Plan Review Notes
Plan Review Notes For Permit 05091456
Permit Number 05091456
Review Stop M
Sequence Number 2
Notes
Date Text
2006-06-27 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 COMMENTS BY HAROLD MOSER ON 1/10/2006
  
 COMMENT 1.RESPONSE REFERS TO FBC(M)
 404.1 & 404.2.SECTION 404 IN THE 2001
 CODE IS VENTILATION OF UNINHABITED
 SPACES WHEREAS THE 2004 FMC 404 IS
 ENCLOSED PARKING GARAGES.THIS BUILDING
 WAS SUBMITTED UNDER THE 2001 FLORIDA
 BUILDING CODE.PLEASE SHOW COMPLIANCE
 WITH 2001 FMC 502.10, 403.4 AND FBC
 411.4.
  
 COMMENT 2.OK
 COMMENT 3.OK
 COMMENT 4.RESPONSE INDICATES
 MECHANICAL CLOSETS WILL COMPLY WITH
 CHAPTER 4 OF THE ENERGY CODE.PLEASE
 NOTE THE SPECIFIC CODE SECTION IS
 410.1.ABCD.3.7 OF THE 2001 FBC.PER THE
 2001 FBC CO SENSORS MAY BE UTILIZED IN
 "PUBLIC" GARAGE.PLEASE CLARIFY IF THE
 PUBLIC NOT JUST THE RESIDENCE WILL HAVE
 ACCESS TO THE GARAGE.
  
 COMMENT 5. RESPONSE INDICATES THE
 ENGINEER OF RECORD IS TO SUBMIT THE
 MANUFACTURE SUBMITTAL DATA.THIS IS
 ACKNOWLEDGED BUT PERMIT CAN NOT BE
 ISSUED WITHOUT REVIEW OF THE EQUIPMENT.
  
 COMMENT 6.OK
 COMMENT 7.OK
 COMMENT 8.OK
 COMMENT 9.OK - RTU-2 IS SHOWN ON PLAN
 SHEET M2.7.2 NOT M2.7.1.
  
 COMMENT 10. OK
 **************NEW COMMENTS*************
  
 1.PLAN SHEET M2.1.1, SHOW THE GARAGE
 FANS DICHARGING ON TO A HANDICAP RAMP
 THAT IS LOCATED WITH IN 10 FT OF THE
 DISCHARGE ACCORDING TO PLAN SHEET A-201
 WHICH DOES NOT COMPLY WITH 2001 FMC
 401.5.2 & 401.5.PLEASE NOTE, IT IS
 RECOMMENDED THE GARAGE EXHAUST SYSTEMS
 ARE DESIGNED TO MINIMIZE NOISE LEVELS
 USING LINE FAN SILENCERS OR OTHER
 APPROVED METHODS.
  
 2.PLAN SHEET M2.3.2, 2.4.2, 2.5.2,
 2.6.2, INDICATES A 6" X 6" FLEX DUCT
 PENETRATING A RATED WALL AT THE
 FOLLOWING ROOM NUMBERS; 339, 434, 534,
 633 & 733.THE EXCEPTION FOR NOT
 INSTALLING A FIRE DAMPER ARE SPECIFIED
 IN 2001 FMC 607.1.3. #3.
  
 3.PLEASE CLARIFY DUCT FROM CORRIDOR
 INTO FOR THE RESIDENCE IS FOR OUTSIDE
 AIR.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 4.PLAN SHEET A-801 TH-1 1ST FLOOR
 DETAIL DESIGNATES THE DOOR TO THE AHU
 CLOSET AS D2.THIS IS ALSO WHAT IS
 DESIGNATED FOR THE CLOSET AREA THAT
 ENCLOSES THE DRYER AND THE AHU.THE
 DOOR SCHEDULE ON PLAN SHEET A-903 FOR
 THE 2 STORY CONDO UNITS (TH) SHOWS THESE
 DOORS AS BI-FOLD WOOD DOORS.RETURN AIR
 CAN NOT BE TRANSFERED THROUGH THE
 LAUNDRY CLOSET AREA TO THE AHU CLOSET.
 2001 FBC 610.1.ABC.3.7 & FMC 603.9.
  
 5.PLEASE NOTE, WOOD DOORS TO SHALL
 HAVE A FLAME SPREAD INDEX LESS THAN 25
 AND A SMOKE INDEX LESS THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 PER
 2001 FMC 602.2.1.
  
 6.PLAN SHEETS M4.1, M4.2, & 4.3, SHOW
 ONLY CERTAIN UNITS THE ARCHITECTURAL
 PLANS INDICATE 25 UNITS WITH DIFFERENT
 SQUARE FOOTAGE.ARE THE MECHANICAL
 PLANS TO BE TYPICAL? EXAMPLE ARE ALL THE
 C2 UNIT GOING TO HAVE THE SAME AIR
 DISTRIBUTION AS A C2A, B, C, D, E, F, G,
 & H?
  
 7.PLAN SHEET M4.1 UNIT C2 DOES NOT
 INDICATE SUPPLY AIR INTO THE BATHROOM
 AREA, ONLY EXHAUST.PLEASE CLARIFY.
  
 8.PLAN SHEET M4.4 IN BOTH THE LOWER
 LOBBY AND THE UPPER LOBBY PLEASE CLARIFY
 THE MAKE-UP AIR THROUGH THE TRASH ROOM
 IN A TWO HOUR ENCLOSURE BUT THEN
 TERMINATES IN THE RATED WALLS. IF FIRE
 DAMPER'S ARE INSTALLED THIS WOULD
 NULLIFY THE MAKE-UP AIR REQUIREMENT FOR
 THE GARAGE SHOULD DAMPERS CLOSE.
  
 9.PLAN SHEET M5.1 THE DRYER EXHAUST
 SHAFT SHALL COMPLY WITH 2001 FBC
 705.2.3.3, ENCLOSURE AT BOTTOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.