| Date |
Text |
| 2006-06-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | CITY WPB CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. ALL ARCHITECTURAL SHEETS: THE |
| | PERSONAL SEAL, SIGNATURE, AND THE DATE |
| | THE ARCHITECT SHALL APPEAR ON ALL |
| | DOCUMENTS TO BE FILED FOR PUBLIC RECORD. |
| | THE SIGNATURE IS A "STAMP OF THE |
| | SIGNATURE" AND AS SUCH IS NOT APPROVED. |
| | THERE IS NOT DATE ON THE SEAL WHEN IT |
| | WAS AFFIXED TO THE PLANS. FAC |
| | 61G1-16.003 61G1-16.004(5) & FS 481.2055 |
| | ***RESPONSE NOTED, BUT THE DATE THE SEAL |
| | AND SIGNATURE ARE AFFIXED TO THE PLANS |
| | SHALL BE ON THE SEAL. |
| | |
| | 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS |
| | PER REQUIREMENTS #6 & 7B FHA DESIGN |
| | MANUAL. THE CLEAR FLOOR SPACE FOR THE |
| | SHOWERS SHALL BE PARALLEL WITH THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL. |
| | SEE PAGE 7.56 FHA DESIGN MANUAL. |
| | ***RESPONSE NOTED, BUT NO OTHER FIXTURE |
| | MAY OVERLAP THE CLEAR FLOOR SPACE AT THE |
| | SHOWERS. THIS INCLUDES THE W/C'S, LAV |
| | VANITIES, OR SHOWER DOORS. |
| | |
| | 9. SHTS A-801 THRU A-802C & A-808 ALL |
| | "TH" UNITS: PRIMARY LEVEL TO BE COVERED |
| | PER FHA DESIGN MANUAL. SHOW THE FLOOR |
| | PLAN FOR EACH TYPE OF "TH" UNIT WITH |
| | CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43 |
| | & 7.47. ALSO SHOW MAX HEIGHT FOR LAV AT |
| | 34" REQUIRED ON PAGE 7.52 FHA DESIGN |
| | MANUAL. |
| | ***RESPONSE NOTED, BUT THE W/C CAN NOT |
| | BE IN THE CLEAR FLOOR SPACE FOR THE |
| | SHOWER. PAGE 7.57 |
| | |
| | 10. SHTS A-803 THRU A-807A INDICATE |
| | SPECIFICATION "A" OR "B" FOR EACH UNIT - |
| | BATHROOM AS REQUIRED ON PAGES 7.34 & |
| | 7.44 OF THE FHA DESIGN MANUAL. |
| | ***RESPONSE NOTED, BUT THE SPECIFICATION |
| | FOR EACH UNIT HAS NOT BEEN FOUND. |
| | |
| | 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS |
| | P1.1, P5.1.4, P5.1.5, & P6.1.4 ARE NOT |
| | SHOWN ON THE INDEX.- SHTS P2.5.1 & |
| | P2.5.2 DO NOT REFLECT THE SHEETS |
| | SUBMITTED. - SHTS P2.6.1, P2.6.2, |
| | P2.7.1, P2.7.2, P2.8.1, P2.8.2, P3.6.1 |
| | WERE NOT SUBMITTED. - SHT P5.1.3 DOES |
| | NOT REFLECT THE INDEX, AND P5.1.5 & |
| | P5.1.6 SHOWN AS STORM, BUT SHEETS |
| | INDICATE SANT. SYSTEM. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE NOTED, BUT SHTS |
| | P2.5.1 & P2.5.2 DO NOT REFLECT THE |
| | PLUMBING SHEET INDEX FOR SHEET |
| | IDENTIFICATION, AND SHT P3.6.1 IS NOT |
| | NUMBERED CORRECTLY. |
| | |
| | 15. P2.1.2 FLOOR DRAINS IN THE TRASH |
| | ROOM/AREA AND IN THE CORRIDOR SHALL BE |
| | VENTED. SECTION 901.2.1. |
| | ***NO COMMENT RESPONSE NOTED, FLOOR |
| | DRAINS ARE NOT VENTED. |
| | |
| | 22. SHT FOR 7TH FLOOR WEST SECTION |
| | DRAINAGE PLAN (P2.6.2). CONDENSATE FOR |
| | RESIDENT STORAGE & CONDO UNIT C-1(730) |
| | SHOWS PLAN NOTE #2. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE NOTED, CONDENSATE |
| | NOTE FOR RESIDENT STORAGE UNCHANGED. |
| | |
| | 23. SHT P2.7.1 SHOW THE LOCATION FOR ALL |
| | VENTS THRU ROOF AND INDICATE RISER |
| | NUMBER FOR EACH. |
| | ***NO COMMENT RESPONSE NOTED. NO VENTS |
| | THRU ROOF LOCATED. |
| | |
| | |
| | 29. SHT INDICATING WATER SUPPLY PLAN 5TH |
| | FLOOR "NORTH" SECTION, PREVIOUS SHEETS |
| | WERE DESIGNATED AS "EAST" OR "WEST". |
| | THIS IS ALSO THE SECOND SHEET NUMBERED |
| | P3.5.1. - INDICATE WHAT DESIGNATION WSC2 |
| | IS FOR. - NOTE STATES "SEE UNIT LAYOUTS |
| | ON SHEET P4.1". SHT P4.1 NOT SUBMITTED. |
| | SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE NOTED, BUT NOW |
| | THERE ARE TWO SHEETS WITH THE NUMBER |
| | P3.5.2. THE FIRST SHOULD BE P3.5.1. |
| | PLEASE CLARIFY. |
| | |
| | 30. FIRST SHT P3.6.2 INDICATES WATER |
| | SUPPLY PLAN 6TH FLOOR "SOUTH" SECTION. |
| | EAST AND WEST WERE INDICATED PRIOR TO |
| | THIS. 2ND SHT WITH THE SAME NUMBER |
| | INDICATES "WEST" SECTION. PLEASE |
| | CLARIFY.SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE, PLANS STILL HAVE |
| | TWO SHEETS NUMBERED P3.6.2. |
| | |
| | 35. SHT P5.1.1 STATES "SANT DRAINAGE |
| | ISOMETRIC "WEST" SECTION". THIS DOES NOT |
| | REFLECT THE PLUMBING SHEET INDEX. - |
| | VENTS ARE REQUIRED ON THE FLOOR DRAINS |
| | IN THE TRASH ROOM/AREA & CORRIDOR. |
| | SECTION 901.2.1. - CLEANOUTS REQUIRED IN |
| | BUILDING MAX. 100'. SECTION 708.3.2. - |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN UPSTREAM OF SANT. RISER #22. - |
| | RISER DIAGRAMS AS INDICATED TO "TH" |
| | UNITS DO NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE NOTED, BUT VENTS |
| | FOR THE FLOOR DRAINS ARE NOT SHOWN. |
| | |
| | 37. SHTS P5.1.3 THRU P5.1.5, EVERY VENT |
| | STACK SHALL CONNECT TO THE BASE OF THE |
| | DRAINAGE STACK. ALL RISERS WITH VENT |
| | STACKS SHALL COMPLY. SECTION 903.4. |
| | ***NO COMMENT RESPONSE NOTED, BUT RISERS |
| | 1, 2, 14, 18, 21, 23, 25 & 26 VENTSS |
| | STILL DO NOT CONNECT TO THE STACK. |
| | |
| | 38. SHT P5.1.3 SANT RISER #2 DOES NOT |
| | REFLECT THE FLOOR PLAN. AN EXTRA LAV IS |
| | SHOWN. SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE, NOT ADDRESSED. |
| | |
| | 41. SHT P5.1.3 SANT. RISER #8 DOES NOT |
| | REFLECT THE FLOOR PLAN FOR 2 BATHROOM |
| | GROUPS ALL FLOORS, AND THE FIRST |
| | BATHROOM GROUP 3RD FLOOR. SECTION |
| | 104.2.1. |
| | ***NO COMMENT RESPONSE, RISER STILL DOES |
| | NOT REFLECT THE FLOOR PLAN FOR THE |
| | BRANCH & STACK CONNECTIONS TO THE |
| | BUILDING DRAIN. - SHOW LAV ARM FOR THE |
| | THIRD FLOOR LAST BATHROOM ON RISER. |
| | |
| | 42. SHT P5.1.4 SANT. RISER #9 DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE RISERS |
| | AND BRANCH LINES CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE, RISER D0ES NOT |
| | REFLECT THE FLOOR PLAN AT THE POWDER |
| | ROOM. THE W/C IS NOT VENTED. W/M TO |
| | DISCHARGE DOWNSTREAM OF THE BATHROOM |
| | FIXTURES. SECTIONS 901.2.1, & 909.1. |
| | |
| | 44. SHT P5.1.4 SANT. RISER #12 DOES NOT |
| | REFLECT THE FLOOR PLAN AT LAV ARMS BY |
| | JAC2, NOR WHERE THE RISERS & BRANCH |
| | LINES CONNECT TTO THE BUILDING DRAIN. |
| | SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE, BUT THE BRANCH |
| | LINES AND RISER CONNECTIONS TO THE |
| | BUILDING DRAIN DO NOT REFLECT THE FLOOR |
| | PLAN. |
| | |
| | 50. SHT P5.1.5 SANT. RISER #21 DOES NOT |
| | REFLECT THE FLOOR PLAN WHERE THE RISERS |
| | AND BRANCH LINES CONNECT TO THE BUILDING |
| | DRAIN. SECTION 104.2.1. |
| | ***NO COMMENT RESPONSE, BUT THE RISER |
| | FOR THE W/M STILL DOES NOT REFLECT THE |
| | FLOOR PLAN. |
| | |
| | 61. SUBMIT WATER ISOMETRICS FOR THE |
| | FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B, |
| | C-2C, C-2D, C-2E, C-2F, C-2G, C-2H, |
| | C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2, |
| | TH-2A, TH-2B, TH-2C. |
| | ***NO COMMENT RESPONSE, ALSO SUBMIT |
| | WATER RISERS FOR UNITS C1, C2, C3, C3A, |
| | C4, C5, TH1, AND TH1E. |
| | |
| | 62.SHT P6.1.4 GAS PIPING ISOMETRIC: |
| | SUBMIT APPROVED TABLES FOR SIZING PIPE |
| | PER FBC-2001 FUEL GAS CODE. |
| | ***GAS TABLE INDICATED, BUT NOT |
| | SUBMITTED. |
| | |
| | 63. SHT P6.1.4 PROVIDE MANUF. |
| | SPECIFICATION SHEETS FOR ALL PRV'S. - |
| | SHOW ALL VENT PIPING FOR PRV'S AND |
| | INDICATE THE MATERIAL REQUIRED FOR |
| | VENTS. SECTIONS 410.2 & 410.3. - A |
| | LISTED SHUTOFF VALVE SHAL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | SECTION 410.2(5) - POOL HEATER LINE |
| | DOWNSTREAM OF SHUTOFF VALVE INDICATES |
| | "MAXIMUM LENTH = 20'". MAXIMUM DISTANCE |
| | FROM APPLIANCES TO SHUTOFF VALVE IT 6'. |
| | SECTION 409.7. - PIPE DOWNSTREAM OF |
| | METER TO 1ST BRANCH LINE STARTS OFF |
| | 1-1/4", THEN REDUCES TO 1", THEN |
| | INCREASES TO 1-1/4". PLEASE CLARIFY. |
| | ***NO COMMENT RESPONSE, NOT ADDRESSED. |
| | |
| | PROVIDE THE FOLLOWING FOR APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGHTS PER FBC-2001 |
| | FUEL GAS. |
| | ***NO COMMENT RESPONSE, NOT ADDRESSED |
| | |
| | B. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | ***NO COMMENT RESPONSE. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | ***NO COMMENT RESPONSE, MANUF. SHEETS |
| | NOT FOUND. |
| | |
| | 64. INFORMATIONAL: PLANS DO NOT APPEAR |
| | TO BE COMPLETE AT THIS TIME. MORE |
| | COMMENTS MAY BE FORTHCOMING UPON NEXT |
| | SUBMITTAL OF PLAN AND DEPENDING UPON |
| | COMMENT RESPONSES. |
| | ***IT APPEARS THAT MAJOR PLAN |
| | DEVELOPMENT WAS DONE BETWEEN SUBMITTALS |
| | FOR REVIEW. THAT PLUS THE LACK OF |
| | COMMENT RESPONSES ATTRIBUTE TO THE |
| | ADDITIONAL TIME TO REVIEW PLANS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ***NO COMMENT RESPONSES FROM THE |
| | ENGINEER. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SUBMIT A CONDENSATE ISOMETRIC FOR |
| | THE BUILDING DRAIN SHOWING ALL PIPE |
| | SIZES, RISERS, AND POINT OF TERMINATION. |
| | ALSO SUBMIT CONDENSATE RISER DIAGRAMS |
| | SHOWING ALL PIPE SIZES AND VENTS. |
| | SECTION 104.3.1.1. |
| | |
| | 2B. SUBMIT WATER RISER DIAGRAM |
| | ISOMETRICS FOR EACH UNIT TYPE. SHOW ALL |
| | PIPE SIZES, VALVES, AND WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTVE RANGE" |
| | NOT IN THE CEILING. SECTION 104.3.1.1. |
| | |
| | 3B. SHT P0.1 SHEET INDEX, SHEET NUMBERS |
| | ARE OUT OF SEQUENCE AND INDICATES "NORTH |
| | & SOUTH" WHERE AS "EAST" & "WEST" ARE |
| | USED ON MOST SHEETS. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | 4B. SHTS P2.1.1, P2.1.2, P5.1.1 & P5.1.2 |
| | INDICATE DFU'S FOR RETAIL SPACES. TABLE |
| | 709.1(2). |
| | |
| | 5B. SHTS P2.1.2 & P5.1.1 FLOOR DRAINS |
| | NOT VENTED. RELEIF VENT REQUIRED FOR THE |
| | AAV FOR THE TOILET ROOM NEAR THE BASE OF |
| | STACK S/13. SECTION 917.3.2. |
| | |
| | 6B. SHT P2.1.3 ORD SDR 1/2 INDICATES 4" |
| | PIPE. SDR # 1/2 RISER DIAGRAM AND TABLE |
| | 1106.3 INDICATE 6" PIPE REQUIRED. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN LAYOUT. |
| | SECTION 104.2.1. |
| | |
| | 7B. SHT P2.2.1 ORD SDR # 1/2 INDICATES |
| | 3600SF. SRD # 1/2 ARE 900SF EACH. PLEASE |
| | CORRELATE SDR & ORD. SECTION 104.2.1. |
| | |
| | 8B. SHT P2.3.2 INDICATES 3RD FLOOR |
| | "SOUTH". PREVIOUS SHEETS INDICATE "EAST" |
| | OR "WEST". PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 9B. SHT P2.4.2 INDICATES 4TH - 6TH |
| | FLOORS "SOUTH" PLEASE CLARIFY. |
| | |
| | 10B. SHTS P2.7.1, P2.7.2 & PT.2.1 ODR'S |
| | SHALL DRAIN THE SAME AREA AS THE SDR |
| | DRAINS. PLEASE INDICATE THE AREA TO BE |
| | DRAINED, AND NOT THE MAXIMUM AREA |
| | ALLOWED. TABLE 1106.3. |
| | |
| | 11B. TWO P3.4.2 SHEETS SUBMITTED. |
| | MISSING SHT P3.4.1. PLEASE CORRELATE |
| | SHEET NUMBERS WITH SHEET INDEX. SECTION |
| | 104.2.1. |
| | |
| | 12B. TWO P3.5.2 SHEETS SUBMITTED. |
| | MISSING SHT P3.5.1. PLEASE CORRELATE |
| | SHEET NUMBERS WITH SHEET INDEX. SECTION |
| | 104.2.1. |
| | |
| | 13B. SHTS P4.16 & P4.17 SHOWS 2 "TH2B" |
| | UNITS, AND NO "TH2A" UNITS. PLEASE |
| | CLARIFY. |
| | |
| | 14B. SHT P5.1.4 RISER 27 A RELIEF VENT |
| | IS REQUIRED FOR THE AAV. SECTION |
| | 917.3.2. |
| | |
| | 15B. SHT P5.1.4 RISER #13 30DFU'S, RISER |
| | 15 33DFU'S, RISER 16/20 110DFU'S. |
| | RECHECK ALL RISER DFU'S PER TABLES 709.1 |
| | & 709.2. |
| | |
| | 16B. SHT P5.2.1 SDR'S 2, 8, 10, & 15. |
| | THE FLOOR DRAINS AT THE 2ND FLOOR ARE |
| | MISSING FROM THE RISERS. SECTION |
| | 104.2.1. |
| | |
| | 17B. SHT P5.2.1 SHOWS 2 SDR & ODR #9'S |
| | AND TWO 3 10"S. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 18B. SHT P5.2.1 SDR #2 INDICATES 1800SF |
| | BUT ROOF PLAN SHOWS 900SF. PLEASE |
| | CORRELATE RISER & ROOF PLAN. SECTION |
| | 104.2.1. |
| | |
| | 19B. SHT P5.2.2 15" 56,755SF THRU 15" |
| | 69,655SF TO BE RUN A MINIMUM 1/4"/FT |
| | SLOPE. PLEASE INDICATE ON PLANS AT THE |
| | FLOOR PLAN AND THE BLDG DRAIN ISOMETRIC. |
| | TABLE 1106.3. |
| | |
| | 20B. SHT P5.2.2 ODR/DDR'S #1 & #18 10" |
| | PIPE REQUIRED. TABLE 1106.3 |
| | |
| | 21B. SHT P5.2.2 DDR'S #4 & #8 2ND FLOOR |
| | FLOOR DRAINS NOT SHOWN ON RISER DIAGRAM. |
| | SECTION 104.2.1. |
| | |
| | 22B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL AND FS 55.80(2)(B). |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | PLEASE SUBMIT ONE SET OF OLD PLANS FOR |
| | COMPAIRSON. |
| | |