Plan Review Notes
Plan Review Notes For Permit 05091456
Permit Number 05091456
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-11 00:00:00REVIEW CONTINUED
 ******** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE NEEDED TO BE
 ADDRESSED. PLEASE ALSO SEE SOME NEW
 COMMENTS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT DESIGN/LAYOUT WHICH
 WILL HAVE A DIRECT AFFECT ON ELECTRICAL PLANS.(BUILDING
 NOTES).
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW ANS NEW
 NOTES ARE ADDED TO THE BOTTOM.
  
 *********IMPORTANT***********
  
 PLEASE BE SURE THREE COMPLETE SETS ARE
 SUBMITTEDAS THIS IS A THRESHOLD JOB
 AND PLEASE BE SURE ALL SHEETS ARE BOUND
 TOGETHER IN A MEANS THAT SETS AND SHEETS
 DO NOT READILY FALL APART.
 THE SETS SUBMITTED DO NOT CONTAIN
 STAPLES THAT ADEQUATELY HOLD SETS/SHEETS
 IN PLACE. THANK YOU FOR ANTICIPATED
 ATTENTION TO THIS.
 **************************************
  
  
 MIZNER LAKES BLDG #5.
  
 1)NOTE: NO, PLEASE SEE APPLICATION STILL
 INDICATES 117 UNITS.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE BLDG PLANS AND
 PERMIT APPLICATION WITH ELECTRICAL
 PLANS. PLEASE SEE BLDG SHEETS INDICATE
 114 UNITS, ALTHOUGH PERMIT APPLICATION
 INDICATE 117.
 PLEASE ALSO CORRELATE SQ FT FROM BLDG
 SHEET (A) WITH ELECTRICAL PLANS AS THE
 A/C SQ FT FOR SOME DO NOT SEEM TO MATCH
 UP.
  
 2)NOTE: OK.
  
 3)NOTE: NOTE #3 OK FOR MOST, HOWEVER
 PLEASE SEE FIRE PROTECTION SHEETS STILL
 REFERENCE THE 1999 NFPA-20. PLEASE SEE
 FIRE REVIEW COMMENTS.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE ALL ARCHITECTUAL
 AND ELECTRICAL SHEETS CONTAIN REFERENCE
 TO THE 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72, NFPA-20 2002 WITH ANY
 OTHER CODES CURRENTLY IN EFFECT NEEDED.
  
 4)NOTE:NOTE #4, NO, PLEASE STILL SEE
 THERE IS SOME DIFFERENCES IN PLANS.
 PLEASE SEE FP SHEETS IDENIFY THE FIRE
 PUMP CONTROLLER AND ATS. IF THIS PUMP IS
 DIESEL AS INDICATED IN RESPONSE, THNE
 THE ATS MUST BE A MISPRINT. PLEASE SEE
 FIRE SHEET FS0.2
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FIRE PUMP CONTROLLER
 (DIESEL) AND PUMP. THESE MUST BE IN SETS
 EVEN IF THE FIRE PUMP IS GOING TO BE
 SUBMITTED SEPARATELY.
  
 ** PREVIOUS NOTE **PLEASE SEE FP
 SHEETS AND A SHEETS INDICATE A FIRE PUMP
 AND FIRE HOUSE, HOWEVER THERE IS NOT
 INDICATION OF THIS ON ELECTRICAL RISER
 ETC.
 PLEASE KNOW, AS PER DISCUSSION WITH
 CHIEF ELECTRICAL INSPECTOR AND FIRE
 MARSHAL'S OFFICE, GENERATOR BACK UP MAY
 BE REQUIRED IF ELECTRIC FIRE PUMP AND
 NOT DIESEL.
 IT WAS ALSO MENTIONED THERE MAY BE ONE
 FOR EACH BLDGOR ONE FOR BOTH?
 PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS
 AND 695 OF NEC.(2002).
 695.3, 9.2, 9.6.2.2
 PLEASE SEE THIS BLDG SET OF PLANS
 CONTAINS MORE INFORMATION THAT THERE
 WILL BE AN ELECTRICAL FIRE PUMP. PLEASE
 SEE ALL OTHER COMMENTS FROM ELECTRIC AND
 FIRE REVIEWER(S).
 PLEASE KNOW THERE IS NOT ENOUGH
 INFORMATION FOR THE REVIEW.
 PLEASE ALSO KNOW, SINCE THE REVIEW OF
 BLDG #4, IT IS BEING DISCUSSED WITHIN
 THE AHJ IF A GENERATOR SIZED FOR THE MIN
 BACK UP OF FIRE PUMP WILL BE REQUIRED.
 IF INDEED THIS IS THE CASE IT WILL ALSO
 REQUIRE A MIN OF ON SITE FUEL FOR A MIN
 OF 8HRS RUNNING TIME.
  
  
 5)NOTE: NOTE #5 NO, PLEASE SEE IT IS NOW
 INDICATED THAT THE FIRE PUMP IS OF FUEL
 TYPE HOWEVER NO SPECS FOR TANK/FUEL
 STORAGE AND MIN FUEL FOR STORAGE ON
 SITE. PLEASE SEE A MIN OF 8HRS RUNNING
 IS REQUIRED.
 1999 NFPA-20 8-4.3, 2003 NFPA-20 11-4.3
 PLEASE SEE MORE INFORMAION IS STILL
 NEEDED FOR REVIEW OF FIRE PUMP/FP HOUSE/
 ETC THIS WILL ALSO BE IN FIRE MARSHAL'S
 REVIEW.
  
 **PREVIOUS REVIEW **
 IF AN ELECTRICAL FIRE PUMP IS
 INSTALLED, PLEASE SUBMIT ALL
 SPECS/MANUFACTURES CUT SHEETS FOR PUMP,
 FIRE PUMP CONTROLLER, GENERATOR AND ANY
 SUB-BASE FUEL TANKS.
 PLEASE BE SURE ALL SPECS/CUT SHEETS
 CONTAIN A LISTING FROM A NRTL.
  
 6)NOTE: OK.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE NEW NOTES
 AND FLOORS WHICH EM FIXTURES ARE NOT
 SHOWN.2.41-2.72
 THIS IS MORE DETAILED IN NEW NOTES.
 PLEASE SEE MOST WERE DONE.
  
 ** PREVIOUS NOTE ** PLEASE KNOW, A MIN
 BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN MAIN ELECTRICAL RM,
 ELECTRICAL RMS, FIRE PUMP RM/HOUSE,
 ELEVATOR EQUIPMENT RMS.
 700.16,7.8,7.9 ETC.
  
 8)NOTE: OK.
  
 9)NOTE: NOTE #9, NO, PLEASE SEE NEW
 NOTES WITH RESPECT TO FIXTURES ON UPER
 FLRS. 2.41-2.72
  
 ** PREVIOUS NOTE**
 PLEASEIDENTIFY THE FIXTURE
 TYPES IN STAIR TOWERS. PLEASE LABEL.
  
 10)NOTE:NOTE #10 NO, THIS COULD NOT BE
 LCOATED. PLEASE SEE REPSONSE MENTIONS
 THIS DETAIL IS ON E0.9, HOWEVER THIS
 SHEET E0.9 IS NOT IN ANY OF THE TWO SETS SUBMITTED?
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE DETAIL FOR
 DISCONNECT(S) FOR ROOF TOP UNITS.
 440.11, MAY BE A "TYPICAL" DETAIL FOR
 CU'S.
  
 11)NOTE: NOTE #11 NO, ALTHOUGH MOST ALL
 WAS DONE PLEASE SEE SHEET 2.32 WHICH IS
 MISSING CIRCUITING FOR CORRIDIOR.
 PLEASE SEE NEW NOTES FOR THIS SAME
 SHEET.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL CIRCUITING
 ON PLANS, INCLUDING ALL COMMON AREAS ,
 PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING.
 MOST ARE ON PLANS SOME ARE
 MISSING. SEE SOME REDLINED.
  
 12)NOTE: OK THIS WAS DONE, HOWEVER
 PLEASE SEE NEW NOTES.
  
 13)NOTE:NOTE #13 NO, PLEASE SEE THE
 CIRCUIUTS HAVE NOW BEEN DIVIDED, HOWEVER
 LOADS FOR THESE STILL ARE NOT REFLECTED
 ON PANEL SCHEDULES. PLEASE SEE
 210.52B1,210.11C1 AND 220.16A WHICH
 REQUIRES 1.5VA FOR EACH OF THE TWO OR
 MORE CIRCUITS. PLEASE SEE DINING, AND
 NOOK AREAS ARE CONSIDERED AS AREAS OF
 THE LIKE AS STATED IN 210.52B
 PLEASE SEE THESE ONES HAVE BEEN REDLINED
 ON ONE SET OF PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.52B1 WHICH
 REQUIRES RECEPTS IN DINING AREAS/ROOMS T
 BE ON THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE LIGHTING ETC MAY
 NOT BE ON THESE CIRCUITS. THIS WOULD
 ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS.
  
 14)NOTE: OK.
  
 15)NOTE:OK, HOWEVER PLEASE SEE NEW
 NOTES FOR MORE DETAIL OF MANY FIXTURES.
 PLEASE ALSO SEE THE RESPONSE LETTER
 MENTIONS TO SEE SHEET E0.9, HOWEVER NO
 SHEET E0.9 WAS SUBMITTED.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE FIXTURE SCHEDULE
 CORRELATE WITH PLANS AND "LABELING" OF
 SOME SORT ALSO CORRELATES.
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
 18)NOTE: OK.
  
 19)NOTE: NOTE#15 NO, PLEASE SEE LAUNDRY
 CIRCUIT STILL SHOWN AS 1.2.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.11C, 220.16B
 WHICH REQUIRES A MIN OF 1.5KW FOR
 LAUNDRY/WASHER CIRCUITS.
 PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME
 SHOWN WITHOUT LOADS.
  
 20)NOTE: N/A
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: NOTE#24 NO, PLEASE SEE SOME
 LOCATIONS WHICH RECEPTS ARE MISSING.
 PLEASE SEE ONE SET OF ELECTRICLA PLANS
 HAVE BEEN REDLINED. C-4, TH2
 PLEASE NOTE: AREAS CONTAINING RAILS ARE
 CONSIDERED WALL SPACE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE LOCATIONS ON PLANS
 FOR MISSING RECEPTS PER 210.52, DINING
 RM WALL C-2, BEDRM IN C-5, C-4 VERIFY
 ANY OTHER POSSIBLE LOCATIONS.
  
 25)NOTE: OK.
  
 26)NOTE: OK.
  
 27)NOTE: OK, HOWEVER SEE NEW NOTES NOW
 THAT CIRCUITS WERE ADDED.
  
 ** PREVIOUS NNOTE **
 PLEASE SEE SOME CIRCUITING
 MISSING ON PLANS FOR BATH ETC C-5
  
 28)NOTE: NOTE #28 NO, IT WAS NOTED THAT
 SOME OF THE CLOSETS MAY NOT BE LARGE
 ENOUGH, HOWEVER SEE UNIT TH2 WHICH
 APPEARS THIS WOULD NOT BE THE CASE. THIS
 WAS CONFIRMED WITH THE MECH REVIEWER AND
 A LT WOULD BE REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.70 FOR MIN LT
 REQUIRED FOR A/C CLOSETS.
  
 29)NOTE: OK, MOST APPEAR TO BE OK.
  
 30)NOTE: NOTE #30 NO, PLEASE SEE THE
 SAME COUNTER SPACE IS REDLINED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE POSSIBLE MISSING
 RECEPT FOR KITCHEN COUNTERSPACE PER
 210.52C1, C-4
  
 31)NOTE: OK.
  
 32)NOTE: OK, HOWEVER SEE NEW NOTES FOR CIRCUITING.
  
 33)NOTE: OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE
 RESPONSE MENTIONS TO SEE 7.1.1 FOR
 DETAIL, HOWEVER NO DETAIL WAS SHOWN FOR
 "BUS-DUCT" PENETRATIONS.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE MIN CURB DETAIL
 FOR THROUGH FLOOR PENETRATIONS.368.6
 FOR BUS-DUCT RISER.
  
 35)NOTE: NOTE # 35 NO, PLEASE SEE KW
 RATINGS WERE REVISED, HOWEVER PLEASE SEE
 LOADS AND OCP DO NOT CORRELATE WITH THE
 MECHANICAL PLANS.
 PLEASE SEE MAX OCP ETC.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MANY A/C HEAT LOADS
 ARE SHOWN AS "0"??
 PLEASE ALSO SEE OTHERS WHICH INDICATE
 65% OF 4KW AS 20KW? PLEASE RE-FIGURE
 LOADS FOR A/C'S AND PLEASE ADJUST PANELS
 AND LOAD CALCULATIONS.
  
 36)NOTE: NOTE #36 NO, PLEASE SEE A NOTE
 WAS ADDED, HOWEVER THIS NOTE NOW
 MENTIONS TO "PROVIDE A BUILDING
 LIGHTNING PROTECTION SYSTEM".
 PLEASE SEE PREVIOUS NOTE WAS NOT TO
 REQUIRE A LIGHTNING PROTECTION AS THE
 STRUCTURE DOES NOT FALL UNDER CODES
 WHICH DO REQUIRE LIGHTNIGN PROTECTION.
 THE NOTE WHICH WAS REQUESTED WAS FOR ANY
 SYSTEM WHICH MAY BE INSTALLED UNDER A
 SEPARATE PERMIT SHALL MEET NFPA-780, UL
 96.
 PLEASE KNOW MANY SYSTEMS ARE ON THE
 MARKET WHICH DO NOT MEET CODE.
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON "ROOF TOP"
 PLANS WHICH WILL BE WORDED TO MENTION:
 ANY PROPOSED LIGHTNING PROTECTION
 SYSTEM, SHALL BE INSTALLEDPER
 NFPA-780" OR WORDS TO THAT AFFECT.
  
 37)NOTE: OK.
  
 38)NOTE: OK, HOWEVER SEE NEW NOTES.
  
 39)NOTE: OK.
  
 40)NOTE: OK.
  
 41)NOTE:NOTE #41 NO, PLEASE SEE IT IS
 NOTED THAT THE "STREET" LIGHTING IS DONE
 BY THE CITY OF WEST PALM BEACH AS THE
 PLANS MENITONS PALM BEACH COUNTY. PLEASE
 KNOW, THIS COMMENT WAS FOR ANY POLE
 LIGHTING ON POOL DECK AREA.
  
 ** PREVIOUS NOTE **
 PLEASE SEE SITE PLANS INCLUDE
 SITE LIGHTING.
 PLEASE SUBMIT ALL WIND LOAD CALCULATIONS
 AT THIS TIME FOR REVIEW IF ALL SITE
 LIGHTING POLES AND FIXTURES ARE GOING TO
 BE INCLUDED UNDER BLDG #5 SCOPE OF WORK
 AND PERMIT.
 IF DESIRED, THIS MAY BE PULLED FROM SETS
 AND SUBMITTED FOR SEPARATE PERMIT, PLANS
 AND FEES AT A LATER DATE.
 PLEASE BE SURE CALCULATIONS INLCUDE LT
 FIXTURES ON POLES.
 PLEASE ALSO COMPLETE DETAIL FOR POLE
 BASE WITH ALL DIMENSIONS, ONCE
 CALCULATIONS ARE DONE.
  
 42)NOTE: OK.
  
 *********** NEW NOTES ****************
  
 43) NOTE: PLEASE SEE SEC'S TO "L1FP" ARE
 SHOWN AS 1/0'S WHERE THE MCB OCP IS
 400A'S?? PLEASE ADJUST 240.4,310.16
  
 44) NOTE: PLEASE SEE THE ADDRESS OF
 PROJECT IS NOW ASSESSED, PLEASE REVISE
 TITLE BLOCKS ACCORDINGLY.
  
 ** PLEASE SEE ALL SHEETS SHALL
 CONTAIN THE PRINTED LICENSE NUMBER FOR
 THE ARCHITECTUARAL FIRM AS REQUIRED
 UNDER FAC 61G1-16.004.
 PLEASE ALSO SEE ALL SHEETS SIGNED AND
 SEALED BY THE ARCHITECT SHALL ALSO
 CONTAIN THE PRINTED ANME AND THE PRINTED
 LICENSE NUMBER OF SAID ARCHITECT.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER ORNOT COMMENT IS
 MADE BY OTHER TRADES. THIS COMMENT IS
 NOT FOR KAMM CONSULTING , HOWEVER ALL
 MEP,FS, FA SHEETS CONTAINING THE
 ARCHITECTURAL FIRM SHALL CONTAIN THE
 FIRM LICENSE NUMBER.
 ** PLEASE KNOW, FOR SHEET WHICH DO NOT
 NEED TO BE REVSIED MAY HAVE THIS NUMBER
 STAMPED/PRINTED/ ON SHEETS.
 PLEASE SEE ALL SHEETS MAY END UP BEING
 CHANGED.
 THIS WAS MISSED ON PREVIOUS REVIEW.
  
 45) NOTE: PLEASE SEE UNLESS THE RETAIL
 SERVICE SHALL CONTAIN A MAIN IN THE MAIN ELECTRICAL RM
 WHICH THEN WOULD FEED THE
 GUTTER IN THE RETAIL ELECTRICAL RM. ONLY
 IF THERE IS A "FIRE WALL" SEPARATION.
 230.2E
  
 46) NOTE: PLEASE SEE AREA OF POOL DECK
 SHALL CONTAIN EM BATTERY BACK UP
 FIXTURES OF SOME SORT TO PROVIDE THE MIN
 LIGHTING LEVELS UNDER EMERGENCY
 CONDITIONS (1FT CANDLE) TO THE PUBLIC
 RIGHT OF WAY.
 NFPA-101 7.8.1.3, 7.8.1.1
  
 47) NOTE: PLEASE SEE MININUM SIZES FOR
 SEC'S SHALL BE SIZED PER 310.16, 240.4C
 PLEASE SEE ALL SEC'S SHALL BE EQUAL OR
 ABOVE THE OCP FOR DEVICES OVER 800A'S.
 PLEASE SEE SEC'S FOR SBA AND MSB.
  
 48) NOTE: PLEASE SEE SHEET 5.14 WHICH
 MENTIONS MSB SECTION 1 WITH A "MAIN 1 OF
 2", WHICH DOES NOT CORRELATE WITH THE
 OTHER SECTION OF MSB , AS THIS IS SHOWN
 AS "MAIN 1 OF 3".
 PLEASE SEE REDLINED PLANS.
  
 49) NOTE: PLEASE SEE ROOF TOP PLANS
 WHICH MENTIONS AND NOTES STAIR LTS
 FEEDING FLOOR ABOVE.??
  
 50) NOTE: PLEASE SEE SHEETS 2.41-2.72 AS PERVIOUSLY
 MENITONED IN ABOVE NOTES,
 THESE SHEETS SEEM TO BE MISSING THE
 EMERGENCY LIGHTING FIXTURE
 DESIGNATION(S) FOR STAIRS AND ROOMS.
 PLEASE SEE REDLINED PLANS.
 LS 101 7.8,7.9
  
 51) NOTE: PLEASE SEE FPL VAULT IS
 SHOWING LT FIXTURES "G". PLEASE CONFIRM
 WITH FPL AS THESE SHOUDL NOT BE IN THE
 FPL VAULT.
  
 52) NOTE: PLEASE SEE SHEET 2.32 WHICH
 SEEMS TO CONTAIN A MISPRINT AS IT IS
 LABLED FOR 2ND FLR AND 3RD FLR.
 REDLINED.
 215.5
  
 53) NOTE: PLEASE SEE PANEL IN UNIT C-3
 WILL NOT BE PERMITTED IN CLOSET.
 408.7,240.24 ETC
  
 54) NOTE: PLEASE SEE BATH RMS WHEN
 CIRCUITED AS REQUIRED FOR LIGHTING AND
 GFI RECEPT ON ONE CIRCUIT, THIS CIRCUIT
 MAY FEED ANY OTHER RMS, LTS, DEVICES
 ETC. PER 210.11C3
 PLEASE SEE UNITS C-4 AND C-1 AS THESE
 WERE REDLINED AS THE DEDIACTED BATH
 CIRCUITS AS SHOWN FEED OTHER
 LIGHTING.:CLOSET AND HALL.
  
 55) NOTE: PLEASE SEE SBA AND MSB CONTAIN
 NUMERICAL NOTES NEXT TO SOME BRANCH
 DEVICES "NOTE #1" YET, NOTE #1 ON PANEL
 SCHEDULE FOR EACH OF THESE ARE BLANK??
 PLEASE CLARIFY.215.5
  
 56) NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL REQUIREMENTS OF THE FHAR 24CFR
 100.205 SHALL BE MET.
  
 57) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED AT LOCATIONS OF
 COMMENTS ON ONE SET OF THE PLANS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTSFROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
 PLEASE BE SURE TO SEE FIRE REVIEW
 COMMENTS AS THERE ARE MANY THAT WILL
 AHVE A DIRECT EFFECT ON ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS COMPLETELY AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 ** PLEASE SEE ONE COPY OF THE OLD SETS
 COULD NOT BE LOCATED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-09 00:00:00REVIEW STARTED.
2006-05-17 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.