Plan Review Notes
Plan Review Notes For Permit 05091467
Permit Number 05091467
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
 FHA 98 DESIGN MANUAL
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 4.)FBC* 105.13.1SPECIAL INSPECTOR.
 A STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQ FT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING
 PURPOSES.ALSO, PLEASE ARRANGE WITH
 HAROLD PISKURA (INSPECTION SERVICES
 MANAGER, 561-805-6711) A MEETING
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR,
 AND ENGINEER.
  
 5.)IF THE DWELLING UNITS ARE TO BE
 SOLD AS CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 6.)DOCUMENTS PREPARED BY AN ENGINEER
 ARE TO HAVE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.THE CIVIL SHEETS ARE
 LACKING A CA NUMBER AND PRINTED LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT.ALSO, THE SIGNATURE APPEARS
 TO BE A STAMP.ORIGINAL "WET" SIGNATURE
 REQUIRED AS PER FBPE.THE STRUCTURAL
 CALCS DO NOT HAVE THE COFA NUMBER FOR
 THE ENGINEER.CHECK ALL SHEETS,
 CALCULATIONS AND SPECIFICATIONS FOR
 TITLE BLOCK COMPLIANCE PRIOR TO
 RESUBMITTAL.
  
 7.)THE STRUCTURAL ENGINEER'S AND FIRE
 PROTECTION ENGINEER'S SEALS ARE OLD
 SEALS.PLEASE NOTE THAT THE SEAL SHOULD
 STATE "LICENSE" RATHER THAN
 "CERTIFICATE" IF SEALED AFTER DECEMBER
 31, 2005.THIS COMMENT APPLIES TO
 ANYTHING SEALED AFTER THIS DATE ONLY
 (FUTURE SUBMITTALS).
  
 8.)ARCHITECT BUSINESS NUMBER FOR
 COLLADO AND PARTNERS, INC. IS REQUIRED
 ON ALL SHEETS, FAC61G1-16.002, 003.
  
 9.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 10.)PROVIDE A SCHEDULE OF OPENINGS
 WITH DESIGN PRESSURES, OR INDICATE
 DESIGN PRESSURES ON THE ELEVATIONS.
  
 11.)THE STRUCTURAL CALCS PROVIDE A
 BUILDING HEIGHT OF 70 ON SHEET ED4,
 SECTION 2.
  
 12.)THE STRUCTURAL CALCS, SECTION 5,
 CD74, REFERS TO ACI 318-95 FOR CODE.
 THIS REFERENCE IS NOT THE CURRENT
 STANDARD, FBC35.
  
 13.) FBC 13-103.0ENERGY CODE
 COMPLIANCE SHALL BE DEMONSTRATED BY
 SUBMITTAL OF APPROPRIATE CODE COMPLIANCE
 FORMS.
  
 14.) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 15.)PROVIDE A SURVEY FOR THIS
 PROPERTY.
  
 16.)SOME OF THE SHEETS SUBMITTED WERE
 NOT SEALED.ALL SHEETS ARE TO BE
 SIGNED, SEALED, AND DATED ORIGINALS.
 ALL SEALS ARE TO BE LEGIBLE.
  
 17.)PLEASE REVISE A-1.0 TO INCLUDE THE
 GOVERNING CODE WHICH IS APPARENTLY
 FBC2001 (HANDWRITTEN AND NOT INITIALED
 BY ARCHITECT).NEITHER THE ARCHITECT
 NOR ENGINEER DECLARED GOVERNING CODE.
 THIS REVIEW HAS BEEN DONE UNDER THE
 FBC2001 CODE.
  
 18.)SHEET S1 STATES IN VARIOUS PLACES
 THAT THIS HAS BEEN DESIGNED TO HVHZ AND
 ACI318 99.CITY OF WEST PALM BEACH IS
 NOT IN THE HIGH VELOCITY HURRICANE ZONE
 AND THE CORRECT ACI STANDARD IS 318 02,
 FBC35.ALSO THERE ARE INCORRECT
 REFERENCES ON A-G.1.CHECK ALL
 REFERENCES AND REVISE AS NECESSARY.
  
 19.)SHEETS REFERRED TO ON THE INDEX
 SHEET, A-G.0, ARE NOT IN THE PLAN.FOR
 INSTANCE, S7.5, 7.6, 7.7 ARE NOT IN THE
 PLAN.S8.1, WIND PRESSURES, IS REFERRED
 TO FOUR TIMES ON THE INDEX BUT IS NOT IN
 THE PLAN.THIS SHEET IS NECESSARY TO
 DETERMINE CODE COMPLIANCE.PLEASE
 CONFIRM THAT ALL SHEETS NECESSARY ARE IN
 THE PLAN AND REVISE THE INDEX SHEET TO
 CORRELATE.THE LIST REFERRED TO ABOVE
 ARE NOT A COMPLETE LIST; OTHER SHEETS
 ARE MISSING.
  
 20.)ELEVATORS ARE TO CONFORM TO ASME
 A17.1, FBC3001.1.PLEASE ADD TO THE
 NOTE, A-G.2, ITEM 14, CONVEYING SYSTEMS,
 OR ANOTHER APPROPRIATE SHEET.
  
 21.) FBC 3003.4.1STRETCHER ACCESSIBLE
 ELEVATOR.AT LEAST ONE PASSENGER
 ELEVATOR SHALL ACCOMMODATE AN AMBULANCE
 STRETCHER 76IN LONG AND 24IN WIDE IN THE
 HORIZONTAL POSITION.THIS ELEVATOR
 SHALL BE IDENTIFIED BY SIGNAGE.AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 22.)A1.0 DECLARES THE OCCUPANCY AS R2
 WITH AREA CALCULATIONS FOR THE
 RESIDENTIAL UNITS.INCLUDE AREA
 CALCULATIONS AND OCCUPANCY (IF
 APPLICABLE) FOR THE OTHER AREAS OF THE
 BUILDING SUCH AS THE PARKING GARAGE,
 COMMON AREAS, MECHANICAL ROOMS, ETC.
 BUILDING VALUATION CANNOT BE DETERMINED.
  
 23.)DECLARE BUILDING HEIGHT ON SHEET
 A1.0, FBC412.BASED ON ELEVATIONS
 PROVIDED, BUILDING HEIGHT EXCEEDS 75FT.
  
 24.)SHOW REQUIRED OCCUPANCY SEPARATION
 FBC TABLE 704.1.
  
 25.)THE MEZZANINE LEVEL WITH PARKING
 AND AN ELEVATOR LOBBY DOES NOT COMPLY
 WITH THE DEFINITION OF MEZZANINE, FBC
 CHAPTER2, FBC 503.2.3.REVISE THE
 DESIGNATION OF THIS AREA AND FLOOR.
  
 26.)ALL ELEVATORS ON ALL FLOORS SHALL
 OPEN INTO ELEVATOR LOBBIES WHICH ARE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 1 HR FIRE RESISTANT
 CONSTRUCTION WITH 20MINUTE OPENING
 PROTECTIVES, FBC412.6.1.THE LOBBY
 SHOWN ON THE MEZZANINE LEVEL DOES NOT
 COMPLY, ROOF LEVELS DO NOT HAVE A LOBBY.
  
 27.)PROVIDE AREA CALCULATIONS FOR THE
 UNIT MEZZANINES TO SHOW COMPLIANCE WITH
 FBC503.2.3.2.
  
 28.)PROVIDE A LIFE SAFETY PLAN.
  
 29.)A2.1, EMERGENCY STAIRS 1
 DISCHARGES INTO THE PARKING GARAGE.SEE
 FBC1001.1.3, 1001.1.4.DISCHARGING INTO
 THE PATH OF VEHICULAR TRAFFIC WOULD BE
 CONSIDERED HAZARDOUS CONDITIONS.
  
 30.)A2.2, A6 SHOW VENTILATION DUCTS
 THROUGH THE EXIT STAIR 1.SEE
 FBC1006.1.3.1.OTHER SHEETS MAY BE
 AFFECTED.PLEASE REVISE.
  
 31.)A1.0, % OF OPENINGS, STATES THAT
 THE ALLEY SIDE HAS A 1FT SETBACK.THE
 SITE PLAN SHOWS 6IN.PLEASE MAKE THE
 TWO CONSISTENT.
  
 32.)A1.0, % OF OPENINGS, STATES THAT
 THE WEST SIDE HAS A 4IN SETBACK, 6IN IS
 SHOWN.PLEASE MAKE THE TWO CONSISTENT.
  
 33.)SHOW THE DISTANCE OF THE BUILDING
 TO THE PROPERTY LINE, DATURA SIDE, A1.0.
  
 34.)SHEET A2.10, A4.2, AND OTHER
 SHEETS REFER TO ALUMINUM RAILING
 DETAILS, SHEET AX.X.PLEASE PROVIDE
 DETAILS FOR ALL GUARDRAILS AS WELL AS
 DESIGN CRITERIA.CHECK ALL DETAILS.
  
 35.) FBC 1608.2, PROVIDE DESIGN CRITERIA
 FOR BOTH THE HANDRAILS AND GUARDRAILS.
  
 36.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISHES, FBC TABLE 803.3.
  
 37.)PROVIDE A DETAIL FOR THE
 MECHANICAL STANDS, FBC1511.7.
  
 38.)FBC1007.5.5, 11-4.94(2), THE
 HANDRAIL WILL EXTEND AT LEAST 12IN
 HORIZONTALLY BEYOND THE TOP RISER OF A
 FLIGHT.ENDS OF HANDRAILS SHALL BE
 EITHER ROUNDED OR RETURNED SMOOTHLY TO
 FLOOR, WALL OR POST, FBC11-4.94(6),
 FIGURE 11-19.A6.0, A6.1, ALSO OTHER
 DETAILS MAY BE AFFECTED; PLEASE CHECK
 ALL DETAILS.
  
 39.)LOFT UNIT STAIRS, A4.1, AT THE
 BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE DEPTH OF ONE
 TREAD FROM THE BOTTOM RISER,
 FBC1007.5.5.
  
 40.)A3.5 SHOWS A DESIGNATION AS LEVEL
 3 TO 7, A3.6 IS LEVEL 7 PH.SHOULDN'T
 THIS BE LEVEL 8PH?
  
 41.)A3.6.5 IS LEVEL 7PH, A DUPLICATE
 OF A3.6.ACCORDING TO THE INDEX, THIS
 SHEET SHOULD BE LEVEL 8PH2.
  
 42.)SHEETS A2.5, A2.6, A2.65 DO NOT
 PROVIDE DOOR DESIGNATIONS TO CORRELATE
 WITH THE DOOR SCHEDULE.
  
 43.)WHAT WILL BE STORED IN THE STORAGE
 ROOMS?INDICATE THAT IT IS NONHAZARDOUS
 OR DECLARE AN OCCUPANCY AND SHOW
 REQUIRED PROTECTION IF APPLICABLE,
 FBC704.1.1.2(4).
  
 44.)THE TRASH CHUTE IS TO COMPLY WITH
 NFPA82.SHOW THE 6IN REQUIREMENT OF
 3-2.4.3.1 ON THE TRASH CHUTE SECTION.
  
 45.)COMBUSTIBLES NOT ALLOWED IN
 CONCEALED SPACES, FBC707.1.A7.7
 SPECIFIES PT WOOD BACKING FOR CABINETS.
 A6.7 REFERS TO PT FURRING; NOTE THE
 REQUIREMENT OF FBC803.9.1 FOR FURRING.
 CHECK ALL DETAILS AND SPECIFICATIONS.
  
 46.)A8.0, DOOR FIRE RATING SHOULD BE
 IN HOURS RATHER THAN A LETTER RATING,
 FBC705.1.3.2.1.
  
 47.)A8.0 REFERS TO SFBC.GOVERNING
 CODE IS FBC2001.REVISE THE CODE
 REQUIREMENT FROM SFBC3706 TO
 FBC705.1.3.4.PLEASE CHECK ALL
 REFERENCES TO COMPLY WITH GOVERNING
 CODE.
  
 48.)PROVIDE CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS, FBC1503.
 PLEASE ALSO SEE PLUMBING REVIEW NOTES
 REGARDING INCONSISTENCIES IN SCUPPER
 DETAILS.
  
 49.)THE DETAILS ON A7.0 ARE MARKED
 A7.4.
  
 50.)THERE ARE TWO DIFFERENT SHEETS
 LABELED A7.7.
  
 51.)WL2185, A7.1, REFERS TO 3A
 OPTIONAL PACKING MATERIAL.THE UL
 ASSEMBLY DOES NOT INDICATE THIS AS
 OPTIONAL.3B SPECIFIES A MINIMUM OF
 1/2IN THICKNESS, UL ASSEMBLY SPECIFIES A
 MINIMUM OF 5/8IN.WL 2159 ALSO
 SPECIFIES A THICKNESS WHICH DOES NOT
 COMPLY WITH THE CURRENT UL LISTING.
 CHECK ALL UL ASSEMBLY AND SYSTEM
 DETAILS.ALL SPECIFICATIONS SHOULD BE
 CLEAR AND ALL INCLUSIVE FOR
 CONSTRUCTION.
  
 52.)A7.3 PARKING DETAILS DO NOT COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS.
 PLEASE SEE ATTACHED.
  
 53.)DETAIL 10 A7.4 ON SHEET A7.0
 REFERS TO SFBC.
  
 54.)DOOR G05 IS TO BE FIRE RATED, FBC
 TABLE 704.1.
  
 55.)SPECIFY A DOOR TYPE AT RESIDENT?S
 STORAGE, A2.3.
  
 56.)M2.4 SHOWS EXHAUST AIR DUCTS ON
 THE EAST WALL.EVERY EXTERIOR WALL
 WITHIN 15FT OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH APPROVED OPENING
 PROTECTIVES, FBC705.1.1.2.
  
 57.)M2.4, A2.13 OPENINGS FOR
 VENTILATION ARE ALSO SHOWN ON THE SOUTH
 PROPERTY LINE.CLEARLY INDICATE FIRE
 RESISTANCE RATING REQUIREMENTS OF FBC
 TABLE 600 ON THE PLANS AND SHOW
 COMPLIANCE.EVERY EXTERIOR WALL WITHIN
 15FT OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH APPROVED OPENING
 PROTECTIVES, FBC705.1.1.2.
  
 58.)A2.25, ACTIVITY ROOM HAS WINDOWS
 WHICH ARE REQUIRED TO BE PROTECTED,
 FBC705.1.1.2.CLEARLY NOTE FIRE RATING
 REQUIREMENTS ON THE PLAN TO AVOID
 CONFUSION IN THE FIELD.
  
 59.)M2.2 AND M2.3 SHOW FRESH AIR
 INTAKES WHICH ARE REQUIRED TO BE
 PROTECTED, FBC705.1.1.2.ALSO SEE
 FBC705.1.1.4, PROTECT AGAINST EXTERIOR
 FIRE EXPOSURE.PLEASE ADDRESS.
  
 60.)PROVIDE PRODUCT APPROVALS FOR ALL
 COMPONENTS AND CLADDING.ANY PRODUCT
 APPROVALS NOT REVIEWED FOR CODE
 COMPLIANCE PRIOR TO PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS FOR THOSE ITEMS
 WITH SEPARATE FEES BASED ON VALUE.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED IN ADDITION TO THE EVALUATION
 REPORT, FAC9B72.SEE
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 61.)FHA SECTION 5, ACCESSIBLE ENTRANCE
 REQUIRED FOR THE GROUND FLOOR UNITS.
 SEE ALSO SECTION 3, 100.205(D) EXAMPLE
 (1).FOR THE POWDER ROOM ALSO SEE
 REQUIREMENT 7, USABLE KITCHENS AND
 BATHROOMS.
  
 62.)DOORS T10, T12 DO NOT MEET THE
 MIMIMUM CLEARANCE OF 32 IN, FHA
 GUIDELINES SECTION 5 REQUIREMENT 3,
 USABLE DOORS.SEE PAGE 7.17, DESIGN
 MANUAL.
  
 63.)THE SLIDING GLASS DOORS TO THE
 BALCONIES ARE TO BE USABLE, FHA
 GUIDELINES SECTION 5 REQUIREMENT 3.
 CONFIRM THAT THE PRODUCT YOU SELECT
 COMPLIES WITH THE 32IN NOMINAL WIDTH.
  
 64.)PROVIDE A DETAIL FOR GRAB BAR
 BACKING, CHAPTER 6 OF DESIGN MANUAL.
  
 65.)WHEN RESUBMITTING, PLEASE CHANGE
 ONLY SHEETS WHICH HAVE CHANGED AND
 SUBMIT OLD SHEETS SEPARATELY.TO
 EXPEDITE PLAN REVIEW, CLEARLY CLOUD ALL
 CHANGES AND PROVIDE A RESPONSE LETTER
 EXPLAINING HOW EACH ITEM HAS BEEN
 ADDRESSED.