Date Text
2006-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: THE
 PERSONAL SEAL, SIGNATURE, AND THE DATE
 THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 THE SIGNATURE IS A "STAMP OF THE
 SIGNATURE" AND AS SUCH IS NOT APPROVED.
 THERE IS NOT DATE ON THE SEAL WHEN IT
 WAS AFFIXED TO THE PLANS. FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055
 2. SHT A.003 DETAILS 1(A)(B)(C)(D),
 2(A)(B), & 4(A)(B(C)(D), WATER CLOSETS
 ADJACENT TO WALLS SHALL BE 1'6", NOT
 1'6" MINIMUM. THIS IS AN ABSOLUTE
 MEASUREMENT. SEE PAGES 6.3 & 6.5 FHA
 DESIGN MANUAL.
 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS
 PER REQUIREMENTS #6 & 7B FHA DESIGN
 MANUAL. THE CLEAR FLOOR SPACE FOR THE
 SHOWERS SHALL BE PARALLEL WITH THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 SEE PAGE 7.56 FHA DESIGN MANUAL.
 4. SHT A.003 UNIT DETAILS INDICATE
 "APPLICABLE TO UNITS A, B, C, D ETC. BUT
 FLOOR PLANS INDICATE UNITS C1, C2, C3,
 C4 ETC. PLEASE CORRELATE FLOOR PLANS
 WITH TYPICAL DETAILS. SECTION 104.2.1.
 5. SHT A.003 INDICATE WHICH POWDER ROOM
 DETAILS APPLY TO WHICH "TH" UNITS.
 SECTION 104.2.1.
 6. SHT A.003 DETAIL 1(C) PER HUD, THE
 BIDET HAS NO REQUIREMENTS, BUT THE BIDET
 SHALL NOT ENCROACH INTO THE CLEAR FLOOR
 SPACE OF THE WATER CLOSET.
 7. SHT A-106 BUSINESS OFFICE (553)
 ACCESS TO TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR
 BELOW THE EMPLOYEES REGULAR WORK AREA.
 SECTION 403.4.
 8. SHT A-108 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SF FOR EACH AREA DRAINED, ALONG WITH
 1/2 AREA OF ALL VERTICAL WALLS AND ANY
 AREA OF ROOF THAT DRAINS ONTO THE ROOF
 FROM ABOVE. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 9. SHTS A-801 THRU A-802C & A-808 ALL
 "TH" UNITS: PRIMARY LEVEL TO BE COVERED
 PER FHA DESIGN MANUAL. SHOW THE FLOOR
 PLAN FOR EACH TYPE OF "TH" UNIT WITH
 CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43
 & 7.47. ALSO SHOW MAX HIEGHT FOR LAV AT
 34" REQUIRED ON PAGE 7.52 FHA DESIGN
 MANUAL.
 10. SHTS A-803 THRU A-807A INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT -
 BATHROOM AS REQUIRED ON PAGES 7.34 &
 7.44 OF THE FHA DESIGN MANUAL.
 11. SUBMIT A FINISH SCHEDULE FOR PUBLIC
 - COMMON USE TOILET FACILITIES ON THE
 THIRD FLOOR. SECTIONS 1204.2 & 104.2.1.
 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS
 P1.1, P5.1.4, P5.1.5, & P6.1.4 ARE NOT
 SHOWN ON THE INDEX.- SHTS P2.5.1 &
 P2.5.2 DO NOT REFLECT THE SHEETS
 SUBMITTED. - SHTS P2.6.1, P2.6.2,
 P2.7.1, P2.7.2, P2.8.1, P2.8.2, P3.6.1
 WERE NOT SUBMITTED. - SHT P5.1.3 DOES
 NOT REFLECT THE INDEX, AND P5.1.5 &
 P5.1.6 SHOWN AS STORM, BUT SHEETS
 INDICATE SANT. SYSTEM. PLEASE CLARIFY.
 SECTION 104.2.1.
 13. ALL PLUMBING SHEETS: INDICATE RISER
 NUMBER FOR EACH SYSTEM THROUGH ALL
 FLOORS IN ORDER TO TRACE RISERS THROUGH
 BUILDING. - MATCH LINES ARE EITHER NOT
 SHOWN AT ALL OR THE INFORMATION OVERLAPS
 FROM ONE SHEET TO THE OTHER. PLEASE SHOW
 INFORMATION FOR THE EAST SECTION ON THE
 EAST SECTIONS AND THE INFORMATION FOR
 THE WEST SECTION ON THE WEST SECTIONS.
 SECTION 104.2.1.
 14. SHT P2.1.1 SD UP RISER NEXT TO 4"
 SAN DOWN (70DFU) SHOWS NO PIPING TO
 BUILDING DRAIN. SECTION 104.2.1.
 15. P2.1.2 FLOOR DRAINS IN THE TRASH
 ROOM/AREA AND IN THE CORRIDOR SHALL BE
 VENTED. SECTION 901.2.1. - CLEANOUTS IN
 THE BUILDING DRAIN ARE REQUIRED A
 MAXIMUM OF EVERY 100'. SECTION 708.3.2.
 - 3/4" CONDENSATE UP NOT SHOWN ON THE
 FLOOR ABOVE. - SANT. UP NOT SHOWN ON THE
 FLOOR ABOVE. (S.W. CORNER). SECTION
 104.2.1.
 16. SHT P2.2.2 INDICATES 2ND FLOOR -
 "SOUTH" SECTION. PLUMBING SHEET INDEX
 AND PREVIOUS FLOOR LEVELS INDICATE "WEST
 SECTION" PLEASE CORRELATE FLOOR PLANS
 AND INDEX. - TWO SETS OF STORM RISERS
 SHOWN ON THE FLOOR PLAN WERE NOT SHOWN
 ON PREVIOUS LEVEL FLOOR PLAN. - ONE SET
 OF STORM RISERS SHOWN ON THE FLOOR PLAN
 WERE NOT SHOWN ON THE FOLLOWING LEVEL
 FLOOR PLAN - ONE SANT. RISER SHOWN ON
 PREVIOUS & FOLLOWING FLOOR PLANS ARE NOT
 SHOWN ON FLOOR PLAN. - 1 FD4 SHOWN
 CONNECTING TO TWO SD RISERS. PLEASE
 CLARIFY. SECTION 104.2.1.
 17. SHT P2.3.1 SHOW THE LOCATION OF ALL
 SECONDARY DRAINS REQUIRED BY SECTION
 1107. SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY DRAINS PER 1106 & 1107. SEE
 COMMENT NUMBER 8.
 18. SHT P2.3.2 UNIT C-1B(313) PIPING
 DOES NOT REFLECT THE FLOOR PLAN
 FIXTURES. - UNIT C-2B(331) MASTER BATH
 WATER CLOSET, LAV, & SHOWER PIPING DOES
 NOT CONNECT TO A BRANCH LINE. - SANT.
 RISER #24 NOT SHOWN ON THE FLOOR BELOW.
 PLEASE CLARIFY. SECTION 104.2.1.
 19. SHT P2.4.1 INDICATES 4TH-6TH FLOORS
 EAST SECTION. PLUMBING SHEET INDEX AND
 SHEET I.D. BY TITLE BLOCK INDICATE 4TH
 FLOOR ONLY. PLEASE CORRELATE SHEETS AND
 INDEX. SECTION 104.2.1.
 20. SHT P2.5.1 INDICATE CONDENSATE PLAN
 NOTE NUMBER FOR AHU IN UNIT C-5A(520) -
 CONDO UNIT C-2(515) INDICATES PLAN NOTE
 #3. PLEASE CLARIFY. SECTION 104.2.1.
 21. SHT P2.5.2 CONDENSATE RISERS IN
 UNITS C-2G(529) & C-1A(523) INDICATES
 PLAN NOTE #5. PLEASE CLARIFY. SECTION
 104.2.1.
 22. SHT FOR 7TH FLOOR EAST SECTION
 DRAINAGE PLAN IS MIS-NUMBERED. - SHT FOR
 7TH FLOOR WEST SECTION DRAINAGE PLAN IS
 MIS-NUMBERED. ALSO CONDENSATE FOR
 RESIDENT STORAGE & CONDO UNIT C-1(730)
 SHOWS PLAN NOTE #2. PLEASE CLARIFY AND
 CORRELATE WITH SHT P0.1 PLUMBING SHEET
 INDEX. SECTION 104.2.1.
 23. SHT P2.7.1 SHOW THE LOCATION FOR ALL
 VENTS THRU ROOF AND INDICATE RISER
 NUMBER FOR EACH. -SUBMIT CALCULATION
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SEE COMMENT #8. SECTIONS 1106 & 1107 AND
 ALL SUBSECTONS.
 24. SHT P2.7.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SEE
 COMMENT #8. SECTIONS 1106 & 1107. -
 DRAINS FOR CCC UNITS SHALL BE LOCATED
 UNDER THE UNITS TO PREVENT TRIPPING
 HAZARDS AND TO KEEP STORM WATER FROM
 DRAINING INTO THE SANT. SYSTEM. ONE
 DRAIN FOR EACH UNIT REQUIRED. CITY CODE
 90-125(5).
 25. SHT P3.1.2 COLD WATER UP TO CHUTE
 WASHDOWN REQUIRES BACKFLOW PROTECTION.
 INDICATE METHOD OF PROTECTION. SECTION
 608.
 26. SHT P3.2.1 GAS LINE APPEARS TO EXIT
 & ENTER THE BLDG. PRIOR TO RISER UP TO
 POOL ROOM . PLEASE CLARIFY SEC 104.2.1.
 27. SHT P3.3.1 SEPARATE BACKFLOW
 PROTECTION REQUIRED FOR POOL FILL LINE.
 AN RPZV BACKFLOW IS REQUIRED. SECTION
 608.13.2.
 28. SHEET INDICATING WATER SUPPLY PLAN
 5TH FLOOR-WEST SECTION MIS-NUMBERED.
 PLEASE CLARIFY/CORRELATE WITH PLUMBING
 SHEET INDEX. SECTION 104.2.1.
 29. SHT INDICATING WATER SUPPLY PLAN 5TH
 FLOOR "NORTH" SECTION, PREVIOUS SHEETS
 WERE DESIGNATED AS "EAST" OR "WEST".
 THIS IS ALSO THE SECOND SHEET NUMBERED
 P3.5.1. - INDICATE WHAT DESIGNATION WSC2
 IS FOR. - NOTE STATES "SEE UNIT LAYOUTS
 ON SHEET P4.1". SHT P4.1 NOT SUBMITTED.
 SECTION 104.2.1.
 30. FIRST SHT P3.6.2 INDICATES WATER
 SUPPLY PLAN 6TH FLOOR "SOUTH" SECTION.
 EAST AND WEST WERE INDICATED PRIOR TO
 THIS. 2ND SHT WITH THE SAME NUMBER
 INDICATES "WEST" SECTION. PLEASE
 CLARIFY.SECTION 104.2.1.
 31. SHTS P3.6.1 & 2ND SHT P3.6.2
 INDICATE WHAT DESIGNATION WSC2 MEANS.
 SHT P4.1 REFERENCED HAS NOT BEEN
 SUBMITTED. PLEASE CLARIFY. SEC 104.2.1.
 32. SHTS P3.7.1 & P3.7.2 SHT P4.1
 REFERENCED HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 104.2.1.
 33. SHT P4.1.1INDICATES TWO "TYPICAL
 UNIT "C2" FOR THE WATER SUPPLY. ONLY ONE
 C2 FLOOR PLAN FOUND. PLEASE CLARIFY.
 SECTION 104.2.1.
 34. PLEASE SUBMIT WATER SUPPLY PLANS AND
 FLOOR PLANS FOR THE FOLLOWING UNITS:
 C-1A, C-2A, C-2B, C-2C, C-2D, C-2E,
 C-2F, C-2G, C-2H, C-5A, TH-1A, TH-1B,
 TH-1C, TH-1D, TH-2A, TH-2B, TH-2C.
 35. SHT P5.1.1 STATES "SANT DRAINAGE
 ISOMETRIC "WEST" SECTION". THIS DOES NOT
 REFLECT THE PLUMBING SHEET INDEX. -
 VENTS ARE REQUIRED ON THE FLOOR DRAINS
 IN THE TRASH ROOM/AREA & CORRIDOR.
 SECTION 901.2.1. - CLEANOUTS REQUIRED IN
 BUILDING MAX. 100'. SECTION 708.3.2. -
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN UPSTREAM OF SANT. RISER #22. -
 RISER DIAGRAMS AS INDICATED TO "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 104.2.1.
 36. SHT P5.1.2 STATES "SANITARY DRAINAGE
 ISOMETRICS - "EAST" SECTION. THIS DOES
 NOT REFLECT THE PLUMBING SHEET INDEX. -
 RISER DIAGRAMS AS INDICATED TO THE "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 CLEANOUTS FOR BUILDING DRAIN SHALL BE
 INSTALLED A MAXIMUM OF 100'. SECTION
 708.3.2. - CLEANOUT AT END OF RUN BY
 SANT. RISER #8 NOT SHOWN. - BLDG DRAIN
 DOES NOT REFLECT THE FLOOR PLAN WHERE
 THE DRAIN SPLITS TOWARD RISERS #1 &
 RISERS 4 THRU 8. SECTION 104.2.1.
 37. SHTS P5.1.3 THRU P5.1.5, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. ALL RISERS WITH VENT
 STACKS SHALL COMPLY. SECTION 903.4.
 38. SHT P5.1.3 SANT RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN. AN EXTRA LAV IS
 SHOWN. SECTION 104.2.1.
 39. SHT P5.1.3 SANT RISER #4 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWS A SHOWER,
 BUT A TUB IS ON FLOOR PLAN.- A VENT IS
 REQUIRED ON LAV IN THE MASTER BATH.
 SECTIONS 104.2.1 & 901.2.1.
 40. SHT P5.1.3 SANT RISER #6 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 & BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 41. SHT P5.1.3 SANT. RISER #8 DOES NOT
 REFLECT THE FLOOR PLAN FOR 2 BATHROOM
 GROUPS ALL FLOORS, AND THE FIRST
 BATHROOM GROUP 3RD FLOOR. SECTION
 104.2.1.
 42. SHT P5.1.4 SANT. RISER #9 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 43. SHT P5.1.4 SANT. RISER #10 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2. SECTION 104.2.1.
 44. SHT P5.1.4 SANT. RISER #12 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2, NOR WHERE THE RISERS & BRANCH
 LINES CONNECT TTO THE BUILDING DRAIN.
 SECTION 104.2.1.
 45. SHT P5.1.4 SANT. RISER #13 DOES NOT
 REFLECT THE FLOOR PLAN. 1ST & 2ND FLOORS
 ARE NOT SHOWN ON RISER. SECTION 104.2.1.
 46. SHT P5.1.4 SANT. RISER #14 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARM NEXT
 TO JAC2. SECTION 104.2.1.
 47. SHT P5.1.4 SANT. RISERS #'S 16 & 20
 DRAIN REQUIRED FOR EACH CCC UNIT ON THE
 ROOF LOCATED UNDERNEATH THE UNITS TO
 PREVENT A TRIPPING HAZARD AND TO PREVENT
 STORM WATER FROM ENTERING THE SANT.
 SYSTEM.
 48. SHT P5.1.4 SANT RISER #17 BATHROOM
 GROUPS DO NOT REFLECT THE FLOOR PLAN 3RD
 THRU 7TH FLOORS. SECTION 104.2.1.
 49. SHT P5.1.5 SANT. RISER #18 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 50. SHT P5.1.5 SANT. RISER #21 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 51. SHT P5.15 SANT. RISER #22 DOES NOT
 REFLECT THE FLOOR PLAN ON THE 1ST FLOOR
 AT TH W/C AND LAV. SECTION 104.2.1.
 52. SHT P5.1.5 SANT. RISER #23 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 53. SHTS P5.2.1, P5.2.2 & P5.2.3SHOWS
 CONDENSATE LINES CONNECTING TO NEAREST
 SANT. VENT. THIS IS NOT APPROVED.
 SECTION 901.2. - SECONDARY DRAINS ARE
 NOT SHOWN FOR THE POOL DECK LEVEL AS
 REQUIRED BY SECTION 1107. DISCHARGE
 SHALL BE ABOVE GRADE IN A LOCATION WHICH
 WOULD NORMALLY BE OBSERVED BY THE
 BUILDING OCCUPANTS OR MAINTENANCE
 PERSONAL, AND SEPARATE SYSTEMS ARE
 REQUIRED FOR PRIMARY AND SECONDARY
 DRAINS. SECTION 1107.2- SIZING OF
 STORM SYSTEM TO BE CHECKED AFTER
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS ARE SUBMITTED. SECTION 1106
 & 1107.
 54. SHT P6.1.1 SEPARATE RPZV BACKFLOW IS
 REQUIRED FOR THE IRRIGATION SYSTEM.
 SECTION 608.13.2.
 55. SHT P6.1.3 TYPICAL UNIT "C1" WATER
 HAMMER ARRESTOR REQUIRED ON ICE MAKER
 LINE, AND ON BOTH HOT & COLD LINES FOR
 THE W/M. SECTION 604.9
 56. SHT P6.1.3 TYPICAL UNIT "C2" WATER
 HAMMER ARRESTOR REQUIRED ON COLD WATER
 AT KITCHEN SINK FOR ICE MAKER. SECTION
 604.9.
 57. SHT P6.1.3 TYPICAL UNIT "C3" WATER
 HAMMER ARRESTOR REQUIRED ON COLD WATER
 AT KITCHEN SINK FOR ICE MAKER. - RISER
 DOES NOT REFLECT THE FLOOR PLAN.
 SECTIONS 104.2.1 & 604.9.
 58. SHT P6.1.3 TYPICAL UNIT "C5" DOES
 NOT REFLECT THE FLOOR PLAN. SECTION
 104.2.1.
 59. SHT P6.1.3 TYPICAL UNIT "TH-1" WATER
 HAMMER REQUIRED ON ICE MAKER LINE.
 SECTION 604.9.
 60. SHT P6.1.3 SHOWS 2 OTHER "TYPICAL
 UNITS C1". THESE DO NOT REFLECT ANY
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 61. SUBMIT WATER ISOMETRICS FOR THE
 FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B,
 C-2C, C-2D, C-2E, C-2F, C-2G, C-2H,
 C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2,
 TH-2A, TH-2B, TH-2C.
 62.SHT P6.1.4 GAS PIPING ISOMETRIC:
 SUBMIT APPROVED TABLES FOR SIZING PIPE
 PER FBC-2001 FUEL GAS CODE.
 63. SHT P6.1.4 PROVIDE MANUF.
 SPECIFICATION SHEETS FOR ALL PRV'S. -
 SHOW ALL VENT PIPING FOR PRV'S AND
 INDICATE THE MATERIAL REQUIRED FOR
 VENTS. SECTIONS 410.2 & 410.3. - A
 LISTED SHUTOFF VALVE SHAL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 SECTION 410.2(5) - POOL HEATER LINE
 DOWNSTREAM OF SHUTOFF VALVE INDICATES
 "MAXIMUM LENTH = 20'". MAXIMUM DISTANCE
 FROM APPLIANCES TO SHUTOFF VALVE IT 6'.
 SECTION 409.7. - PIPE DOWNSTREAM OF
 METER TO 1ST BRANCH LINE STARTS OFF
 1-1/4", THEN REDUCES TO 1", THEN
 INCREASES TO 1-1/4". PLEASE CLARIFY.
 PROVIDE THE FOLLOWING FOR APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS.
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 64. INFORMATIONAL: PLANS DO NOT APPEAR
 TO BE COMPLETE AT THIS TIME. MORE
 COMMENTS MAY BE FORTHCOMING UPON NEXT
 SUBMITTAL OF PLAN AND DEPENDING UPON
 COMMENT RESPONSES.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  