEPING RMS AS REQUIRED PER NFPA-72 |
| | 11.5.1.1 |
| | PLEASE ALSO SEE FBC 905 |
| | PLEASE ALSO PROVIDE A NOTE ON ALL UNIT |
| | SHEETS WHICH REFERENCES NFPA-72 11.8.3.5 |
| | PLEASE SEE ALL SD'S ARE REQUIRED TO BE A |
| | MIN OF 3' FROM BATH AND KITCHEN DOOR'S, |
| | 3' FROM SUPPLYAND 5' FROM RETURN AIR |
| | GRILLES. |
| | PLEASE ALSO SEE SD'S ARE ALSO REQUIRED |
| | TOBE A MIN OF 20' FROM COOKING |
| | APPLIANCES, WITH EXCEPTIONS. |
| | |
| | 25)NOTE: PLEASE SEE UNIT 203, MASTER |
| | BATH GFI WHICH IS SHOWN ON SMALL |
| | APPLIANCE CIRCUIT. PLEASE SEE 210.52B1 , |
| | NO OTHERS PERMITTED. |
| | THIS APPEARS TO BE A MISPRINT AS, THE |
| | BATH GFI CIRCUIT IS #2. |
| | |
| | 26)NOTE: PLEASE SEE 210.52B1 WHICH DOES |
| | NOT PERMIT ANY OTHER OUTLETS/DEVICES ON |
| | THE ONE OR MORE SMALL APPL CIRCUITS. |
| | PLEASE SEE SOME DINING AREAS APPEAR TO |
| | CONTAIN OTHER GEN LT CIRCUIT. |
| | PLEASE DEFINE DINING AREA. |
| | |
| | 27)NOTE: PLEASE SEE NOTE #29 ON RISER |
| | INDICATES SD'S TO BE WIRED TO THE |
| | BATH/KITCHEN LIGHTING CIRCUIT?? |
| | PLEASE VERIFY THIS AS THE #'S DO NOT |
| | MATCH UP. |
| | THIS IS PERMITTED, HOWEVER THEN THE |
| | KITCHEN/BATH LTS WOULD ALSO BE ARC |
| | FAULT.210.12 |
| | |
| | 28)NOTE: PLEASE SEE REDLINED METER |
| | CENTER CALCULATIONS, PLEASE CORRLEATE |
| | ALL . 532/538 ETC |
| | |
| | 29)NOTE: PLEASE SEE THE FEEDER FOR THE |
| | FIRE PUMP FROM THE GENERATOR SHALL ALSO |
| | BE ENCASED IN CONCRETE UNLESS "OUTSIDE" |
| | THE BLDG.695.6, LS 101 9.3 |
| | |
| | 30)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | CUT/SPEC SHETS FOR GENERATOR, ATS, FIRE |
| | PUMP, FIRE PUMP CONTROLLER AND SUB-BASE |
| | FUEL TANK. PLEASE KNOW, REVIEW FOR MANY |
| | ITEMS FOR CODE COMPLIANCE CAN NOT BE |
| | DONE AT THIS TIME AS NONE WERE |
| | SUBMITTED. |
| | PLEASE ALSO VERIFY AND NOTE SETTING FOR |
| | LOCKED ROTOR PER 695.4B1 |
| | PLEASE SEE NFPA-20 CHAPTERS 9 AND 10. |
| | PLEASE KNOW, THE SUB-BASE FUEL TANK WILL |
| | BE REVIEWED BY OTHERS. |
| | |
| | |
| | 31)NOTE: PLEASE SEE NFPA-20 WHICH |
| | REQUIRES A MIN OF 8HRS RUNNING TIME AT |
| | 100% LOAD FOR THE FIRE PUMP. |
| | 9.6.2.2 |
| | PLEASE ALSO BARE IN MIND THE MIN RUNNINF |
| | TIME AT 100% FOR ALL OTHER EMERGENCY |
| | LOADS. |
| | |
| | 32)NOTE: PLEASE SEE 450.13 FOR MIN. |
| | SIZING OF CONDCUTORS FROM GENERATOR TO |
| | THE FIRST MEANS OF OCP. |
| | PLEASE VERIFY IF THE GENERATOR COMES |
| | WITH THE BUILT IN OCP IN LEIU OF |
| | ADDITIONAL DISCONNECTS. |
| | |
| | 33)NOTE: PLEASE SEE "WHITE-OUT" ON E4.0 |
| | FOR EDR, EDP AND MDP. |
| | PLEASE SEE FS 471. THIS IS TO BE |
| | CORRECTED WHEN RE-PRINTING PLANS. |
| | |
| | 34)NOTE: PLEASE SEE L4E IS SBEING SHOWN |
| | AS BEING FED WITH 3/0'S FROM A 225A CB. |
| | PLEASE SEE 310.16, 3/0'S ONLY RATED AT |
| | 200A'S. PLEASE ADJUST FEEDERS. |
| | PLEASE ALSO CORRECT RISER DIAGRAM. |
| | |
| | 35)NOTE: PLEASE SEE RISER APPEARS TO |
| | SHOWS ALL SEC'S'A ND CONDUITS BEING |
| | ROUTED OVERHEAD FROM FPL VAULT INTO MAIN |
| | EQUIPMENT. PLEASE KNOW, THAT NO MORE |
| | THAN 8' OF UNPROTECTED CONDUCTORS ARE |
| | PERMITTED "INSIDE" THE BLDG. THIS |
| | INCLUDES THE MAIN ELECTRICAL ROOM. |
| | 230.70 |
| | IF MORE THAN 8' OF CONDUCTORS, THEN |
| | THESE WILL ALSO BE REQUIRED TO BE |
| | "ENCASED" IN CONCRETE. |
| | |
| | 36)NOTE: PLEASE SEE MDP WHICH LISTS OCP |
| | AND FEED TO PANEL L-4, HOWEVER NOTE FOR |
| | THIS FEEDER MENTIONS "NOT USED" ON |
| | LEGEND? |
| | PLEASE ADJUST AND CORRELATE. |
| | |
| | 37)NOTE: PLEASE SEE POOL PANEL IS BEING |
| | SHOWN ON PANEL SCHEDULE L-4, HOWEVER |
| | THIS IS NOT ON RIER DIAGRAM. |
| | |
| | 38)NOTE: PLEASE SEE A PANEL L2E IS BEING |
| | SHOWN ON RISER DIAGRAM COMING FROM PANEL |
| | EDR, HOWEVER EDR DOES NOT INDICATE THIS |
| | PANEL, OCP ETC. |
| | PLEASE ADJUST. |
| | |
| | 39)NOTE: PLEASE SEE EDP, WILL BE |
| | REQUIRED TO CONTAIN A MCB FOR GROUPING |
| | OF MAINS. IF THE EM MAIN IS SHUT DOWN, |
| | THE GENERATOR WOULD THEN TURN ON, AND |
| | SEND POWER TOEDP. |
| | PLEASE KNOW, A SHUNT TRIP WILL NOT BE |
| | PERMITTED. |
| | 230.76,230.79, 230.72 |
| | |
| | 40)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS @125%. |
| | LIGHTING/POOL MOTOR, LARGEST MOTORS ETC. |
| | 215.3, 230.42 |
| | THIS WILL AFFECT ALL LOADS ON ALL |
| | PANELS. |
| | |
| | 41)NOTE: PLEASE VERIFY LOAD ON PANEL FOR |
| | UNITS OF 1150 SQ FT. |
| | LOAD SHOWN AFTER ALL DERATING, IS 124A'S |
| | WHICH IS VERLY CLOSE TO THE MAX LOAD OF |
| | 125A BRKR WHICH SUPPLIES UNIT. |
| | PLEASE KNOW, SOME ROOM FOR FUTURE LOADS |
| | SHOWN BE ALLOTTED FOR UNITS AND SHOULD |
| | NOT BE DESIGNED THIS CLOSE. |
| | PLEASE VERIFY THE LOADS FOR APPLICANCES, |
| | DISH, DISP ETC. |
| | 215.5 |
| | |
| | 42)NOTE: PLEASE SEE MIN OCP FOR WATER |
| | HEATER UNITS SHALL BE SIZED AT |
| | 125%.422.13 |
| | PLEASE ADJSUT OCP IN PANELS AND AWG |
| | WHERE NEEDED. |
| | |
| | 43)NOTE: PLEASE SEE ANY COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY HAVE AN AFFECT |
| | ON THE ELECTRICAL PLANS. |
| | |
| | 44)NOTE: PLEASE MAKE NOTE FOR ALL MIN |
| | FAIR HOUSING ACT REQUIREMENTS FOR DEVICE |
| | HEIGHTS. |
| | 24 CFR 100.205 |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | ** PLEASE KNOW, FURTHER INFORMATION MAY |
| | BE NEEDED FOR THE LOCATION MAIN |
| | ELECTRICAL ROOM. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |