| 2006-06-27 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE |
| | |
| | COMMENTS BY HAROLD MOSER ON 1/10/2006 |
| | |
| | COMMENT 1.RESPONSE REFERS TO FBC(M) |
| | 404.1 & 404.2.SECTION 404 IN THE 2001 |
| | CODE IS VENTILATION OF UNINHABITED |
| | SPACES WHEREAS THE 2004 FMC 404 IS |
| | ENCLOSED PARKING GARAGES.THIS BUILDING |
| | WAS SUBMITTED UNDER THE 2001 FLORIDA |
| | BUILDING CODE.PLEASE SHOW COMPLIANCE |
| | WITH 2001 FMC 502.10, 403.4 AND FBC |
| | 411.4. |
| | |
| | COMMENT 2.OK |
| | COMMENT 3.OK |
| | COMMENT 4.RESPONSE INDICATES |
| | MECHANICAL CLOSETS WILL COMPLY WITH |
| | CHAPTER 4 OF THE ENERGY CODE.PLEASE |
| | NOTE THE SPECIFIC CODE SECTION IS |
| | 410.1.ABCD.3.7 OF THE 2001 FBC.PER THE |
| | 2001 FBC CO SENSORS MAY BE UTILIZED IN |
| | "PUBLIC" GARAGE.PLEASE CLARIFY IF THE |
| | PUBLIC NOT JUST THE RESIDENCE WILL HAVE |
| | ACCESS TO THE GARAGE. |
| | |
| | COMMENT 5. RESPONSE INDICATES THE |
| | ENGINEER OF RECORD IS TO SUBMIT THE |
| | MANUFACTURE SUBMITTAL DATA.THIS IS |
| | ACKNOWLEDGED BUT PERMIT CAN NOT BE |
| | ISSUED WITHOUT REVIEW OF THE EQUIPMENT. |
| | |
| | COMMENT 6.OK |
| | COMMENT 7.OK |
| | COMMENT 8.OK |
| | COMMENT 9.OK - RTU-2 IS SHOWN ON PLAN |
| | SHEET M2.7.2 NOT M2.7.1. |
| | |
| | COMMENT 10. OK |
| | **************NEW COMMENTS************* |
| | |
| | 1.PLAN SHEET M2.1.1, SHOW THE GARAGE |
| | FANS DICHARGING ON TO A HANDICAP RAMP |
| | THAT IS LOCATED WITH IN 10 FT OF THE |
| | DISCHARGE ACCORDING TO PLAN SHEET A-201 |
| | WHICH DOES NOT COMPLY WITH 2001 FMC |
| | 401.5.2 & 401.5.PLEASE NOTE, IT IS |
| | RECOMMENDED THE GARAGE EXHAUST SYSTEMS |
| | ARE DESIGNED TO MINIMIZE NOISE LEVELS |
| | USING LINE FAN SILENCERS OR OTHER |
| | APPROVED METHODS. |
| | |
| | 2.PLAN SHEET M2.3.2, 2.4.2, 2.5.2, |
| | 2.6.2, INDICATES A 6" X 6" FLEX DUCT |
| | PENETRATING A RATED WALL AT THE |
| | FOLLOWING ROOM NUMBERS; 339, 434, 534, |
| | 633 & 733.THE EXCEPTION FOR NOT |
| | INSTALLING A FIRE DAMPER ARE SPECIFIED |
| | IN 2001 FMC 607.1.3. #3. |
| | |
| | 3.PLEASE CLARIFY DUCT FROM CORRIDOR |
| | INTO FOR THE RESIDENCE IS FOR OUTSIDE |
| | AIR.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS IN ACCORDANCE WITH 2001 FMC |
| | TABLE 403.3. |
| | |
| | 4.PLAN SHEET A-801 TH-1 1ST FLOOR |
| | DETAIL DESIGNATES THE DOOR TO THE AHU |
| | CLOSET AS D2.THIS IS ALSO WHAT IS |
| | DESIGNATED FOR THE CLOSET AREA THAT |
| | ENCLOSES THE DRYER AND THE AHU.THE |
| | DOOR SCHEDULE ON PLAN SHEET A-903 FOR |
| | THE 2 STORY CONDO UNITS (TH) SHOWS THESE |
| | DOORS AS BI-FOLD WOOD DOORS.RETURN AIR |
| | CAN NOT BE TRANSFERED THROUGH THE |
| | LAUNDRY CLOSET AREA TO THE AHU CLOSET. |
| | 2001 FBC 610.1.ABC.3.7 & FMC 603.9. |
| | |
| | 5.PLEASE NOTE, WOOD DOORS TO SHALL |
| | HAVE A FLAME SPREAD INDEX LESS THAN 25 |
| | AND A SMOKE INDEX LESS THAN 50 WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E 84 PER |
| | 2001 FMC 602.2.1. |
| | |
| | 6.PLAN SHEETS M4.1, M4.2, & 4.3, SHOW |
| | ONLY CERTAIN UNITS THE ARCHITECTURAL |
| | PLANS INDICATE 25 UNITS WITH DIFFERENT |
| | SQUARE FOOTAGE.ARE THE MECHANICAL |
| | PLANS TO BE TYPICAL? EXAMPLE ARE ALL THE |
| | C2 UNIT GOING TO HAVE THE SAME AIR |
| | DISTRIBUTION AS A C2A, B, C, D, E, F, G, |
| | & H? |
| | |
| | 7.PLAN SHEET M4.1 UNIT C2 DOES NOT |
| | INDICATE SUPPLY AIR INTO THE BATHROOM |
| | AREA, ONLY EXHAUST.PLEASE CLARIFY. |
| | |
| | 8.PLAN SHEET M4.4 IN BOTH THE LOWER |
| | LOBBY AND THE UPPER LOBBY PLEASE CLARIFY |
| | THE MAKE-UP AIR THROUGH THE TRASH ROOM |
| | IN A TWO HOUR ENCLOSURE BUT THEN |
| | TERMINATES IN THE RATED WALLS. IF FIRE |
| | DAMPER'S ARE INSTALLED THIS WOULD |
| | NULLIFY THE MAKE-UP AIR REQUIREMENT FOR |
| | THE GARAGE SHOULD DAMPERS CLOSE. |
| | |
| | 9.PLAN SHEET M5.1 THE DRYER EXHAUST |
| | SHAFT SHALL COMPLY WITH 2001 FBC |
| | 705.2.3.3, ENCLOSURE AT BOTTOM. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |