| 2006-06-11 00:00:00 | REVIEW CONTINUED |
| | ******** UNSAT 2ND REVIEW *********** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH ARE NEEDED TO BE |
| | ADDRESSED. PLEASE ALSO SEE SOME NEW |
| | COMMENTS. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH WILL AFFECT DESIGN/LAYOUT WHICH |
| | WILL HAVE A DIRECT AFFECT ON ELECTRICAL PLANS.(BUILDING |
| | NOTES). |
| | |
| | ** PLEASE SEE COMMENTS BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW ANS NEW |
| | NOTES ARE ADDED TO THE BOTTOM. |
| | |
| | *********IMPORTANT*********** |
| | |
| | PLEASE BE SURE THREE COMPLETE SETS ARE |
| | SUBMITTEDAS THIS IS A THRESHOLD JOB |
| | AND PLEASE BE SURE ALL SHEETS ARE BOUND |
| | TOGETHER IN A MEANS THAT SETS AND SHEETS |
| | DO NOT READILY FALL APART. |
| | THE SETS SUBMITTED DO NOT CONTAIN |
| | STAPLES THAT ADEQUATELY HOLD SETS/SHEETS |
| | IN PLACE. THANK YOU FOR ANTICIPATED |
| | ATTENTION TO THIS. |
| | ************************************** |
| | |
| | |
| | MIZNER LAKES BLDG #5. |
| | |
| | 1)NOTE: NO, PLEASE SEE APPLICATION STILL |
| | INDICATES 117 UNITS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CORRELATE BLDG PLANS AND |
| | PERMIT APPLICATION WITH ELECTRICAL |
| | PLANS. PLEASE SEE BLDG SHEETS INDICATE |
| | 114 UNITS, ALTHOUGH PERMIT APPLICATION |
| | INDICATE 117. |
| | PLEASE ALSO CORRELATE SQ FT FROM BLDG |
| | SHEET (A) WITH ELECTRICAL PLANS AS THE |
| | A/C SQ FT FOR SOME DO NOT SEEM TO MATCH |
| | UP. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE: NOTE #3 OK FOR MOST, HOWEVER |
| | PLEASE SEE FIRE PROTECTION SHEETS STILL |
| | REFERENCE THE 1999 NFPA-20. PLEASE SEE |
| | FIRE REVIEW COMMENTS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE BE SURE ALL ARCHITECTUAL |
| | AND ELECTRICAL SHEETS CONTAIN REFERENCE |
| | TO THE 2002 NFPA-70, 2003 NFPA-101, |
| | 2002 NFPA-72, NFPA-20 2002 WITH ANY |
| | OTHER CODES CURRENTLY IN EFFECT NEEDED. |
| | |
| | 4)NOTE:NOTE #4, NO, PLEASE STILL SEE |
| | THERE IS SOME DIFFERENCES IN PLANS. |
| | PLEASE SEE FP SHEETS IDENIFY THE FIRE |
| | PUMP CONTROLLER AND ATS. IF THIS PUMP IS |
| | DIESEL AS INDICATED IN RESPONSE, THNE |
| | THE ATS MUST BE A MISPRINT. PLEASE SEE |
| | FIRE SHEET FS0.2 |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE FIRE PUMP CONTROLLER |
| | (DIESEL) AND PUMP. THESE MUST BE IN SETS |
| | EVEN IF THE FIRE PUMP IS GOING TO BE |
| | SUBMITTED SEPARATELY. |
| | |
| | ** PREVIOUS NOTE **PLEASE SEE FP |
| | SHEETS AND A SHEETS INDICATE A FIRE PUMP |
| | AND FIRE HOUSE, HOWEVER THERE IS NOT |
| | INDICATION OF THIS ON ELECTRICAL RISER |
| | ETC. |
| | PLEASE KNOW, AS PER DISCUSSION WITH |
| | CHIEF ELECTRICAL INSPECTOR AND FIRE |
| | MARSHAL'S OFFICE, GENERATOR BACK UP MAY |
| | BE REQUIRED IF ELECTRIC FIRE PUMP AND |
| | NOT DIESEL. |
| | IT WAS ALSO MENTIONED THERE MAY BE ONE |
| | FOR EACH BLDGOR ONE FOR BOTH? |
| | PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS |
| | AND 695 OF NEC.(2002). |
| | 695.3, 9.2, 9.6.2.2 |
| | PLEASE SEE THIS BLDG SET OF PLANS |
| | CONTAINS MORE INFORMATION THAT THERE |
| | WILL BE AN ELECTRICAL FIRE PUMP. PLEASE |
| | SEE ALL OTHER COMMENTS FROM ELECTRIC AND |
| | FIRE REVIEWER(S). |
| | PLEASE KNOW THERE IS NOT ENOUGH |
| | INFORMATION FOR THE REVIEW. |
| | PLEASE ALSO KNOW, SINCE THE REVIEW OF |
| | BLDG #4, IT IS BEING DISCUSSED WITHIN |
| | THE AHJ IF A GENERATOR SIZED FOR THE MIN |
| | BACK UP OF FIRE PUMP WILL BE REQUIRED. |
| | IF INDEED THIS IS THE CASE IT WILL ALSO |
| | REQUIRE A MIN OF ON SITE FUEL FOR A MIN |
| | OF 8HRS RUNNING TIME. |
| | |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE IT IS NOW |
| | INDICATED THAT THE FIRE PUMP IS OF FUEL |
| | TYPE HOWEVER NO SPECS FOR TANK/FUEL |
| | STORAGE AND MIN FUEL FOR STORAGE ON |
| | SITE. PLEASE SEE A MIN OF 8HRS RUNNING |
| | IS REQUIRED. |
| | 1999 NFPA-20 8-4.3, 2003 NFPA-20 11-4.3 |
| | PLEASE SEE MORE INFORMAION IS STILL |
| | NEEDED FOR REVIEW OF FIRE PUMP/FP HOUSE/ |
| | ETC THIS WILL ALSO BE IN FIRE MARSHAL'S |
| | REVIEW. |
| | |
| | **PREVIOUS REVIEW ** |
| | IF AN ELECTRICAL FIRE PUMP IS |
| | INSTALLED, PLEASE SUBMIT ALL |
| | SPECS/MANUFACTURES CUT SHEETS FOR PUMP, |
| | FIRE PUMP CONTROLLER, GENERATOR AND ANY |
| | SUB-BASE FUEL TANKS. |
| | PLEASE BE SURE ALL SPECS/CUT SHEETS |
| | CONTAIN A LISTING FROM A NRTL. |
| | |
| | 6)NOTE: OK. |
| | |
| | 7)NOTE: NOTE #7 NO, PLEASE SEE NEW NOTES |
| | AND FLOORS WHICH EM FIXTURES ARE NOT |
| | SHOWN.2.41-2.72 |
| | THIS IS MORE DETAILED IN NEW NOTES. |
| | PLEASE SEE MOST WERE DONE. |
| | |
| | ** PREVIOUS NOTE ** PLEASE KNOW, A MIN |
| | BATTERY BACK |
| | UP FIXTURE OF SOME TYPE WILL ALSO BE |
| | REQUIRED IN MAIN ELECTRICAL RM, |
| | ELECTRICAL RMS, FIRE PUMP RM/HOUSE, |
| | ELEVATOR EQUIPMENT RMS. |
| | 700.16,7.8,7.9 ETC. |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE: NOTE #9, NO, PLEASE SEE NEW |
| | NOTES WITH RESPECT TO FIXTURES ON UPER |
| | FLRS. 2.41-2.72 |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASEIDENTIFY THE FIXTURE |
| | TYPES IN STAIR TOWERS. PLEASE LABEL. |
| | |
| | 10)NOTE:NOTE #10 NO, THIS COULD NOT BE |
| | LCOATED. PLEASE SEE REPSONSE MENTIONS |
| | THIS DETAIL IS ON E0.9, HOWEVER THIS |
| | SHEET E0.9 IS NOT IN ANY OF THE TWO SETS SUBMITTED? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE DETAIL FOR |
| | DISCONNECT(S) FOR ROOF TOP UNITS. |
| | 440.11, MAY BE A "TYPICAL" DETAIL FOR |
| | CU'S. |
| | |
| | 11)NOTE: NOTE #11 NO, ALTHOUGH MOST ALL |
| | WAS DONE PLEASE SEE SHEET 2.32 WHICH IS |
| | MISSING CIRCUITING FOR CORRIDIOR. |
| | PLEASE SEE NEW NOTES FOR THIS SAME |
| | SHEET. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS, INCLUDING ALL COMMON AREAS , |
| | PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING. |
| | MOST ARE ON PLANS SOME ARE |
| | MISSING. SEE SOME REDLINED. |
| | |
| | 12)NOTE: OK THIS WAS DONE, HOWEVER |
| | PLEASE SEE NEW NOTES. |
| | |
| | 13)NOTE:NOTE #13 NO, PLEASE SEE THE |
| | CIRCUIUTS HAVE NOW BEEN DIVIDED, HOWEVER |
| | LOADS FOR THESE STILL ARE NOT REFLECTED |
| | ON PANEL SCHEDULES. PLEASE SEE |
| | 210.52B1,210.11C1 AND 220.16A WHICH |
| | REQUIRES 1.5VA FOR EACH OF THE TWO OR |
| | MORE CIRCUITS. PLEASE SEE DINING, AND |
| | NOOK AREAS ARE CONSIDERED AS AREAS OF |
| | THE LIKE AS STATED IN 210.52B |
| | PLEASE SEE THESE ONES HAVE BEEN REDLINED |
| | ON ONE SET OF PLANS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 210.52B1 WHICH |
| | REQUIRES RECEPTS IN DINING AREAS/ROOMS T |
| | BE ON THE ONE OR MORE SMALL APPLIANCE |
| | CIRCUITS. PLEASE SEE LIGHTING ETC MAY |
| | NOT BE ON THESE CIRCUITS. THIS WOULD |
| | ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS. |
| | |
| | 14)NOTE: OK. |
| | |
| | 15)NOTE:OK, HOWEVER PLEASE SEE NEW |
| | NOTES FOR MORE DETAIL OF MANY FIXTURES. |
| | PLEASE ALSO SEE THE RESPONSE LETTER |
| | MENTIONS TO SEE SHEET E0.9, HOWEVER NO |
| | SHEET E0.9 WAS SUBMITTED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE BE SURE FIXTURE SCHEDULE |
| | CORRELATE WITH PLANS AND "LABELING" OF |
| | SOME SORT ALSO CORRELATES. |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE: OK. |
| | |
| | 18)NOTE: OK. |
| | |
| | 19)NOTE: NOTE#15 NO, PLEASE SEE LAUNDRY |
| | CIRCUIT STILL SHOWN AS 1.2. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 210.11C, 220.16B |
| | WHICH REQUIRES A MIN OF 1.5KW FOR |
| | LAUNDRY/WASHER CIRCUITS. |
| | PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME |
| | SHOWN WITHOUT LOADS. |
| | |
| | 20)NOTE: N/A |
| | |
| | 21)NOTE: OK. |
| | |
| | 22)NOTE: OK. |
| | |
| | 23)NOTE: OK. |
| | |
| | 24)NOTE: NOTE#24 NO, PLEASE SEE SOME |
| | LOCATIONS WHICH RECEPTS ARE MISSING. |
| | PLEASE SEE ONE SET OF ELECTRICLA PLANS |
| | HAVE BEEN REDLINED. C-4, TH2 |
| | PLEASE NOTE: AREAS CONTAINING RAILS ARE |
| | CONSIDERED WALL SPACE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE LOCATIONS ON PLANS |
| | FOR MISSING RECEPTS PER 210.52, DINING |
| | RM WALL C-2, BEDRM IN C-5, C-4 VERIFY |
| | ANY OTHER POSSIBLE LOCATIONS. |
| | |
| | 25)NOTE: OK. |
| | |
| | 26)NOTE: OK. |
| | |
| | 27)NOTE: OK, HOWEVER SEE NEW NOTES NOW |
| | THAT CIRCUITS WERE ADDED. |
| | |
| | ** PREVIOUS NNOTE ** |
| | PLEASE SEE SOME CIRCUITING |
| | MISSING ON PLANS FOR BATH ETC C-5 |
| | |
| | 28)NOTE: NOTE #28 NO, IT WAS NOTED THAT |
| | SOME OF THE CLOSETS MAY NOT BE LARGE |
| | ENOUGH, HOWEVER SEE UNIT TH2 WHICH |
| | APPEARS THIS WOULD NOT BE THE CASE. THIS |
| | WAS CONFIRMED WITH THE MECH REVIEWER AND |
| | A LT WOULD BE REQUIRED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 210.70 FOR MIN LT |
| | REQUIRED FOR A/C CLOSETS. |
| | |
| | 29)NOTE: OK, MOST APPEAR TO BE OK. |
| | |
| | 30)NOTE: NOTE #30 NO, PLEASE SEE THE |
| | SAME COUNTER SPACE IS REDLINED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE POSSIBLE MISSING |
| | RECEPT FOR KITCHEN COUNTERSPACE PER |
| | 210.52C1, C-4 |
| | |
| | 31)NOTE: OK. |
| | |
| | 32)NOTE: OK, HOWEVER SEE NEW NOTES FOR CIRCUITING. |
| | |
| | 33)NOTE: OK. |
| | |
| | 34)NOTE: NOTE #34 NO, PLEASE SEE |
| | RESPONSE MENTIONS TO SEE 7.1.1 FOR |
| | DETAIL, HOWEVER NO DETAIL WAS SHOWN FOR |
| | "BUS-DUCT" PENETRATIONS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE MIN CURB DETAIL |
| | FOR THROUGH FLOOR PENETRATIONS.368.6 |
| | FOR BUS-DUCT RISER. |
| | |
| | 35)NOTE: NOTE # 35 NO, PLEASE SEE KW |
| | RATINGS WERE REVISED, HOWEVER PLEASE SEE |
| | LOADS AND OCP DO NOT CORRELATE WITH THE |
| | MECHANICAL PLANS. |
| | PLEASE SEE MAX OCP ETC. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE MANY A/C HEAT LOADS |
| | ARE SHOWN AS "0"?? |
| | PLEASE ALSO SEE OTHERS WHICH INDICATE |
| | 65% OF 4KW AS 20KW? PLEASE RE-FIGURE |
| | LOADS FOR A/C'S AND PLEASE ADJUST PANELS |
| | AND LOAD CALCULATIONS. |
| | |
| | 36)NOTE: NOTE #36 NO, PLEASE SEE A NOTE |
| | WAS ADDED, HOWEVER THIS NOTE NOW |
| | MENTIONS TO "PROVIDE A BUILDING |
| | LIGHTNING PROTECTION SYSTEM". |
| | PLEASE SEE PREVIOUS NOTE WAS NOT TO |
| | REQUIRE A LIGHTNING PROTECTION AS THE |
| | STRUCTURE DOES NOT FALL UNDER CODES |
| | WHICH DO REQUIRE LIGHTNIGN PROTECTION. |
| | THE NOTE WHICH WAS REQUESTED WAS FOR ANY |
| | SYSTEM WHICH MAY BE INSTALLED UNDER A |
| | SEPARATE PERMIT SHALL MEET NFPA-780, UL |
| | 96. |
| | PLEASE KNOW MANY SYSTEMS ARE ON THE |
| | MARKET WHICH DO NOT MEET CODE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PLACE NOTE ON "ROOF TOP" |
| | PLANS WHICH WILL BE WORDED TO MENTION: |
| | ANY PROPOSED LIGHTNING PROTECTION |
| | SYSTEM, SHALL BE INSTALLEDPER |
| | NFPA-780" OR WORDS TO THAT AFFECT. |
| | |
| | 37)NOTE: OK. |
| | |
| | 38)NOTE: OK, HOWEVER SEE NEW NOTES. |
| | |
| | 39)NOTE: OK. |
| | |
| | 40)NOTE: OK. |
| | |
| | 41)NOTE:NOTE #41 NO, PLEASE SEE IT IS |
| | NOTED THAT THE "STREET" LIGHTING IS DONE |
| | BY THE CITY OF WEST PALM BEACH AS THE |
| | PLANS MENITONS PALM BEACH COUNTY. PLEASE |
| | KNOW, THIS COMMENT WAS FOR ANY POLE |
| | LIGHTING ON POOL DECK AREA. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE SITE PLANS INCLUDE |
| | SITE LIGHTING. |
| | PLEASE SUBMIT ALL WIND LOAD CALCULATIONS |
| | AT THIS TIME FOR REVIEW IF ALL SITE |
| | LIGHTING POLES AND FIXTURES ARE GOING TO |
| | BE INCLUDED UNDER BLDG #5 SCOPE OF WORK |
| | AND PERMIT. |
| | IF DESIRED, THIS MAY BE PULLED FROM SETS |
| | AND SUBMITTED FOR SEPARATE PERMIT, PLANS |
| | AND FEES AT A LATER DATE. |
| | PLEASE BE SURE CALCULATIONS INLCUDE LT |
| | FIXTURES ON POLES. |
| | PLEASE ALSO COMPLETE DETAIL FOR POLE |
| | BASE WITH ALL DIMENSIONS, ONCE |
| | CALCULATIONS ARE DONE. |
| | |
| | 42)NOTE: OK. |
| | |
| | *********** NEW NOTES **************** |
| | |
| | 43) NOTE: PLEASE SEE SEC'S TO "L1FP" ARE |
| | SHOWN AS 1/0'S WHERE THE MCB OCP IS |
| | 400A'S?? PLEASE ADJUST 240.4,310.16 |
| | |
| | 44) NOTE: PLEASE SEE THE ADDRESS OF |
| | PROJECT IS NOW ASSESSED, PLEASE REVISE |
| | TITLE BLOCKS ACCORDINGLY. |
| | |
| | ** PLEASE SEE ALL SHEETS SHALL |
| | CONTAIN THE PRINTED LICENSE NUMBER FOR |
| | THE ARCHITECTUARAL FIRM AS REQUIRED |
| | UNDER FAC 61G1-16.004. |
| | PLEASE ALSO SEE ALL SHEETS SIGNED AND |
| | SEALED BY THE ARCHITECT SHALL ALSO |
| | CONTAIN THE PRINTED ANME AND THE PRINTED |
| | LICENSE NUMBER OF SAID ARCHITECT. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER ORNOT COMMENT IS |
| | MADE BY OTHER TRADES. THIS COMMENT IS |
| | NOT FOR KAMM CONSULTING , HOWEVER ALL |
| | MEP,FS, FA SHEETS CONTAINING THE |
| | ARCHITECTURAL FIRM SHALL CONTAIN THE |
| | FIRM LICENSE NUMBER. |
| | ** PLEASE KNOW, FOR SHEET WHICH DO NOT |
| | NEED TO BE REVSIED MAY HAVE THIS NUMBER |
| | STAMPED/PRINTED/ ON SHEETS. |
| | PLEASE SEE ALL SHEETS MAY END UP BEING |
| | CHANGED. |
| | THIS WAS MISSED ON PREVIOUS REVIEW. |
| | |
| | 45) NOTE: PLEASE SEE UNLESS THE RETAIL |
| | SERVICE SHALL CONTAIN A MAIN IN THE MAIN ELECTRICAL RM |
| | WHICH THEN WOULD FEED THE |
| | GUTTER IN THE RETAIL ELECTRICAL RM. ONLY |
| | IF THERE IS A "FIRE WALL" SEPARATION. |
| | 230.2E |
| | |
| | 46) NOTE: PLEASE SEE AREA OF POOL DECK |
| | SHALL CONTAIN EM BATTERY BACK UP |
| | FIXTURES OF SOME SORT TO PROVIDE THE MIN |
| | LIGHTING LEVELS UNDER EMERGENCY |
| | CONDITIONS (1FT CANDLE) TO THE PUBLIC |
| | RIGHT OF WAY. |
| | NFPA-101 7.8.1.3, 7.8.1.1 |
| | |
| | 47) NOTE: PLEASE SEE MININUM SIZES FOR |
| | SEC'S SHALL BE SIZED PER 310.16, 240.4C |
| | PLEASE SEE ALL SEC'S SHALL BE EQUAL OR |
| | ABOVE THE OCP FOR DEVICES OVER 800A'S. |
| | PLEASE SEE SEC'S FOR SBA AND MSB. |
| | |
| | 48) NOTE: PLEASE SEE SHEET 5.14 WHICH |
| | MENTIONS MSB SECTION 1 WITH A "MAIN 1 OF |
| | 2", WHICH DOES NOT CORRELATE WITH THE |
| | OTHER SECTION OF MSB , AS THIS IS SHOWN |
| | AS "MAIN 1 OF 3". |
| | PLEASE SEE REDLINED PLANS. |
| | |
| | 49) NOTE: PLEASE SEE ROOF TOP PLANS |
| | WHICH MENTIONS AND NOTES STAIR LTS |
| | FEEDING FLOOR ABOVE.?? |
| | |
| | 50) NOTE: PLEASE SEE SHEETS 2.41-2.72 AS PERVIOUSLY |
| | MENITONED IN ABOVE NOTES, |
| | THESE SHEETS SEEM TO BE MISSING THE |
| | EMERGENCY LIGHTING FIXTURE |
| | DESIGNATION(S) FOR STAIRS AND ROOMS. |
| | PLEASE SEE REDLINED PLANS. |
| | LS 101 7.8,7.9 |
| | |
| | 51) NOTE: PLEASE SEE FPL VAULT IS |
| | SHOWING LT FIXTURES "G". PLEASE CONFIRM |
| | WITH FPL AS THESE SHOUDL NOT BE IN THE |
| | FPL VAULT. |
| | |
| | 52) NOTE: PLEASE SEE SHEET 2.32 WHICH |
| | SEEMS TO CONTAIN A MISPRINT AS IT IS |
| | LABLED FOR 2ND FLR AND 3RD FLR. |
| | REDLINED. |
| | 215.5 |
| | |
| | 53) NOTE: PLEASE SEE PANEL IN UNIT C-3 |
| | WILL NOT BE PERMITTED IN CLOSET. |
| | 408.7,240.24 ETC |
| | |
| | 54) NOTE: PLEASE SEE BATH RMS WHEN |
| | CIRCUITED AS REQUIRED FOR LIGHTING AND |
| | GFI RECEPT ON ONE CIRCUIT, THIS CIRCUIT |
| | MAY FEED ANY OTHER RMS, LTS, DEVICES |
| | ETC. PER 210.11C3 |
| | PLEASE SEE UNITS C-4 AND C-1 AS THESE |
| | WERE REDLINED AS THE DEDIACTED BATH |
| | CIRCUITS AS SHOWN FEED OTHER |
| | LIGHTING.:CLOSET AND HALL. |
| | |
| | 55) NOTE: PLEASE SEE SBA AND MSB CONTAIN |
| | NUMERICAL NOTES NEXT TO SOME BRANCH |
| | DEVICES "NOTE #1" YET, NOTE #1 ON PANEL |
| | SCHEDULE FOR EACH OF THESE ARE BLANK?? |
| | PLEASE CLARIFY.215.5 |
| | |
| | 56) NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | ALL REQUIREMENTS OF THE FHAR 24CFR |
| | 100.205 SHALL BE MET. |
| | |
| | 57) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS. THIS IS ONLY A NOTICE GIVEN AT |
| | THIS TIME. |
| | |
| | ** PLEASE SEE MANY OF THE ABOVE ITEMS |
| | HAVE BEEN REDLINED AT LOCATIONS OF |
| | COMMENTS ON ONE SET OF THE PLANS |
| | SUBMITTED. |
| | |
| | **PLEASE SEE ANY POSSIBLE COMMENTSFROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN. |
| | PLEASE BE SURE TO SEE FIRE REVIEW |
| | COMMENTS AS THERE ARE MANY THAT WILL |
| | AHVE A DIRECT EFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | FROM SETS COMPLETELY AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. ONE SET OF ALL |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | ** PLEASE SEE ONE COPY OF THE OLD SETS |
| | COULD NOT BE LOCATED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-06-09 00:00:00 | REVIEW STARTED. |
| 2006-05-17 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW. |