Plan Review Notes
Plan Review Notes For Permit 05091456
Permit Number 05091456
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL ARCHITECTURAL SHEETS: THE
 PERSONAL SEAL, SIGNATURE, AND THE DATE
 THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 THE SIGNATURE IS A "STAMP OF THE
 SIGNATURE" AND AS SUCH IS NOT APPROVED.
 THERE IS NOT DATE ON THE SEAL WHEN IT
 WAS AFFIXED TO THE PLANS. FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055
 ***RESPONSE NOTED, BUT THE DATE THE SEAL
 AND SIGNATURE ARE AFFIXED TO THE PLANS
 SHALL BE ON THE SEAL.
  
 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS
 PER REQUIREMENTS #6 & 7B FHA DESIGN
 MANUAL. THE CLEAR FLOOR SPACE FOR THE
 SHOWERS SHALL BE PARALLEL WITH THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 SEE PAGE 7.56 FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT NO OTHER FIXTURE
 MAY OVERLAP THE CLEAR FLOOR SPACE AT THE
 SHOWERS. THIS INCLUDES THE W/C'S, LAV
 VANITIES, OR SHOWER DOORS.
  
 9. SHTS A-801 THRU A-802C & A-808 ALL
 "TH" UNITS: PRIMARY LEVEL TO BE COVERED
 PER FHA DESIGN MANUAL. SHOW THE FLOOR
 PLAN FOR EACH TYPE OF "TH" UNIT WITH
 CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43
 & 7.47. ALSO SHOW MAX HEIGHT FOR LAV AT
 34" REQUIRED ON PAGE 7.52 FHA DESIGN
 MANUAL.
 ***RESPONSE NOTED, BUT THE W/C CAN NOT
 BE IN THE CLEAR FLOOR SPACE FOR THE
 SHOWER. PAGE 7.57
  
 10. SHTS A-803 THRU A-807A INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT -
 BATHROOM AS REQUIRED ON PAGES 7.34 &
 7.44 OF THE FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT THE SPECIFICATION
 FOR EACH UNIT HAS NOT BEEN FOUND.
  
 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS
 P1.1, P5.1.4, P5.1.5, & P6.1.4 ARE NOT
 SHOWN ON THE INDEX.- SHTS P2.5.1 &
 P2.5.2 DO NOT REFLECT THE SHEETS
 SUBMITTED. - SHTS P2.6.1, P2.6.2,
 P2.7.1, P2.7.2, P2.8.1, P2.8.2, P3.6.1
 WERE NOT SUBMITTED. - SHT P5.1.3 DOES
 NOT REFLECT THE INDEX, AND P5.1.5 &
 P5.1.6 SHOWN AS STORM, BUT SHEETS
 INDICATE SANT. SYSTEM. PLEASE CLARIFY.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT SHTS
 P2.5.1 & P2.5.2 DO NOT REFLECT THE
 PLUMBING SHEET INDEX FOR SHEET
 IDENTIFICATION, AND SHT P3.6.1 IS NOT
 NUMBERED CORRECTLY.
  
 15. P2.1.2 FLOOR DRAINS IN THE TRASH
 ROOM/AREA AND IN THE CORRIDOR SHALL BE
 VENTED. SECTION 901.2.1.
 ***NO COMMENT RESPONSE NOTED, FLOOR
 DRAINS ARE NOT VENTED.
  
 22. SHT FOR 7TH FLOOR WEST SECTION
 DRAINAGE PLAN (P2.6.2). CONDENSATE FOR
 RESIDENT STORAGE & CONDO UNIT C-1(730)
 SHOWS PLAN NOTE #2. PLEASE CLARIFY.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, CONDENSATE
 NOTE FOR RESIDENT STORAGE UNCHANGED.
  
 23. SHT P2.7.1 SHOW THE LOCATION FOR ALL
 VENTS THRU ROOF AND INDICATE RISER
 NUMBER FOR EACH.
 ***NO COMMENT RESPONSE NOTED. NO VENTS
 THRU ROOF LOCATED.
  
  
 29. SHT INDICATING WATER SUPPLY PLAN 5TH
 FLOOR "NORTH" SECTION, PREVIOUS SHEETS
 WERE DESIGNATED AS "EAST" OR "WEST".
 THIS IS ALSO THE SECOND SHEET NUMBERED
 P3.5.1. - INDICATE WHAT DESIGNATION WSC2
 IS FOR. - NOTE STATES "SEE UNIT LAYOUTS
 ON SHEET P4.1". SHT P4.1 NOT SUBMITTED.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT NOW
 THERE ARE TWO SHEETS WITH THE NUMBER
 P3.5.2. THE FIRST SHOULD BE P3.5.1.
 PLEASE CLARIFY.
  
 30. FIRST SHT P3.6.2 INDICATES WATER
 SUPPLY PLAN 6TH FLOOR "SOUTH" SECTION.
 EAST AND WEST WERE INDICATED PRIOR TO
 THIS. 2ND SHT WITH THE SAME NUMBER
 INDICATES "WEST" SECTION. PLEASE
 CLARIFY.SECTION 104.2.1.
 ***NO COMMENT RESPONSE, PLANS STILL HAVE
 TWO SHEETS NUMBERED P3.6.2.
  
 35. SHT P5.1.1 STATES "SANT DRAINAGE
 ISOMETRIC "WEST" SECTION". THIS DOES NOT
 REFLECT THE PLUMBING SHEET INDEX. -
 VENTS ARE REQUIRED ON THE FLOOR DRAINS
 IN THE TRASH ROOM/AREA & CORRIDOR.
 SECTION 901.2.1. - CLEANOUTS REQUIRED IN
 BUILDING MAX. 100'. SECTION 708.3.2. -
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN UPSTREAM OF SANT. RISER #22. -
 RISER DIAGRAMS AS INDICATED TO "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT VENTS
 FOR THE FLOOR DRAINS ARE NOT SHOWN.
  
 37. SHTS P5.1.3 THRU P5.1.5, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. ALL RISERS WITH VENT
 STACKS SHALL COMPLY. SECTION 903.4.
 ***NO COMMENT RESPONSE NOTED, BUT RISERS
 1, 2, 14, 18, 21, 23, 25 & 26 VENTSS
 STILL DO NOT CONNECT TO THE STACK.
  
 38. SHT P5.1.3 SANT RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN. AN EXTRA LAV IS
 SHOWN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, NOT ADDRESSED.
  
 41. SHT P5.1.3 SANT. RISER #8 DOES NOT
 REFLECT THE FLOOR PLAN FOR 2 BATHROOM
 GROUPS ALL FLOORS, AND THE FIRST
 BATHROOM GROUP 3RD FLOOR. SECTION
 104.2.1.
 ***NO COMMENT RESPONSE, RISER STILL DOES
 NOT REFLECT THE FLOOR PLAN FOR THE
 BRANCH & STACK CONNECTIONS TO THE
 BUILDING DRAIN. - SHOW LAV ARM FOR THE
 THIRD FLOOR LAST BATHROOM ON RISER.
  
 42. SHT P5.1.4 SANT. RISER #9 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, RISER D0ES NOT
 REFLECT THE FLOOR PLAN AT THE POWDER
 ROOM. THE W/C IS NOT VENTED. W/M TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTIONS 901.2.1, & 909.1.
  
 44. SHT P5.1.4 SANT. RISER #12 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2, NOR WHERE THE RISERS & BRANCH
 LINES CONNECT TTO THE BUILDING DRAIN.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE, BUT THE BRANCH
 LINES AND RISER CONNECTIONS TO THE
 BUILDING DRAIN DO NOT REFLECT THE FLOOR
 PLAN.
  
 50. SHT P5.1.5 SANT. RISER #21 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, BUT THE RISER
 FOR THE W/M STILL DOES NOT REFLECT THE
 FLOOR PLAN.
  
 61. SUBMIT WATER ISOMETRICS FOR THE
 FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B,
 C-2C, C-2D, C-2E, C-2F, C-2G, C-2H,
 C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2,
 TH-2A, TH-2B, TH-2C.
 ***NO COMMENT RESPONSE, ALSO SUBMIT
 WATER RISERS FOR UNITS C1, C2, C3, C3A,
 C4, C5, TH1, AND TH1E.
  
 62.SHT P6.1.4 GAS PIPING ISOMETRIC:
 SUBMIT APPROVED TABLES FOR SIZING PIPE
 PER FBC-2001 FUEL GAS CODE.
 ***GAS TABLE INDICATED, BUT NOT
 SUBMITTED.
  
 63. SHT P6.1.4 PROVIDE MANUF.
 SPECIFICATION SHEETS FOR ALL PRV'S. -
 SHOW ALL VENT PIPING FOR PRV'S AND
 INDICATE THE MATERIAL REQUIRED FOR
 VENTS. SECTIONS 410.2 & 410.3. - A
 LISTED SHUTOFF VALVE SHAL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 SECTION 410.2(5) - POOL HEATER LINE
 DOWNSTREAM OF SHUTOFF VALVE INDICATES
 "MAXIMUM LENTH = 20'". MAXIMUM DISTANCE
 FROM APPLIANCES TO SHUTOFF VALVE IT 6'.
 SECTION 409.7. - PIPE DOWNSTREAM OF
 METER TO 1ST BRANCH LINE STARTS OFF
 1-1/4", THEN REDUCES TO 1", THEN
 INCREASES TO 1-1/4". PLEASE CLARIFY.
 ***NO COMMENT RESPONSE, NOT ADDRESSED.
  
 PROVIDE THE FOLLOWING FOR APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS.
 ***NO COMMENT RESPONSE, NOT ADDRESSED
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 ***NO COMMENT RESPONSE.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***NO COMMENT RESPONSE, MANUF. SHEETS
 NOT FOUND.
  
 64. INFORMATIONAL: PLANS DO NOT APPEAR
 TO BE COMPLETE AT THIS TIME. MORE
 COMMENTS MAY BE FORTHCOMING UPON NEXT
 SUBMITTAL OF PLAN AND DEPENDING UPON
 COMMENT RESPONSES.
 ***IT APPEARS THAT MAJOR PLAN
 DEVELOPMENT WAS DONE BETWEEN SUBMITTALS
 FOR REVIEW. THAT PLUS THE LACK OF
 COMMENT RESPONSES ATTRIBUTE TO THE
 ADDITIONAL TIME TO REVIEW PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO COMMENT RESPONSES FROM THE
 ENGINEER.
  
 **************NEW COMMENTS**************
  
 1B. SUBMIT A CONDENSATE ISOMETRIC FOR
 THE BUILDING DRAIN SHOWING ALL PIPE
 SIZES, RISERS, AND POINT OF TERMINATION.
 ALSO SUBMIT CONDENSATE RISER DIAGRAMS
 SHOWING ALL PIPE SIZES AND VENTS.
 SECTION 104.3.1.1.
  
 2B. SUBMIT WATER RISER DIAGRAM
 ISOMETRICS FOR EACH UNIT TYPE. SHOW ALL
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTVE RANGE"
 NOT IN THE CEILING. SECTION 104.3.1.1.
  
 3B. SHT P0.1 SHEET INDEX, SHEET NUMBERS
 ARE OUT OF SEQUENCE AND INDICATES "NORTH
 & SOUTH" WHERE AS "EAST" & "WEST" ARE
 USED ON MOST SHEETS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 4B. SHTS P2.1.1, P2.1.2, P5.1.1 & P5.1.2
 INDICATE DFU'S FOR RETAIL SPACES. TABLE
 709.1(2).
  
 5B. SHTS P2.1.2 & P5.1.1 FLOOR DRAINS
 NOT VENTED. RELEIF VENT REQUIRED FOR THE
 AAV FOR THE TOILET ROOM NEAR THE BASE OF
 STACK S/13. SECTION 917.3.2.
  
 6B. SHT P2.1.3 ORD SDR 1/2 INDICATES 4"
 PIPE. SDR # 1/2 RISER DIAGRAM AND TABLE
 1106.3 INDICATE 6" PIPE REQUIRED. PLEASE
 CORRELATE RISER AND FLOOR PLAN LAYOUT.
 SECTION 104.2.1.
  
 7B. SHT P2.2.1 ORD SDR # 1/2 INDICATES
 3600SF. SRD # 1/2 ARE 900SF EACH. PLEASE
 CORRELATE SDR & ORD. SECTION 104.2.1.
  
 8B. SHT P2.3.2 INDICATES 3RD FLOOR
 "SOUTH". PREVIOUS SHEETS INDICATE "EAST"
 OR "WEST". PLEASE CLARIFY. SECTION
 104.2.1.
  
 9B. SHT P2.4.2 INDICATES 4TH - 6TH
 FLOORS "SOUTH" PLEASE CLARIFY.
  
 10B. SHTS P2.7.1, P2.7.2 & PT.2.1 ODR'S
 SHALL DRAIN THE SAME AREA AS THE SDR
 DRAINS. PLEASE INDICATE THE AREA TO BE
 DRAINED, AND NOT THE MAXIMUM AREA
 ALLOWED. TABLE 1106.3.
  
 11B. TWO P3.4.2 SHEETS SUBMITTED.
 MISSING SHT P3.4.1. PLEASE CORRELATE
 SHEET NUMBERS WITH SHEET INDEX. SECTION
 104.2.1.
  
 12B. TWO P3.5.2 SHEETS SUBMITTED.
 MISSING SHT P3.5.1. PLEASE CORRELATE
 SHEET NUMBERS WITH SHEET INDEX. SECTION
 104.2.1.
  
 13B. SHTS P4.16 & P4.17 SHOWS 2 "TH2B"
 UNITS, AND NO "TH2A" UNITS. PLEASE
 CLARIFY.
  
 14B. SHT P5.1.4 RISER 27 A RELIEF VENT
 IS REQUIRED FOR THE AAV. SECTION
 917.3.2.
  
 15B. SHT P5.1.4 RISER #13 30DFU'S, RISER
 15 33DFU'S, RISER 16/20 110DFU'S.
 RECHECK ALL RISER DFU'S PER TABLES 709.1
 & 709.2.
  
 16B. SHT P5.2.1 SDR'S 2, 8, 10, & 15.
 THE FLOOR DRAINS AT THE 2ND FLOOR ARE
 MISSING FROM THE RISERS. SECTION
 104.2.1.
  
 17B. SHT P5.2.1 SHOWS 2 SDR & ODR #9'S
 AND TWO 3 10"S. PLEASE CLARIFY. SECTION
 104.2.1.
  
 18B. SHT P5.2.1 SDR #2 INDICATES 1800SF
 BUT ROOF PLAN SHOWS 900SF. PLEASE
 CORRELATE RISER & ROOF PLAN. SECTION
 104.2.1.
  
 19B. SHT P5.2.2 15" 56,755SF THRU 15"
 69,655SF TO BE RUN A MINIMUM 1/4"/FT
 SLOPE. PLEASE INDICATE ON PLANS AT THE
 FLOOR PLAN AND THE BLDG DRAIN ISOMETRIC.
 TABLE 1106.3.
  
 20B. SHT P5.2.2 ODR/DDR'S #1 & #18 10"
 PIPE REQUIRED. TABLE 1106.3
  
 21B. SHT P5.2.2 DDR'S #4 & #8 2ND FLOOR
 FLOOR DRAINS NOT SHOWN ON RISER DIAGRAM.
 SECTION 104.2.1.
  
 22B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 55.80(2)(B).
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 PLEASE SUBMIT ONE SET OF OLD PLANS FOR
 COMPAIRSON.
  
 REVIEW BY KEN STEVENS