| | BUILDING PLAN REVIEW |
| | PERMIT: 05091456MIZNER LAKES |
| | ADD: 1580 SAMANTHA LN |
| | CONT: AVS CONSTRUCTION |
| | TEL: (954)655-5162 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | ARCH:SLATTERY & ASSOC/PAUL J SLATTERY |
| | 2060 NW BOCA RATON BLVD |
| | BOCO RATON, FL |
| | TEL: (561) 392-3848 |
| | FAX: (561) 392-5402 |
| | |
| | STRUC: CHM STRUCTURAL ENG, LLC |
| | 9200 S DADELAND, SUITE 409 |
| | MIAMI, FL |
| | TEL (305) 667-1621 |
| | FAX (305) 662-9673 |
| | |
| | ARCHITECTURAL SHEET A.002, BUILDING |
| | DATA DOES NOT IDENTIFY THE MINIMUM |
| | BUILDING DESIGN GOVERNED BYINTENDED |
| | OCCUPANCYSEE 503.1.2 AND TABLE 500. |
| | COMMENT# 10 ALSO REFERS BACK TO THIS |
| | SAME ISSUE. PLEASE PROVIDE THIS |
| | INFORMATION ON A-002 UNDER BUILDING# 5 |
| | DATA. |
| | |
| | ARCHITECTURAL SHEET A-251 INDICATES THAT |
| | THIS PLAN WAS DEVELOPED UNDER THE 2001 |
| | FBC, BUT HAS CODE REFRENCES FOR THE 2004 |
| | FBC (TYPE II-B). S-0.00 ALSO INDICATES |
| | THE PLANS WERE DEVELOPED UNDER THE 2001 |
| | FBC. |
| | NOTE A-253-A-256 STILL REFRENCE A R-3 |
| | OCCUPANCY WHICH IS FOR SINGLE |
| | FAMILY THIS WILL BE AN R2 OCCUPANCY CLASSIFICATION. |
| | |
| | THIS BUILDING IS A MIXED OCCUPANCY |
| | BUILDING AND TO COMPLY WITH SECTION 303. |
| | PLANS ARE TO INDICATE WHERE AREA AND |
| | HEIGTH MODIFICATIONS ARE TAKEN, SECTION |
| | 503. |
| | |
| | THIS REVIEW WILL BE COMPLETED UNDER THE: |
| | 2001 FBC |
| | TYPE: II, SPRINKLERED NFPA 13 |
| | |
| | |
| | ---NOTE--- |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1)2ND REQUEST, PROVIDE NOC RECORDED WITH |
| | THE CLERK OF COURT BEFORE A PERMIT CAN |
| | BE ISSUED. NOTE: FL S S 713.13(2) IF THE |
| | NOC ISRECORDED AT THE CLERK OF THE |
| | COURT ANDWORK HAS NOT STATED WITH 90 |
| | DAYS OF RECORDING IT IS NULL & VOID |
| | REQUIRING RE-RECORDING. |
| | |
| | 2) 2ND REQUEST,FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING |
| | CAPACITY IS NOT DEFINETLY KNOWN OR IS IN |
| | QUESTION. WHERE THE BEARING CAPACITY OF |
| | THE SOIL IS NOT DEFINITLY KNOWN OR IS IN |
| | QUESTION THE BUILDING OFFICIAL MAY |
| | REQUIRE EXPLORATIONS, TEST OR OTHER |
| | ADEQUATE PROOF AS TO THE PERMISSIBLE |
| | SAFE BEARING CAPACITY. REQUIRED TEST AND |
| | RECOMMENDATIONS SUBMITTED TO VERIFY |
| | BEARING CAPACITY SHALL BE CERTIFIED BY A |
| | GEOTECHNICALREPORT FROM A DESIGN |
| | PROFESSIONAL PROPERLY LICENSED IN THE |
| | STATE OF FLORIDA. |
| | |
| | 3)2ND REQUEST, FBC 13-103.1.2 BEFORE A |
| | BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 4)COMPLIED. |
| | |
| | 5)2ND REQUEST, BEFORE A PERMIT TO |
| | CONSTRUCT, MAY BE ISSUED, IMPACT FEES |
| | MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 6)2ND REQUEST,WPB AMENDMENT 105.13.6. |
| | W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) ADDITIONAL INFORMATION REQUIRED FOR |
| | RECORD KEEPING PURPOSES 104.1.2*: |
| | |
| | 10)SHEET A-002 |
| | |
| | 10A) 2ND REQUEST,AS NOTED ABOVE PLANS |
| | ARE TO INDICATE THE MINIMUM BUILDING |
| | TYPE, 503.1.2& TABLE 500.PROVIDE AREA |
| | AND HEIGTH MODIFICATIONS. |
| | |
| | 10C)A) FLOOD ZONE |
| | 10C)B) FLOOD ELEVATION (IF A ZONE) |
| | 10C)C) LOMAR (IF A ZONE) |
| | 10C)D) COMPLIED. |
| | 10C)E) COMPLIED. |
| | 10C)F) COMPLIED. |
| | 10C)G) COMPLIED. |
| | 10C)H) COMPLIED. |
| | 10C)I) COMPLIED. |
| | 10C)J) COMPLIED. |
| | 10C)K) SQ FT UNDER ROOF (TOTAL) |
| | |
| | 11) SHEET A-102; |
| | |
| | 11A) COMPLIED. |
| | |
| | 11B) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13A)2ND REQUEST, PROVIDE A SECTION |
| | THROUGH STAIRWAYS INDICATING COMPLIANCE |
| | WITH GUARDRAILS FOR HEIGHT (HEAD PROTECTION).COMMON |
| | PROBLEM TO ALL STAIRWAYS,11-4.4.2 HEAD ROOM. WALKS, |
| | HALLS, CORRIDORS, PASSAGEWAYS, AILES OR |
| | OTHER CIRCULATION SPACES SHALL HAVE 80 |
| | INCHES MINIMUM CLEAR HEAD ROOM (SEE |
| | FIGURE 8(A)). IF VERTICAL CLEARENCE OF |
| | AN AREAADJOINING AN ACCESSIBLE ROUTE IS |
| | REDUCED TO LESS THAN 80 IN. (NOMINAL |
| | DIMENSION), A BARRIER TO WARN BLIND OR VISUALLY-IMPARED |
| | PERSONS SHALL BE |
| | PROVIDED. (SEE FIGURE 8(C-1)). |
| | |
| | 13B) 2ND REQUEST, STAIR TOWER# 4 WINDOWS |
| | WITHIN 10'-0" OF TOWER OPENINGS SEE |
| | 1006.1.3.2 THE 2001 CODE DOES NOT |
| | PROVIDE A WATER CURTAIN AS AN EQUALENT. |
| | |
| | 13C) COMPLIED. |
| | |
| | 13D)THIS COMMENT TO BE RESTATED!!!SINCE |
| | THIS REVIEW THE CONFIGURATION OF LOFT |
| | UNITS VS PASSAGE TO THE PARKING GARAGE |
| | WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT |
| | TO THE ATTENTION OF THE BUILDING |
| | OFFICIAL. WE ARE SEEING MORE OF THIS |
| | TYPE DESIGN AND THE BUILDING OFFICIAL |
| | HAS RULED THAT THIS IS AN UNSAFE |
| | PRACTICE. THE OCCUPANTS LEAVE THE R-2 |
| | UNIT AND HAVE NO EXIT ACCESS CORRIDOR |
| | WHEN ENTERING THE PARKING GARAGE AREA. |
| | ALTHOUGH THE CODE DOESN'T QUOTE A |
| | SECTION, THAT AN EXIT ACCESS CORRIDOR IS |
| | REQUIRED THE BUILDING OFFICIAL IS USING |
| | THESE (2) CODE SECTIONS TO ENFORCE |
| | REQUIRING A EXIT ACCESS CORRIDOR TAKING |
| | THE OCCUPANT TO THE SAFETY OF AN EXIT. |
| | 103.6** REQUIREMENTS NOT COVERED BY |
| | THE CODE. ANY REQUIREMENTS NECCESAARY |
| | FOR THE STRENGTH, STABILITY OR PROPER |
| | OPERATION OF EXITING OR PROPOSED |
| | BUILDING, STRUCTURE, ELECTRIC, GAS, |
| | MECANICAL OR PLUMBING SYSTEM, OR FOR |
| | PUBLIC SAFETY, HEALTH AND GENERAL |
| | WELFARE , NOT SPECIFICALLY COVERED BY |
| | THIS OR OTHER TECHNICAL CODES, SHALL BE |
| | DETERMINED BY THE BUILDING OFFICIAL. IN |
| | ADDITION, OTHER REQUIREMENTS TO |
| | IMPLEMENT, CLARIFY OR SET PROCEDURES TO |
| | IMPLEMENT THIS CODE MAY BE SET IN |
| | WRITING BY THE BUILDING OFFICIAL AND BE |
| | POSTED ELECTRONICALLY FOR BUBLIC ACCESS. |
| | 1001.1.4 WHEN UNUSUALLY HAZARDOUS |
| | CONDITIONS EXIST, THE BUILDING |
| | OFFICIAL MAY REQUIRE ADDITIONAL MEANS |
| | OF EGRESS TO ASSURE THE SAFETY OF |
| | THE OCCUPANTS. |
| | |
| | NOTE: COMMENTS 13E-13H NOT FOUND IN |
| | COMMENT SHEET!!!!!!!!!!!!!!!! |
| | 13E) ON THE RIGHT SIDE OF 201- 202 THE |
| | COMMERCIAL AREA, IT APPEARS THERE IS A |
| | HANDICAPPED RAMP AND STAIRS, BUT NO |
| | SECTIONS THROUGH FOR FURTHER DETAILS? NO ELEVATIONS |
| | PROVIDED? IT APPEARS THAT THE |
| | EXHAUST FROM THE PARKING GARAGE IS |
| | WITHIN 5'-0" OF THE HANDICAPPED RAMP, IS |
| | THERE FLARINGS TO DIRECT EXHAUST FROM |
| | THE RAMP? |
| | |
| | 13F) HANDICAPPED SPACE WITHIN PARKING |
| | GARAGE NEEDS TO SHOW VAN ACCESSIBLE |
| | PARKING.11-4.1.2(5)(B) IN PARKING |
| | STRUCTURES, ONE IN EVERY EIGHT |
| | ACCESSIBLE SPACES, BUT NOT LESS THAN |
| | ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL |
| | BE DESIGNED AS REQUIRED BY 11-4.6.3. |
| | THE VERTICAL CLEARANCE AT SUCH SPACES |
| | SHALL COMPLY WITH ?11-4.6.5.ALL SUCH |
| | SPACES MAY BE GROUPED ON ONE LEVEL OF A |
| | PARKING STRUCTURE.WHEN SUCH SPACES ARE |
| | PROVIDED IN A PARKING STRUCTURE AND ONLY |
| | ONE IN EIGHT MEET THE HEIGHT REQUIREMENT |
| | OF 11-4.6.5, THEY SHALL BE DESIGNATED AS |
| | REQUIRED BY 11-4.6.4. |
| | |
| | 13G) PROVIDE MORE INFORMATION, PLANS |
| | INDICATE A TRASH ROOM # 103 BUT THERE IS |
| | AN AREA # 124 TRAASH AREA? EXPLAIN?THIS |
| | AREA IS NOT AUTOMOBILE STORAGE BUT A S1 |
| | STORAGE REQUIRING A 3HR SEPERATION. SEE |
| | TABLE 704.1. |
| | |
| | 13H) THE 2 STORY LOFT UNITS DO NOT HAVE |
| | EXIT ACCESS CORRIDORS TO THESE UNITS. |
| | EXIT ACCESS CORRIDORS WILL BE REQUIRED |
| | BECAUSE THE GARAGE ENTRY DOOR IS THE |
| | PRIMARY ENTRY DOOR COVERED UNDER FAIR |
| | HOUSING. SEE FAIR HOUSING P. 1.22 |
| | ELEVATORS MUST PROVDE ACCESS TO PRIMARY |
| | ENTRY FLOORS OF 2-STORY DWELLING IN |
| | ELEVATOR BUILDINGS. NOTED THE 2-STORY |
| | LOFT UNITS DO HAVE A FRONT DOOR WHERE |
| | STAIRS ARE PRESENT, THE ENTERIOR ENTRY |
| | DOOR IS CONSIDERED THE MAIN OR PRIMARY |
| | ENTRY DOOR. |
| | 1001.1.3 MEANS OF EGRESS SHALL CONSIST |
| | OF CONTINUOUS AND UNOBSTRUCTED PATHS OF |
| | TRAVEL TO THE EXTERIOR OF A BUILDING. |
| | MEANS OF EGRESS SHALL NOT BE PERMITTED |
| | THROUGH KITCHENS, CLOSETS, RESTROOMS AND |
| | "SIMILAR AREAS" NOR THROUGH ADJACENT |
| | TENANT SPACES. |
| | THE BUILDING OFFICIAL HAS REVIEWED |
| | THE LAYOUT OF THIS PLAN AND INTERPRETS |
| | THROUGH THE GARGE AS SIMILAR AREAS. |
| | 1001.1.4 WHEN UNUSUALLY HAZARDOUS |
| | CONDITIONS EXIST, THE BUILDING OFFICIAL |
| | MAY REQUIRE ADDITIONAL MEANS OF EGRESS |
| | TO ASSURE THE SAFETY OF THE OCCUPANTS |
| | |
| | 14) A.203 |
| | 14A) COMPLIED |
| | |
| | 14B) COMPLIED. |
| | |
| | 14C) COMPLIED. |
| | |
| | 14D) MAY BE REVISITED RESULTS OF 13D. |
| | |
| | 15) A.204 |
| | 15A) COMPLIED. |
| | |
| | 15B) COMPLIED. |
| | |
| | 15C) COMPLIED. |
| | |
| | 16) A.205 |
| | 16A) COMPLIED. |
| | |
| | 16B) COMPLIED. |
| | |
| | 16C) POOL PAVILION SINK DETAIL STILL |
| | DOESN'T INDICATE COUNTER HEIGTH. |
| | |
| | 16D) COMPLIED. |
| | |
| | 16E) COMPLIED. |
| | |
| | 16F)2ND REQUEST RESPONCE BY MEP |
| | ENGINEER? |
| | POOL DECK DRAINS WILL BE INSTALLED |
| | IN A RATED FLOOR, PROVIDE THE TYPE OF |
| | PIPE TO BE USED AND THE RATED ASSEMBLY |
| | FOR THIS INSTALATION. |
| | 705.6 PENETRATIONS OF HORIZONTAL |
| | ASSEMBLIES. ALL PENETRATIONS OF A FLOOR, FLOOR/CEILING |
| | ASSEMBLY, OR THE CEILING |
| | MEMBRANE OF A ROOF/CEILING ASSEMBLY |
| | SHALL BE PROTECTED BY A SHAFT ENCLOSURE |
| | IN ACCORDANCE WITH 705.2 OR SHALL COMPLY |
| | WITH ?705.6.1 THROUGH 705.6.4. |
| | 705.6.1 THROUGH-PENETRATIONS. THROUGH-PENETRATIONS |
| | OF FIRE RATED |
| | HORIZONTAL ASSEMBLIES SHALL COMPLY |
| | WITH 705.6.1.1 OR 705.6.1.2. |
| | |
| | 16G) NOTED |
| | |
| | 16H) NOTED. |
| | |
| | 16I) COMPLIED. |
| | |
| | 16J) COMPLIED. |
| | |
| | 17) A.206 |
| | |
| | 17A) COMPLIED. |
| | |
| | 17B) COMPLIED. |
| | |
| | 17C) COMPLIED. |
| | |
| | 17D) 2ND REQUEST, STAIRWELL# 2, IT |
| | APPEARS THAT A SHAFT IS DIRECTLY IN |
| | FRONT OF THE STAIRWELL. PROVIDE SECTION |
| | THROUGH GIVING WALL TYPE AND RATING? |
| | 705.2.2 SHAAFT ENCLOSURES. A SECTION |
| | THROUGH THE STAIRWELL WALL IS PROVIDED |
| | BUT NOT THE SHAFT ENCLOSURE. |
| | |
| | 18) A.208 |
| | 18A) COMPLIED. |
| | |
| | 18B) COMPLIED. |
| | |
| | 19) A.300 |
| | 19A) COMPLIED. |
| | |
| | 19B) COMPLIED. |
| | |
| | 20) A.403-A.406 |
| | 20A) COMPLIED. |
| | |
| | 20B) 2ND REQUEST, 1404.1.1 ARCHITECTURAL |
| | TRIM ON BUILDINGS OF TYPE I, II AND IV |
| | CONSTRUCTION NOT MORE THAN THREE |
| | STORIES OR 40 FT (12.2 M) HIGH MAY BE OF |
| | TYPE VI CONSTRUCTION, THIS MEANS FOAM |
| | CAN NOT BE USED SINCE THIS BUILDING IS |
| | OVER 40'-0". FOAM IS CONSIDERED A |
| | CONBUSTIBLE. |
| | |
| | 20C) COMPLIED. |
| | |
| | 20D) 2ND REQUEST, PRODUCT APPROVALS |
| | SUBMITTED WITH PERMIT APPLICATION AFTER |
| | OCTOBER 1, 2003 ARE REQUIRED TO COMPLY |
| | WITH THE FLORIDA PRODUCT APPROVAL |
| | SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 20E) COMPLIED. |
| | |
| | 20F) PRODUCT APPROVALS: |
| | A)WINDOWS/STOREFRONT FL APPROVAL |
| | NEEDED, MEETS PRESSURES |
| | B) WINDOWS: LAWSON SH-7500- REQUIRES |
| | SHUTTERS NO LARGE OR SMALL NISSLE |
| | TESTING ARCHITECT ALL GLAZING SHALL |
| | |
| | BE IMPACT RESISTANT. |
| | C) MULLIONS- NO REPORT SUBMITTED SPANS |
| | |
| | OF 23'-0" SPANDRIAL GLASS |
| | |
| | D) SLIDING GLASS DOORS-NO LARGE OR |
| | SMALL MISSLE IMPACT RATING |
| | |
| | E) LOUVERED DOORS- NO REPORT SUBMITTED |
| | |
| | F) STEEL DOORS- FIREDOOR CORP MISSING |
| | FLORIDA APPROVAL, PRESSURES GOOD |
| | FOR: |
| | 4080 FIREDOOR SINGLE OUTSWING |
| | 8080 FIREDOOR OUTSWING |
| | |
| | G) EXTERIOR OVERHEAD DOORS- NO REPORT |
| | SUBMITTED |
| | |
| | H) EXTERIOR HANDRAILS- NO REPORT |
| | SUBMITTED. |
| | |
| | I)STORM SHUTTERS- ARCHITECT INDICATES |
| | NO STORM SHUUTERS IMPACT GLASS BUT |
| | CONTRACTOR IS SUBMITTING PRODUCT |
| | APPROVALS REQUIRING SHUTTERS. |
| | |
| | J) TRUSS ANCHORS- NO REPORT SUBMITTED |
| | |
| | K) ROOFING ASSEMBLIES:BOTH MISSING |
| | FLORIDA APPROVAL: |
| | |
| | GAF MODIFIED BITUMEN ROOF SYSTEMS |
| | CONTRACTOR FAILED TO IDENTIFY WHICH SUB-SYSTEM TO |
| | BE USED, NOTE IF |
| | LITATION 7 OR 9 ALLOWED. IF |
| | LIMITATION# 7, PROVIDE CALCULATIONS |
| | |
| | FOR ENHANCED FASTENING. |
| | NOTE, VARIOUS ROOF DETAILS DO |
| | INDICATE RIGID INSULATION ON ROOF. |
| | |
| | MONIER TILE: THE STRUCTURAL |
| | CONTRACTOR TO IDENTIFY WHICH |
| | FASTENING SYSTEMS WILL BE USED FOR |
| | ZONES 1,2 &3. |
| | |
| | 20G)) AN INTERPRETATION FROM THE |
| | BUILDING OFFICIAL ON STORM SHUTTERS THAT |
| | ARE USED ON LARGE PROJECTS: |
| | QUESTION# 13) RECOGNIZING SUCH CONCERNS |
| | AS ABSENTEE OWNERS, OR CASES WHERE |
| | LONGER TIME AND EFFORT IS NECESSARY TO |
| | SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING |
| | RECOMMENDED OR IMPLEMENTED TO ENSURE |
| | THAT COMPLETE INSTALLATION OR SECURING |
| | IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE EVENT? |
| | |
| | IN MATTERS FLORIDA BUILDING CODE, 2001 |
| | EDITION, PROVIDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT |
| | REQUIREMENTS FOR ENSURING STABILITY, |
| | STRENGTH, AND PROPER OPERATION OF |
| | EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF |
| | SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDING, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION |
| | PLANS MUST BE SUBMITTED BY THE PROPERTY |
| | OWNERS OR MANAGING AGENTS FOR REVIEW BY |
| | THE CONSTRUCTION SERVICES DEPARTMENT. |
| | ANY SUCH PLAN SHALL INCLUDE, AT A |
| | MINIMUM, ON-SITE LOCATION OF SHUTTERS, |
| | PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS (SAID PARTIES MUST BE LOCATED |
| | WITHIN PALM BEACH COUNTY), TOTAL NUMBER |
| | OF OPENINGS TO BE PROTECTED AND TOTAL |
| | TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE |
| | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR |
| | LESS OF THE OFFICIAL NOTIFICATION BY THE |
| | NATIONAL WEATHER SERVICE OF A HURRICANE |
| | WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND |
| | THIS STANDARD) ARE NOT INTENDED TO |
| | PROHIBIT THE USE OF ALTERNATIVE |
| | MATERIALS AND METHODS, AND ALLOW THE |
| | BUILDING OFFICIAL TO REVIEW AND APPROVE |
| | ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY |
| | PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION, |
| | ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON |
| | A CASE-BY-CASE BASIS AND SHALL REQUIRE |
| | SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING |
| | THE ALTERNATE. |
| | |
| | QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE |
| | FOR USE ON VERY LARGE, MID |
| | OR HIGH-RISE STRUCTURES? |
| | |
| | NO, EXCEPT ON THE GROUND FLOOR. ON |
| | COMMERCIAL AND MULTI-UNIT RESIDENTIAL |
| | STRUCTURES, ABOVE THE FIRST LEVEL, |
| | IMPACT RESISTANT GLAZING OR PERMANENTLY |
| | AFFIXED PROTECTIVE DEVICES SHALL BE |
| | INSTALLED. PERMANENTLY AFFIXED |
| | PROTECTIVE DEVICES SHALL REQUIRE THE |
| | WRITTEN APPROVAL OF THE BUILDING |
| | OFFICIAL. |
| | |
| | 20H) PROVIDE STORM PANEL INFORMATION |
| | WITH INSTALLATION SCHEDULE AND KEY PLAN |
| | WITH SPECIFIC ANCHORS AND MOUNTING TO BE |
| | USED FOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 20I) FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE INSTALLATION |
| | SCHEDULE SUMMARIZING & IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL PRES- |
| | SURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 20J) COMPLIED. |
| | |
| | 21) A550/ A.650 |
| | 21A) THE PLANS STILL DO NOT IDENTIFY |
| | WHAT TYPE OF ROOF SHEATHING TO BE USED? |
| | TABLE 600- TYPE II BUILDING. |
| | |
| | 21B) COMPLIED. |
| | |
| | 21C) COMPLIED. |
| | |
| | 22) A.651 |
| | 22A) NOW SHEET A.650 DETAIL 21, PRODUCT |
| | APPROVALS ARE NOT REQUIRED FOR THIS |
| | SHUTTER, BUT THE ENGINEER WILL NEED TO |
| | PROVIDE CALCULATIONS FOR FIXED SHUTTER |
| | IN THE OPEN POSITION FOR 140 MPH WIND |
| | ZONE. |
| | |
| | 22B) COMPLIED. |
| | |
| | 22C) COMPLIED. |
| | |
| | 22D) COMPLIED. |
| | |
| | 23) A.701 |
| | 23A) COMPLIED. |
| | |
| | 23B) COMPLIED. |
| | |
| | 23C) COMPLIED. |
| | |
| | 24) A.704 |
| | 24A) COMPLIED. |
| | |
| | 24B) COMPLIED. |
| | |
| | 24C) COMPLIED. |
| | |
| | 25) A.801-A807,A.903 |
| | 25A) COMPLIED. |
| | |
| | 25B) COMPLIED. |
| | |
| | 26) A903/A.902/A.901 |
| | 26A) COMPLIED. |
| | |
| | 26B) COMPLIED. |
| | |
| | 27) A9.05 |
| | 27A) COMPLIED. |
| | |
| | 27B) COMPLIED. |
| | |
| | 27C) COMPLIED. |
| | |
| | 28) S-0.00 |
| | 28A) COMPLIED. |
| | |
| | 28B) COMPLIED. |
| | |
| | 28C) COMPLIED. |
| | |
| | 28D) COMPLIED. |
| | |
| | 28E) COMPLIED. |
| | |
| | 28F) COMPLIED. |
| | |
| | 29) S3.2 COMPLIED. |
| | |
| | 30) M0.2 |
| | |
| | 30A) 2ND REQUEST, |
| | ROOF TOP CONDENSING UNITS TO MEET |
| | THE CLEARENCE REQUIREMENTS: |
| | 1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | |
| | |
| | 30B) 2ND REQUEST, |
| | 1503.4.4 PROTECTION AGAINST DECAY & |
| | TERMITES. CONDENSATE LINES & ROOF DOWN |
| | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| | AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| | TENSIONS, OR SPLASH BLOCKS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |